Power-Swing Blocking Scheme Based on Continuous and Higher-Order Incremental Quantities for Systems with Inverter-Based Resources

Henrik Johansson, Qianli Xing, Nathaniel Taylor, Xiongfei Wang

eess.SY ·submitted 2026-11-05 10:34 UTC · v1

Abstract

Conventional power-swing blocking (PSB) schemes for distance protection face new and emerging challenges as the penetration levels of inverter-based resources (IBRs) increase. Several papers highlight interoperability issues concerning faster power swings and unconventional impedance trajectories. Revised relay settings are proposed in attempts to deal with the problems. However, the blinder-based PSB methodology suffers from being dependent on the speed of the apparent impedance trajectory over the tiny region between the blinders, making it difficult to distinguish between fast swings and faults. Moreover, blinders have the inherent limitation that they cannot operate if the measured impedance is inside the blinders when the fault is cleared and immediately enters the distance zones during the first swing cycle - an issue often overlooked in the current literature. This paper proposes a novel PSB scheme based on higher-order incremental quantities (IQs) for difficult swing scenarios with IBRs and synchronous generators (SGs). PSCAD/EMTDC simulations of an SG and an implemented grid-forming (GFM) inverter validate its superior performance compared to conventional dual-blinder PSB schemes. The impacts of GFM inverters on the impedance measured by distance relays during the fault-to-swing transition and first power swing cycle are also discussed.

Comment
9 pages, 11 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems

eess.SY ·2026-11-02 ·Alexander Novikov, Luis A. Garcia-Reyes, Anup Joshi, Ahmar Farooque, Junaid Khalid +1 more
published similarity 0.56
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

The decarbonization of the energy sector, driven by the Paris Agreement and the European Green Deal, is increasing the share of renewable energy sources (RES) in power systems. Unlike traditional systems, RES-based systems rely on power electronic converters, which creates unprecedented challenges for reliability and resilience. The future power system is expected to combine a low-level AC layer with an upper-level High Voltage Direct Current (HVDC) backbone, which requires new understanding of fault protection, stability, and interaction between AC and DC components, as well as new models and simulation tools. This is especially critical in systems moving towards 100 percent converter-based generation. Protection systems detect, locate, and isolate faults to protect assets while the rest of the system keeps operating. Traditionally, they rely on the large fault currents supplied by synchronous machines. In modern systems, converter controls limit the fault current contribution to about 120 percent of rated current, so relays that distinguish faults from normal overcurrents based on current level may operate incorrectly. In addition, inverter-based resources (IBR) may not inject enough negative and zero sequence current for directional relays to work properly, and converters hold the voltage at a fixed value only within their reach, beyond which it drops quickly. As a result, existing protection schemes may not provide the expected accuracy and reliability. This report reviews the protection challenges identified in recent academic literature for power systems with high shares of converter-based resources. It covers the specific characteristics of RES, the challenges for protection with intelligent electronic devices (IED), the challenges of converter control during faults, and the main solutions proposed in research over the last decade.

0.49

Local Energy Function-Based Power System Transient Stability Analysis with Grid Forming and Grid Following Inverters

eess.SY ·2026-09-06 ·Yingyi Tang, Junbo Zhao, Baosen Zhang
similarity 0.55
Abstract

The widespread deployment of inverter-based resources (IBRs) is reshaping power system dynamics by their control strategies. Grid-following (GFL) and grid-forming (GFM) inverters are expected to co-exist from now on. However, ensuring the transient stability of such systems remains a critical and underexplored challenge. In this paper, a comprehensive transient stability analysis of the mixed-GFM-GFL inverter system is conducted using a newly derived local energy function. The transient stability analysis model of the system is first derived to reveal the dynamic interactions between GFL and GFM inverters during transient responses. A local energy function is then proposed for analytical transient stability assessment. Instead of ignoring or making harsh assumptions on inverters' coupled damping effect, the proposed local energy function carefully addresses its impact on system transient stability by locally bounding the region where the system's energy dissipation property holds. Such a property fully considers the combined damping effect of GFL and GFM inverters. The derived critical energy and stability index provide a fast and quantitative transient stability assessment. Furthermore, the adverse impact of insufficient damping of GFM inverters on system transient stability is thoroughly investigated. The effectiveness of the proposed method is validated on the modified IEEE 14-bus system with mixed GFL and GFM inverters, and the numerical simulation results further demonstrate the small conservativeness of the proposed method.

