On the Achievable Inertia Constant of Inverter Based Resources

Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou

eess.SY ·submitted 2026-09-28 08:24 UTC · v1

Abstract

As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,λ,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $λ$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $κ$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(λ,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.

Comment
Under Review in IEEE Transactions on Power Systems

Closest papers

Nearest neighbours by meaning across the whole index.

Frequency Measurement Practices for Inertia Assessment in Inverter Based Resources Dominated Power Systems

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.63
Abstract · Under Review in IEEE Transactions on Power Systems

Transmission system operators and protective relays compute the rate of change of frequency (RoCoF) from frequency averaged over tens to hundreds of milliseconds, as standards and grid codes specify. Any response delivered inside that window lowers the measured RoCoF, so the inferred inertia depends on the window and the responses in service. This paper defines the windowed inertia estimate and derives an exact identity the system inertia divided by one minus the fraction of the disturbance energy delivered inside the window and a closed-form prediction that applies the same estimator to the trajectory of a linear response model. Eleven IEEE 9-bus RMS runs synchronous, grid-following and grid-forming configurations, disturbance sizes and parameter sweeps are reproduced by that model, and the identity closes on the measured response powers. Fast frequency response inflates the estimate most: at 500 ms a grid-following system with 20 % less synchronous inertia reports the same value as the all-synchronous system, the grid-forming system a higher one. On a reduced Greek transmission system the 500ms estimate exceeds the inertia by 17-26%, and a scenario with 10% less synchronous inertia reports more than the all-synchronous scenario's inertia. Operators can thus compute what their measurement reports.

0.26

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

eess.SY ·2026-11-13 ·Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu +1 more
hot direction similarity 0.62
Abstract · This paper has 6 pages with 5 figures. The target journal will be determined at a later stage

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

0.27

Nodal Inertia Pricing for RoCoF Security with Integration of Synchronous and Virtual Resources

eess.SY ·2026-10-24 ·Bomiao Liang, Yu Yang, Licheng Wang, Lei Wan, Dipti Srinivasan +3 more
similarity 0.61
Abstract

Frequency regulation is becoming a more significant challenge in the undergoing low-carbon transition of modern power systems, which is heavily rely on system inertia provision. In the context of market-based energy allocation, reasonable valuation of the system inertia is crucial to its procurement, namely a worthy price should be determined for inertia providers. However, current research on the value of inertia remains insufficient, particularly during the initial phase immediately following a contingency, a critical period when the system primarily relies on the inherent inertia from conventional units and pre-engaged virtual inertia resources. Furthermore, it is found in existing studies that the Center of Inertia (COI) models exhibit significant deviations from actual physical conditions. For market-oriented reforms that explore individual differences, COI models also fail to capture the heterogeneous contributions of inertia at different nodes to system security. Given these circumstances, this paper proposes a nodal inertia pricing mechanism via a day-ahead unit commitment and inertia co-optimization model with nodal resolution. Following the proposed pricing scheme, the day- or hour-ahead inertia provision is monetized and promoted, providing regional guidance to units and devices with virtual inertia provision, which is further verified by simulation results of the South East Australia Power System.

0.21

Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

eess.SY ·2026-11-02 ·Alan Valadez, George Weiss, Chunjiang Jia, Chong Ng
published similarity 0.61
Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

0.62

Control-Layer Interpretation of Reactive Power Recovery Limits in EMT-RMS Model Benchmarking of Inverter-Based Resources

eess.SY ·2026-10-30 ·Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
publishedbenchmark similarity 0.59
Abstract · Accepted for presentation at IEEE PES Grid Edge Technologies 2027, April 19-22, 2027, Salt Lake City, Utah, USA.5 pages, 3 figures, 6 tables

EMT--RMS benchmarking is widely used to verify cross-platform consistency of inverter-based resource (IBR) dynamic models. This paper examines a 200 MW anonymized IBR represented in PSCAD and PSS/E. The EMT model separates inverter electrical capability from a plant-level power plant controller (PPC) recovery target, whereas the RMS model represents these functions through REECC and REPCA parameters. Directly assigning the PPC target of $\pm 0.2764$ pu to REPCA hard reactive limits is initialization-inconsistent at the original lagging operating point because the initial reactive command is 0.396273 pu. A second, near-unity-power-factor operating point initializes successfully with the same diagnostic limit, demonstrating that the conflict is operating-point dependent. Using the non-conflicting capability mapping removes the original hard-limit conflict, but the benchmark still shows 18.5--30.2 MVAr post-event POI reactive-power differences from PSCAD. A one-at-a-time REPCA $K_c$ sensitivity under matched benchmark initial conditions further shows that RMS recovery is parameter- and limit-dependent: at $K_c=0.05$ and 0.10 the aggregate machine reactive output reaches the configured capability bounds, while $K_c=0.15$ moves VDOWN, VUP, and HVRT off those bounds and changes their settled POI reactive power by 8.94, 18.00, and 3.17 MVAr, respectively. Machine-to-POI accounting further shows why machine-side saturation need not reproduce the POI-level PPC recovery magnitude. The results distinguish initialization feasibility from recovery equivalence and provide a control-layer diagnostic workflow beyond waveform comparison.

0.41

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.58
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS

eess.SY ·2026-10-30 ·Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
similarity 0.57
Abstract · 6 pages, 4 figures. Submitted to the 2027 IEEE Texas Power and Energy Conference (TPEC 2027)

Low-voltage ride-through (LVRT) forces a grid-following inverter to allocate finite converter current between active- and reactive-current objectives. This paper uses a PSCAD electromagnetic-transient (EMT) representation of an aggregated battery energy storage system (BESS) to quantify how short-circuit ratio (SCR) and grid impedance X/R ratio alter that tradeoff. Active-current priority and reactive-current priority are compared for five paired grid conditions under the same 150-ms balanced three-phase fault, with pre-fault active power approximately 0.84 pu, POI reactive-power exchange near 0 pu, and a 1.0-pu dq-current limit. Fundamental positive-sequence voltage and power are reconstructed from 100-$μ$s three-phase EMT outputs. Across the fixed-fault SCR sweep, the Q-priority late-fault voltage advantage increases from 0.046 pu in the strongest tested grid to 0.129 pu in the weakest; the weakest P-priority case also shows active-power reversal and a pronounced controller-frequency excursion. At fixed SCR, changing X/R produces a smaller increase from 0.092 to 0.112 pu, mainly through reduced P-priority voltage support. Because the common physical fault also deepens the passive retained-voltage condition as SCR decreases, the SCR result is interpreted as a fixed-fault grid-strength sensitivity rather than a constant-sag comparison. Grid strength is the larger sensitivity in the tested matrix, while X/R remains an additional modifier under the studied fault conditions.

0.37

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.57
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.29