Control-Layer Interpretation of Reactive Power Recovery Limits in EMT-RMS Model Benchmarking of Inverter-Based Resources

Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti

eess.SY ·submitted 2026-10-30 03:59 UTC · v1
publishedbenchmark

Abstract

EMT--RMS benchmarking is widely used to verify cross-platform consistency of inverter-based resource (IBR) dynamic models. This paper examines a 200 MW anonymized IBR represented in PSCAD and PSS/E. The EMT model separates inverter electrical capability from a plant-level power plant controller (PPC) recovery target, whereas the RMS model represents these functions through REECC and REPCA parameters. Directly assigning the PPC target of $\pm 0.2764$ pu to REPCA hard reactive limits is initialization-inconsistent at the original lagging operating point because the initial reactive command is 0.396273 pu. A second, near-unity-power-factor operating point initializes successfully with the same diagnostic limit, demonstrating that the conflict is operating-point dependent. Using the non-conflicting capability mapping removes the original hard-limit conflict, but the benchmark still shows 18.5--30.2 MVAr post-event POI reactive-power differences from PSCAD. A one-at-a-time REPCA $K_c$ sensitivity under matched benchmark initial conditions further shows that RMS recovery is parameter- and limit-dependent: at $K_c=0.05$ and 0.10 the aggregate machine reactive output reaches the configured capability bounds, while $K_c=0.15$ moves VDOWN, VUP, and HVRT off those bounds and changes their settled POI reactive power by 8.94, 18.00, and 3.17 MVAr, respectively. Machine-to-POI accounting further shows why machine-side saturation need not reproduce the POI-level PPC recovery magnitude. The results distinguish initialization feasibility from recovery equivalence and provide a control-layer diagnostic workflow beyond waveform comparison.

Comment
Accepted for presentation at IEEE PES Grid Edge Technologies 2027, April 19-22, 2027, Salt Lake City, Utah, USA.5 pages, 3 figures, 6 tables

Closest papers

Nearest neighbours by meaning across the whole index.

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.65
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

EMT Assessment of SCR and X/R Effects on Current-Priority-Dependent LVRT Response of a Grid-Following BESS

eess.SY ·2026-10-30 ·Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
similarity 0.63
Abstract · 6 pages, 4 figures. Submitted to the 2027 IEEE Texas Power and Energy Conference (TPEC 2027)

Low-voltage ride-through (LVRT) forces a grid-following inverter to allocate finite converter current between active- and reactive-current objectives. This paper uses a PSCAD electromagnetic-transient (EMT) representation of an aggregated battery energy storage system (BESS) to quantify how short-circuit ratio (SCR) and grid impedance X/R ratio alter that tradeoff. Active-current priority and reactive-current priority are compared for five paired grid conditions under the same 150-ms balanced three-phase fault, with pre-fault active power approximately 0.84 pu, POI reactive-power exchange near 0 pu, and a 1.0-pu dq-current limit. Fundamental positive-sequence voltage and power are reconstructed from 100-$μ$s three-phase EMT outputs. Across the fixed-fault SCR sweep, the Q-priority late-fault voltage advantage increases from 0.046 pu in the strongest tested grid to 0.129 pu in the weakest; the weakest P-priority case also shows active-power reversal and a pronounced controller-frequency excursion. At fixed SCR, changing X/R produces a smaller increase from 0.092 to 0.112 pu, mainly through reduced P-priority voltage support. Because the common physical fault also deepens the passive retained-voltage condition as SCR decreases, the SCR result is interpreted as a fixed-fault grid-strength sensitivity rather than a constant-sag comparison. Grid strength is the larger sensitivity in the tested matrix, while X/R remains an additional modifier under the studied fault conditions.

0.37

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.63
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.25

EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data Centers

eess.SY ·2026-11-05 ·Junyuan Zheng, Salish Maharjan, Min Lwin, Soummya Roy, Zhaoyu Wang +3 more
similarity 0.61
Abstract

Large data centers are emerging as power-electronic loads whose response to grid voltage disturbances can affect bulk-system stability. This paper presents the composition and control characteristics of a proprietary electromagnetic transient (EMT) model of a modern data center comprising an uninterruptible power supply (UPS) with battery energy storage, induction-motor cooling loads, a computer room air handler (CRAH) driven by a variable-frequency drive (VFD), and an aggregated server load. A voltage-based state machine coordinates three aspects of the facility response: the UPS operating mode (eco, double conversion, or battery), the supply path of the CRAH, and a ramped reconnection of the grid-side UPS converter after the disturbance clears. A 100 MW facility is implemented in PSCAD/EMTDC and benchmarked against the PSSE PERC1 aggregate data center model under a symmetrical three-phase fault and low- and high-voltage ride-through (LVRT/HVRT) events. The two models agree closely in their voltage and active-power trajectories, while the EMT model also resolves the converter and motor-reacceleration transients that the phasor-domain model cannot.

