A Power-Trajectory Framework for Data Center Participation in Day-Ahead Markets

Menghan Zhang, Caisheng Wang

eess.SY ·submitted 2026-10-12 15:01 UTC · v1

Abstract

The rapid expansion of artificial intelligence (AI) is driving substantial growth in data center electricity demand. Interval-based energy blocks in day-ahead markets do not explicitly retain predictable intra-interval demand evolution, potentially creating mismatches with ramp-feasible generation trajectories and affecting settlement. This paper proposes a power-trajectory framework in which data centers declare predictable aggregate demand evolution through continuous demand-side power trajectories before market clearing. The declared trajectories are treated as exogenous inputs for constructing generation trajectories and the corresponding price trajectory. For feasible market-clearing outcomes, physical temporal consistency is established through continuous-time power balance and satisfaction of the modeled generation operating constraints, while economic temporal consistency is established by preserving the dispatch-price correspondence in energy settlement on a common temporal basis. Under the adopted settlement definitions, a trajectory-based settlement analysis separately quantifies the monetary magnitude of representation-induced power imbalances and the supply-side compensation that may remain under temporally consistent clearing and settlement. An illustrative 5-bus case demonstrates the elimination of representation-induced power imbalance and identifies the timing and physical sources of supply-side compensation. A modified IEEE RTS-GMLC case further illustrates these compensation effects across multiple generating units under workload-driven data center demand variations.

Comment
10 Pages, 7 Figures, 4 Tables

Closest papers

Nearest neighbours by meaning across the whole index.

AI for AI: Optimizing Additional Infrastructure Build-out to Power Artificial Intelligence Data Centers

cs.AI q-fin.GNecon.GN ·2026-09-08 ·Alexander Crosier, Kyle Onghai, Ronnie Sircar
similarity 0.68
Abstract

The twenty-first century's transformative technology, artificial intelligence, is increasingly constrained by the twentieth century's transformative technology, the electricity grid. Rapid growth in electricity demand from data centers is leading to higher electricity prices, without a compensating supply-side response. We develop a framework linking data-center load growth, available generation capacity, and market-clearing prices to understand this phenomenon. We first analyze a deterministic model to show how differing estimates of demand and supply growth rates affect prices. We then model the expansion of new data centers and their associated electricity demand, together with build-outs of new electricity supply, as stochastic processes,resulting in probabilistic distributions of supply, demand, and prices rather than a single forecast. Finally, we formulate generation expansion as a stochastic control problem in which a revenue-maximizing investor dynamically chooses the intensity of supply-side investments. The analysis highlights a central challenge of the data-center build-out: even when rapid demand growth increases the need for new generation, the uncertainties related to load forecasts, development execution risks, and value cannibalization from overbuilding capacity may weaken incentives to invest at the pace required to keep electricity prices stable.

0.22

Grid Demand Flexibility Assessment of AI Data Centers via Batch Workload Temporal Shifting

eess.SY ·2026-09-29 ·Suntao Su, Liang Du, Shengyi Wang
similarity 0.68
Abstract · 5 pages, 5 figures, conference

The rapid growth of artificial intelligence (AI) data centers has introduced new challenges to power system operation. As their power demand becomes larger and more variable, quantitatively characterizing their demand flexibility is increasingly important for effective power system coordination. However, heterogeneous workload characteristics and resource requirements make this flexibility difficult to characterize directly. This paper proposes a framework for assessing the grid-compatible demand flexibility of AI data centers via batch workload temporal shifting. An averaging-based resource usage processing method is developed to map fine-resolution CPU, GPU and memory usage into unified time intervals compatible with power system operation. A workload temporal scheduling model is then formulated to shift batch workloads while preserving execution continuity, delay constraints, and server resource capacities, and is coupled with a utilization-dependent server power model to translate workload scheduling decisions into server power demand. Two complementary flexibility metrics are evaluated: short-term peak demand shaving and the maximum duration of sustained power reduction. Numerical results based on real GPU cluster traces demonstrate that workload temporal shifting can provide quantifiable and grid-compatible demand flexibility for AI data centers with limited disruption to computing workloads.