0.24

Control-Layer Interpretation of Reactive Power Recovery Limits in EMT-RMS Model Benchmarking of Inverter-Based Resources

eess.SY ·2026-10-30 ·Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
publishedbenchmark similarity 0.55
Abstract · Accepted for presentation at IEEE PES Grid Edge Technologies 2027, April 19-22, 2027, Salt Lake City, Utah, USA.5 pages, 3 figures, 6 tables

EMT--RMS benchmarking is widely used to verify cross-platform consistency of inverter-based resource (IBR) dynamic models. This paper examines a 200 MW anonymized IBR represented in PSCAD and PSS/E. The EMT model separates inverter electrical capability from a plant-level power plant controller (PPC) recovery target, whereas the RMS model represents these functions through REECC and REPCA parameters. Directly assigning the PPC target of $\pm 0.2764$ pu to REPCA hard reactive limits is initialization-inconsistent at the original lagging operating point because the initial reactive command is 0.396273 pu. A second, near-unity-power-factor operating point initializes successfully with the same diagnostic limit, demonstrating that the conflict is operating-point dependent. Using the non-conflicting capability mapping removes the original hard-limit conflict, but the benchmark still shows 18.5--30.2 MVAr post-event POI reactive-power differences from PSCAD. A one-at-a-time REPCA $K_c$ sensitivity under matched benchmark initial conditions further shows that RMS recovery is parameter- and limit-dependent: at $K_c=0.05$ and 0.10 the aggregate machine reactive output reaches the configured capability bounds, while $K_c=0.15$ moves VDOWN, VUP, and HVRT off those bounds and changes their settled POI reactive power by 8.94, 18.00, and 3.17 MVAr, respectively. Machine-to-POI accounting further shows why machine-side saturation need not reproduce the POI-level PPC recovery magnitude. The results distinguish initialization feasibility from recovery equivalence and provide a control-layer diagnostic workflow beyond waveform comparison.

0.41

Evaluating Grid Strength with Rising Penetration of Inverter Based Resources

eess.SY ·2026-09-22 ·Mohammed N. Khamees, Gad Ilunga, Zhongxia Zhang, Richard E. Tuck
published similarity 0.55
Abstract · Accepted for publication in 2026 CIGRE USNC Grid of the Future (GOTF) Symposium

Over the years, Dominion Energy Virginia (DEV) has experienced recurring power quality disturbances, including voltage and power oscillations, particularly in areas with significant inverter-based generation. While these phenomena suggest a potential relationship to system strength, no definitive correlation has yet been established. This paper presents methodologies for assessing system strength across the DEV network and identifying regions that may be vulnerable to such disturbances. To this end, three grid-strength metrics are evaluated: the Simple Short-Circuit Ratio (SSCR), the Weighted Short-Circuit Ratio (WSCR), and the Composite Short-Circuit Ratio (CSCR). Historical event data will be analyzed using steady-state snapshots from DEV's proprietary Analysis on Demand (ANODE) platform, which provides 10-minute interval load-flow data. These snapshots will be processed using a developed software tool to compute system strength metrics. The analysis will investigate potential correlations between system strength and observed disturbances. Where such correlations are identified, the study will further evaluate the impact of deploying synchronous condensers (SynCons) as a mitigation strategy.

0.31

The Race between Protection and Control: Fast Reactive Reserves Against Overvoltage Cascade

eess.SY ·2026-11-14 ·Abdallah Alalem Albustami, Mads Almassalkhi, Ahmad F. Taha
similarity 0.55
Abstract

In an overvoltage cascade, each relay trip removes reactive power absorption and raises the voltage at other plants, often faster than controls can act. This paper determines how much fast reactive power to hold, where, and how fast, so that no contingency trips a plant. A trip certificate allows a relay to pick up if it resets before its delay expires, making the sizing a linear program. A necessary condition identifies the relays that only preventive action can protect, and the reserve of one control decreases with the relay delay and increases with its latency. In nonlinear simulations of four systems, the corrective actions prevent every trip within the analysis window for relays without reset hysteresis, and each plant's own set point is the most effective reserve. A 2\% hysteresis or a small error in the relay voltage can change the reserve as much as the relay delay.

0.24

On the Achievable Inertia Constant of Inverter Based Resources

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.55
Abstract · Under Review in IEEE Transactions on Power Systems

As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,λ,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $λ$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $κ$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(λ,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.

0.28

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.55
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.22

EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS

eess.SY ·2026-10-30 ·Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
similarity 0.54
Abstract · 6 pages, 4 figures. Submitted to the 2027 IEEE Texas Power and Energy Conference (TPEC 2027)

Low-voltage ride-through (LVRT) forces a grid-following inverter to allocate finite converter current between active- and reactive-current objectives. This paper uses a PSCAD electromagnetic-transient (EMT) representation of an aggregated battery energy storage system (BESS) to quantify how short-circuit ratio (SCR) and grid impedance X/R ratio alter that tradeoff. Active-current priority and reactive-current priority are compared for five paired grid conditions under the same 150-ms balanced three-phase fault, with pre-fault active power approximately 0.84 pu, POI reactive-power exchange near 0 pu, and a 1.0-pu dq-current limit. Fundamental positive-sequence voltage and power are reconstructed from 100-$μ$s three-phase EMT outputs. Across the fixed-fault SCR sweep, the Q-priority late-fault voltage advantage increases from 0.046 pu in the strongest tested grid to 0.129 pu in the weakest; the weakest P-priority case also shows active-power reversal and a pronounced controller-frequency excursion. At fixed SCR, changing X/R produces a smaller increase from 0.092 to 0.112 pu, mainly through reduced P-priority voltage support. Because the common physical fault also deepens the passive retained-voltage condition as SCR decreases, the SCR result is interpreted as a fixed-fault grid-strength sensitivity rather than a constant-sag comparison. Grid strength is the larger sensitivity in the tested matrix, while X/R remains an additional modifier under the studied fault conditions.

0.37