EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data Centers

Junyuan Zheng, Salish Maharjan, Min Lwin, Soummya Roy, Zhaoyu Wang, Wenlong Shi, Feng Qiu, Rajarshi Roychowdhury

eess.SY ·submitted 2026-11-05 19:06 UTC · v1

Abstract

Large data centers are emerging as power-electronic loads whose response to grid voltage disturbances can affect bulk-system stability. This paper presents the composition and control characteristics of a proprietary electromagnetic transient (EMT) model of a modern data center comprising an uninterruptible power supply (UPS) with battery energy storage, induction-motor cooling loads, a computer room air handler (CRAH) driven by a variable-frequency drive (VFD), and an aggregated server load. A voltage-based state machine coordinates three aspects of the facility response: the UPS operating mode (eco, double conversion, or battery), the supply path of the CRAH, and a ramped reconnection of the grid-side UPS converter after the disturbance clears. A 100 MW facility is implemented in PSCAD/EMTDC and benchmarked against the PSSE PERC1 aggregate data center model under a symmetrical three-phase fault and low- and high-voltage ride-through (LVRT/HVRT) events. The two models agree closely in their voltage and active-power trajectories, while the EMT model also resolves the converter and motor-reacceleration transients that the phasor-domain model cannot.

Closest papers

Nearest neighbours by meaning across the whole index.

Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control

eess.SY ·2026-11-14 ·Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah +2 more
hot direction similarity 0.77
Abstract · 5 pages, 7 figures

The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.

0.22

Open-Source Multi-Fidelity EMT Modeling of Data Center Loads for Power System Studies

eess.SY ·2026-11-06 ·Xingyu Zhao, Yingyi Tang, Junbo Zhao
code/data similarity 0.77
Abstract

Characterizing data center-grid interactions under rapid load fluctuations requires electromagnetic transient (EMT) models that capture fast converter and control dynamics. This paper develops a modular multi-fidelity EMT model of data center loads in PSCAD. The modular design supports flexible assembly of subsystem models for different power supply configurations. The multi-fidelity design incorporates switching models, average-converter models, and reduced-order models to balance simulation accuracy and computational efficiency according to analysis needs. The model also provides a systematic controller tuning procedure and supports control mode switching. Comparative simulations demonstrate how this data center load model responds to both grid-side and load-side disturbances and assess the accuracy and computational efficiency of models with three fidelity levels. The model is publicly available on GitHub.

0.34

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.74
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.22

Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems

eess.SY ·2026-09-02 ·Pengyu Ren, Wei Sun, Fei Teng
similarity 0.73
Abstract

Large data centers are emerging as concentrated, power-electronic grid loads whose abrupt disconnection or transfer to on-site backup supply during voltage disturbances can remove large demand from the power system, and may create a system-level stability problem. Their interconnection feasibility therefore depends not only on steady-state thermal and voltage limits, but also on whether internal power-conditioning systems can maintain IT service while limiting customer-initiated load reduction. This paper presents a voltage ride-through (VRT)-aware data center and grid co-planning framework that couples transmission-level fault simulation with an internal data center ride-through model. Python-based dynamic simulations generate point-of-interconnection (POI) voltage trajectories under selected network faults, and the resulting waveforms drive an internal model incorporating IT and cooling-load dynamics, DC-link, Uninterruptible Power Supply (UPS) response, and converter apparent power limits. The IEEE 118-bus case study shows that internal VRT capability can become a binding interconnection constraint: steady-state planning alone can overestimate feasible data center capacity, whereas increased UPS converter headroom progressively restores hosting capacity. Under the reduced-order response models studied, the grid-forming mode provides greater ride-through margin than the current-limited grid-following mode under the same network fault conditions. The results further show that VRT constraints can materially change both the total hosting capacity of data centers and its spatial allocation across candidate interconnection buses.

0.16

Can STATCOM and UPS-Based Voltage Support Mitigate Fault-Induced Reductions in AI Data Center Grid Power Draw?

eess.SY ·2026-11-12 ·Ziang Liu, Yimeng Liu, Francis Yunhe Hou
hot direction similarity 0.68
Abstract · 10 pages, 5 figures

Artificial intelligence data centers (AIDCs) are rapidly increasing in number and capacity. These large electronic loads are interfaced through power electronic devices and can sharply reduce grid power intake during fault-induced voltage sags. Disturbances exceeding equipment ride-through capabilities may also trigger protective disconnection, posing risks to power system security. Static synchronous compensators (STATCOMs) and appropriately controlled AIDC uninterruptible power supply (UPS) rectifiers can provide reactive power support during voltage sags. This paper compares the individual and combined effectiveness of STATCOM and UPS-based voltage support in mitigating fault-induced reductions in grid power intake through electromagnetic transient simulations of a 1 GW AIDC connected to an IEEE nine-bus system. Simulation results show that STATCOM support better preserves short-term intake in milder tested faults, whereas UPS coordination maintains rectifier operation under deeper sags by reducing active intake to reserve reactive current capacity. Combined support improves auxiliary load retention and recovery in selected cases. However, severe tested sags still cause substantial grid-demand reductions even with combined support.

0.29

Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers

eess.SY ·2026-11-02 ·Muhammad Hamza Ali, Amritanshu Pandey
similarity 0.66
Abstract

This document presents dynamic models of a transmission network and average models of power-electronic devices and loads in the synchronous $dq$ frame. We model the network in the positive sequence and its synchronous generators with the classical swing equation and a first-order turbine governor. The power-electronic models cover grid-following inverters and AI data centers. Each inverter has a phase-locked loop, a power controller, and a current controller. Each data center connects to the grid through two step-down transformers. Its low-voltage bus feeds an IT load, an induction-motor cooling load, and a constant-impedance load. A double-conversion uninterruptible power supply (UPS) serves the IT load. We model its rectifier, grid-forming output inverter, battery, and bidirectional DC-DC converter. A measured GPU power trace drives the IT demand. We replace every non-smooth operation with a smooth surrogate. This keeps the discretized model continuously differentiable for the nonlinear solver. We also show how we initialize each model at its power-flow operating point.

0.25

Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation

eess.SY ·2026-11-12 ·Salish Maharjan, Junyuan Zheng, Lung-An Lee, Min Lwin, Zhaoyu Wang
similarity 0.65
Abstract · 13 pages, 16 figures. Submitted for IEEE publications

Data centers are now one of the fastest-growing loads on the bulk power system, and most of their demand reaches the grid through power converters inside uninterruptible power supplies (UPS). Whether these loads can take part in sub-synchronous control interaction (SSCI), as wind and HVDC converters do, has not been studied extensively. We examine this question with impedance-based frequency scans at the point of common coupling (PCC). Using a detailed proprietary model (INS-ISU), we scan the motor, variable-frequency-drive (VFD), lighting, and UPS-fed information-technology (IT) branches of a representative facility separately. Only the UPS in double-conversion mode shows negative resistance; it covers the whole sub-synchronous band and continues up to about 170 Hz. The other branches, and the UPS in bypass mode, stay passive. We then repeat the scans on three public models from PNNL, TAMU, and NLR. None of them shows negative resistance in bypass mode, while three of the four models do in double-conversion mode. Lowering the load from rated to light load makes the negative resistance deeper, as expected for a constant-power load, so a lightly loaded facility in double-conversion mode is the worst case. Raising the UPS DC-link capacitance pushes the negative resistance into a narrow band around the fundamental. These findings give a basis for screening data centers for SSCI during interconnection studies.

0.29

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.64
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16