0.50

Open-Source Multi-Fidelity EMT Modeling of Data Center Loads for Power System Studies

eess.SY ·2026-11-06 ·Xingyu Zhao, Yingyi Tang, Junbo Zhao
code/data similarity 0.61
Abstract

Characterizing data center-grid interactions under rapid load fluctuations requires electromagnetic transient (EMT) models that capture fast converter and control dynamics. This paper develops a modular multi-fidelity EMT model of data center loads in PSCAD. The modular design supports flexible assembly of subsystem models for different power supply configurations. The multi-fidelity design incorporates switching models, average-converter models, and reduced-order models to balance simulation accuracy and computational efficiency according to analysis needs. The model also provides a systematic controller tuning procedure and supports control mode switching. Comparative simulations demonstrate how this data center load model responds to both grid-side and load-side disturbances and assess the accuracy and computational efficiency of models with three fidelity levels. The model is publicly available on GitHub.

0.34

Comparative Assessment of Frequency Scans using EMT and RMS Models

eess.SY ·2026-08-27 ·Clea Bürgel, Gustavo Valverde, Gabriela Hug
similarity 0.59
Abstract

Frequency scans of inverter and grid impedances are crucial for assessing small-signal stability and system strength in inverter-dominated power systems. This paper compares frequency-scan results for several generating units, including a synchronous generator, grid-following, and grid-forming inverters, using fully dq electromagnetic transient and root-mean-square (RMS) models in Simulink. The scans are performed for the same device rating and operating point. Frequency scans and time-domain simulations show that the RMS models are valid only at low frequencies. We find that the current-controlled grid-forming inverter is more difficult to represent in RMS than the voltage-controlled grid-forming inverter. However, including the inner voltage-control loops improves the accuracy of the RMS representation. The paper also investigates the influence of generator and grid impedance on the total system impedance seen from the point of common coupling and relates the oscillatory modes and zeros of the system to peaks and dips in the first and second singular values of the system impedance, respectively.

0.22

On the Achievable Inertia Constant of Inverter Based Resources

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.59
Abstract · Under Review in IEEE Transactions on Power Systems

As inverter-based resources (IBRs) displace synchronous generators, the inertia they can actually contribute to the grid becomes a critical planning parameter. Unlike synchronous machines, this contribution is bounded simultaneously by the available energy reserve, the converter power rating combined with voltage ride-through (VRT) obligations, and the inertia-emulation control scheme with its activation delay. This paper derives each bound in closed form and combines them into a unified envelope $\Heff(t,λ,V_g)=\min(\HE,\HP,\HC)$, which uses parameters accessible to the system operator to quantify how much inertia a plant can provide at a given loading $λ$, grid voltage $V_g$, and time $t$ after a disturbance. The analysis shows that below a loading-dependent critical voltage, VRT reactive-current priority does not leave active-current headroom for inertial power injection; that the converter overload ratio $κ$ matters mainly during voltage dips; and that de-loading yields a linear, quantifiable inertia gain, while collocated energy storage (ESS) removes the source-coupling constraint, making grid-following (GFL) and grid-forming (GFM) plants with storage equivalent post-activation, up to the GFL activation-delay discount within short RoCoF measurement windows. Simulations on the IEEE 9-bus system confirm the framework and motivate a two-dimensional inertia capability curve $H(λ,V_{g,\min})$ as a grid-code instrument analogous to the P--Q diagram of synchronous generators.

0.28

Unifying Power Flow and Electromagnetic Transient Modeling

eess.SY ·2026-09-08 ·Tina Gao, Aayushya Agarwala, Timothy McNamara, Lawrence Pileggi
similarity 0.59
Abstract

Grid tools are separated by timescales: steady-state analysis is performed by power flow (PF), whereas the fastest dynamics are captured by electromagnetic transient (EMT) simulation. Although operating at varying timescales, different tools should produce consistent results when analyzing the same grid conditions. However, the PF steady-state solution does not match the time-to-infinity EMT response. This mismatch exists because simplified device models in PF are inconsistent with the "ground truth" EMT models derived from first principles. As inverter-based resources (IBRs) and data centers strip away inertia and operating reserves, approximations used in PF risk grid security by missing violations. To address this, we introduce a steady-state framework that uses full-physics EMT models for high-fidelity steady-state grid analysis. The challenge lies in systematically formulating algebraic frequency-domain representations of dynamic power devices that are naturally described in state-space form. Our tool, SALT (Steady-state After Last Transients), constructs steady-state representations that exactly capture grid device physics when embedded into transmission networks. The approach exploits the structural properties of power device models and the single-harmonic, balanced nature of the transmission system. Results demonstrate SALT achieves EMT steady-state accuracy while delivering a 1x10^6 times speedup. We demonstrate that SALT can capture security threats in contingency scenarios without exception --- whereas PF-based analyses reported 75% fewer rated line violations, 18% fewer Q-limit violations, and 7% fewer voltage violations.

0.20