Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers

Muhammad Hamza Ali, Amritanshu Pandey

eess.SY ·submitted 2026-11-02 15:22 UTC · v1

Abstract

This document presents dynamic models of a transmission network and average models of power-electronic devices and loads in the synchronous $dq$ frame. We model the network in the positive sequence and its synchronous generators with the classical swing equation and a first-order turbine governor. The power-electronic models cover grid-following inverters and AI data centers. Each inverter has a phase-locked loop, a power controller, and a current controller. Each data center connects to the grid through two step-down transformers. Its low-voltage bus feeds an IT load, an induction-motor cooling load, and a constant-impedance load. A double-conversion uninterruptible power supply (UPS) serves the IT load. We model its rectifier, grid-forming output inverter, battery, and bidirectional DC-DC converter. A measured GPU power trace drives the IT demand. We replace every non-smooth operation with a smooth surrogate. This keeps the discretized model continuously differentiable for the nonlinear solver. We also show how we initialize each model at its power-flow operating point.

Closest papers

Nearest neighbours by meaning across the whole index.

Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control

eess.SY ·2026-11-14 ·Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah +2 more
hot direction similarity 0.67
Abstract · 5 pages, 7 figures

The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.

0.22

EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data Centers

eess.SY ·2026-11-05 ·Junyuan Zheng, Salish Maharjan, Min Lwin, Soummya Roy, Zhaoyu Wang +3 more
similarity 0.66
Abstract

Large data centers are emerging as power-electronic loads whose response to grid voltage disturbances can affect bulk-system stability. This paper presents the composition and control characteristics of a proprietary electromagnetic transient (EMT) model of a modern data center comprising an uninterruptible power supply (UPS) with battery energy storage, induction-motor cooling loads, a computer room air handler (CRAH) driven by a variable-frequency drive (VFD), and an aggregated server load. A voltage-based state machine coordinates three aspects of the facility response: the UPS operating mode (eco, double conversion, or battery), the supply path of the CRAH, and a ramped reconnection of the grid-side UPS converter after the disturbance clears. A 100 MW facility is implemented in PSCAD/EMTDC and benchmarked against the PSSE PERC1 aggregate data center model under a symmetrical three-phase fault and low- and high-voltage ride-through (LVRT/HVRT) events. The two models agree closely in their voltage and active-power trajectories, while the EMT model also resolves the converter and motor-reacceleration transients that the phasor-domain model cannot.

0.50

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.64
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data Center

eess.SY ·2026-11-19 ·Jesus D. Vasquez-Plaza, Sunil Subedi, Jin Dong, Joao Pereira Pinto
similarity 0.64
Abstract · Submitted to IEEE PES General Meeting 2027

Data centers supplied through centralized uninterruptible power supplies (UPSs) are converter-dominated loads whose grid response reflects IT demand, power-conversion controls, energy storage, cooling, and site-support dynamics. This paper develops and electrically realizes a causal multi-output surrogate for a nominal 1-MW, 0.48-kV simulated data center. Four physics-informed terminal features-normalized IT demand, positive-sequence voltage deviation, voltage-unbalance ratio, and frequency deviation-are used to predict active and reactive power at both the point of common coupling (PCC) and UPS output. Six causal surrogate families are evaluated using separate training, validation, and held-out trajectories. A ridge-regularized low-order nonlinear autoregressive model with exogenous inputs (NARX) achieves the lowest validation and test errors, with mean four-output errors of 0.1959\% and 0.1441\% on a 1-MVA base, respectively. The selected surrogate is then coupled to a three-phase electrical interface in MATLAB/Simulink, where predicted PCC active power controls a variable resistive load and predicted reactive power is realized through controlled current sources synchronized to the PCC voltage. Across two 41-s AI workload profiles, including an additional pipeline parallelism trajectory, the electrical realization tracks the NARX commands with active- and reactive-power RMSEs of 0.604 kW and 0.353 kVAR for Evaluation Profile A and 1.539 kW and 0.442 kVAR for Evaluation Profile B, respectively. The results demonstrate a compact terminal surrogate that can reproduce both predicted power trajectories and their corresponding three-phase electrical behavior under measured PCC excitation.

0.17

AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated Solutions

eess.SY ·2026-10-06 ·Mariam Mughees, Yuzhuo Li, Yize Chen, Yunwei Ryan Li
survey similarity 0.63
Abstract

Artificial intelligence (AI) workloads are creating large, power-electronic loads whose effects on power systems depend on location, temporal variability, controllability, and interactions with other loads and resources. Annual electricity consumption alone cannot capture these effects. This review examines how AI data centers affect power systems stability, renewable-energy integration, and low-carbon planning by tracing the power-delivery chain from accelerators and workloads through rack converters, uninterruptible power supplies (UPS), storage, and microgrids to the transmission point of interconnection. Reported oscillatory events and multi-gigawatt load transfers highlight how facility responses can amplify disturbances, while programmable workloads and controllable power converters offer opportunities for demand flexibility. Challenges and mitigation strategies are organized across device, rack, facility, and power systems levels, spanning millisecond-to-year timescales. A bandwidth-matching framework relates disturbances to the response capabilities of mitigation resources. The review distinguishes computational energy efficiency from power systems and sustainability outcomes: lower energy consumption per token does not necessarily reduce peak demand, electrical disturbances, or carbon emissions. It examines how coordinated workload scheduling, grid-interactive UPS systems, storage, high-voltage DC distribution, and flexible interconnection can support reliability, efficiency, and decarbonization. Key research needs include dynamic load models, high-bandwidth telemetry, carbon-and grid-aware scheduling, and mechanisms for valuing flexible computational demand.

0.08

Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems

eess.SY ·2026-09-02 ·Pengyu Ren, Wei Sun, Fei Teng
similarity 0.63
Abstract

Large data centers are emerging as concentrated, power-electronic grid loads whose abrupt disconnection or transfer to on-site backup supply during voltage disturbances can remove large demand from the power system, and may create a system-level stability problem. Their interconnection feasibility therefore depends not only on steady-state thermal and voltage limits, but also on whether internal power-conditioning systems can maintain IT service while limiting customer-initiated load reduction. This paper presents a voltage ride-through (VRT)-aware data center and grid co-planning framework that couples transmission-level fault simulation with an internal data center ride-through model. Python-based dynamic simulations generate point-of-interconnection (POI) voltage trajectories under selected network faults, and the resulting waveforms drive an internal model incorporating IT and cooling-load dynamics, DC-link, Uninterruptible Power Supply (UPS) response, and converter apparent power limits. The IEEE 118-bus case study shows that internal VRT capability can become a binding interconnection constraint: steady-state planning alone can overestimate feasible data center capacity, whereas increased UPS converter headroom progressively restores hosting capacity. Under the reduced-order response models studied, the grid-forming mode provides greater ride-through margin than the current-limited grid-following mode under the same network fault conditions. The results further show that VRT constraints can materially change both the total hosting capacity of data centers and its spatial allocation across candidate interconnection buses.

0.16

When Gigawatts of Computational Load Disappear: Cycle-Space Certificates for Grid Synchronization and Transient Stability

eess.SY math.DSphysics.soc-ph ·2026-09-23 ·Michael Chertkov
similarity 0.63
Abstract · 13 pages, 2 figures

Rapid growth of data centers and artificial-intelligence services is producing computational loads at scales once associated mainly with largest power plants. Recent grid events show that a routine transmission disturbance can cause several gigawatts of data-center demand to disconnect or transfer to backup nearly at once. This article revisits the classical synchronization and transient-stability theory needed to reason about such events. We organize four lines of work---graph-based synchronization conditions, winding-number descriptions of nonlinear power flow, separable convex network optimization, and direct energy methods---into a single cycle-space certificate framework for the lossless fixed-voltage model. The static layer gives an exact strict-cohesion test within a prescribed winding cell and reveals the widely used Dörfler--Chertkov--Bullo test as a quadratic surrogate of the same convex problem. The dynamic layer converts the critical-energy calculation into a finite family of convex boundary problems. Standard MATPOWER benchmarks illustrate both what the stronger static test gains and where it gains nothing: the 118-bus case admits $16.2\%$ more loading than the sufficient screen, while the 39-bus case is bridge-limited and the thresholds coincide. A stylized $2.7$-GW 39-bus event further shows that transient margin can change by about a factor of two depending on where balancing power is supplied, even when every final balanced operating point remains statically feasible. The result is a tutorial synthesis and an extensible deterministic certificate for emerging gigawatt-scale computational-load contingencies.

0.53

Trajectory Sensitivity-Based Dynamic Assessment of an AI Data Center Under Contingencies

eess.SY ·2026-10-07 ·Arnav Bagga, Saskia A. Putri, Abhishek Banerjee, Xiaofan Wu
similarity 0.62
Abstract · 7 pages, 5 figures

Artificial Intelligence (AI) data centers are emerging as converter-dominated, parameter-rich electrical systems whose dynamic response depends on fast workload-driven demand variations, tightly regulated data-hall converters, and coordinated on-site sources. Assessing such systems by repeatedly solving nonlinear time-domain models for every outage, load realization, and parameter perturbation is computationally expensive and provides limited insight into response sensitivity. This paper presents a trajectory sensitivity (TS)-based dynamic assessment framework for a self-contained AI data center supplied by a 2 kV DC microgrid with a grid-tied interface. The model includes time-varying data-hall load profiles, a voltage source converter (VSC), battery energy storage systems (BESS) units, supercapacitors, and synchronous-generation-side sources. For each disturbance, firstly, TS are computed along the nonlinear disturbance trajectory, capturing the local effect of source trips, data-hall outages, converter controls, and load ramps. Later, the computed TS data is used to estimate system trajectories under simultaneous parameter perturbations. Validation against full nonlinear ODE simulations with $\pm 15\%$ perturbations shows close agreement. In addition, the TS-based approach reduces computational time of dynamic-response evaluations from seconds to milliseconds, demonstrating its potential as a scalable screening tool for AI data center dynamics.

0.17