0.13

State-of-Charge Targets for Storage Participation in Two-Settlement Markets: Reliability, Price, and Compensation Impacts

eess.SY ·2026-11-13 ·Yichen Li, Alexandre Moreira, Ruiwei Jiang, Miguel Heleno, Julie Mulvaney-Kemp
hot direction similarity 0.67
Abstract

As energy storage assumes a larger role in electricity systems, market operation must coordinate its use across time to support reliability during periods of system stress. Minimum state-of-charge (SOC) targets provide a means of preserving energy for these periods, but their design shapes reliability, operating efficiency, and storage compensation. This paper evaluates alternative SOC target designs in a California-based day-ahead and real-time electricity market model. The comparison examines targets based on day-ahead schedules or rolling centralized dispatch, enforced at the individual-resource or system level, across seasons, stress conditions, and participant information settings. The results show that retaining more energy does not necessarily reduce load shedding: targets that restrict discharge can limit storage support during shortages. Under critical summer conditions, individual targets derived from rolling centralized dispatch reduce weekly load shedding by approximately 83--84\% relative to operation without targets. Lower RT clearing costs and average prices can coexist with higher storage compensation, reflecting the role of day-ahead positions and real-time deviations in determining settlement outcomes. These findings highlight the importance of coordinating energy retention with timely discharge and network deliverability when designing SOC requirements for storage participation in electricity markets.

0.25

Extended Version: Storage-Based Strategic Manipulation of Constraint-Binding Patterns in Power Networks

eess.SY econ.GN ·2026-09-14 ·Mehdi Davoudi, Minghao Mou, Junjie Qin
similarity 0.66
Abstract · Extended version of our paper submitted to IEEE Transactions on Power Systems

This paper studies the strategic market participation of a monopolistic energy storage aggregator (ESA) in a day-ahead electricity market. The ESA coordinates geographically distributed storage units, submits a coordinated bid for its portfolio, and may hold financial transmission rights (FTRs). The system operator clears the market through a network-constrained, multi-period economic dispatch, determining generation and load schedules, nodal prices, energy-market payments, and FTR payoffs. We formulate the ESA--system-operator interaction as a Stackelberg game and characterize its equilibrium through a constraint-binding-pattern decomposition of the market-clearing problem. Beyond enabling equilibrium computation, the framework reveals how the ESA can increase its profit by strategically inducing or avoiding particular constraint-binding patterns. It also establishes a novel welfare result: although strategic storage without FTRs is known to weakly improve social welfare relative to the no-storage case, certain FTR positions can overturn this guarantee by strengthening the ESA's incentive to induce particular patterns, causing social welfare to fall below the no-storage level. Motivated by these findings, we develop two system-operator mechanisms for limiting undesirable ESA behavior and its adverse effects on market outcomes and social welfare. Finally, a three-bus study illustrates the theoretical findings, while IEEE test systems demonstrate the scalability of the proposed method.

0.18

AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated Solutions

eess.SY ·2026-10-06 ·Mariam Mughees, Yuzhuo Li, Yize Chen, Yunwei Ryan Li
survey similarity 0.65
Abstract

Artificial intelligence (AI) workloads are creating large, power-electronic loads whose effects on power systems depend on location, temporal variability, controllability, and interactions with other loads and resources. Annual electricity consumption alone cannot capture these effects. This review examines how AI data centers affect power systems stability, renewable-energy integration, and low-carbon planning by tracing the power-delivery chain from accelerators and workloads through rack converters, uninterruptible power supplies (UPS), storage, and microgrids to the transmission point of interconnection. Reported oscillatory events and multi-gigawatt load transfers highlight how facility responses can amplify disturbances, while programmable workloads and controllable power converters offer opportunities for demand flexibility. Challenges and mitigation strategies are organized across device, rack, facility, and power systems levels, spanning millisecond-to-year timescales. A bandwidth-matching framework relates disturbances to the response capabilities of mitigation resources. The review distinguishes computational energy efficiency from power systems and sustainability outcomes: lower energy consumption per token does not necessarily reduce peak demand, electrical disturbances, or carbon emissions. It examines how coordinated workload scheduling, grid-interactive UPS systems, storage, high-voltage DC distribution, and flexible interconnection can support reliability, efficiency, and decarbonization. Key research needs include dynamic load models, high-bandwidth telemetry, carbon-and grid-aware scheduling, and mechanisms for valuing flexible computational demand.

0.08

Scarcity Pricing for State-of-Charge Management in Real-Time Markets Under Intra-Day Uncertainty

eess.SY ·2026-11-09 ·Shailesh Wasti, Aravind Retna Kumar, Sushant Varghese, Anthony Giacomoni, Parviz Alivand +2 more
similarity 0.65
Abstract

The growth in renewable resources will increase net load variability and forecast error. Energy storage resources can provide flexibility when ramp capability is limited and contribute to load leveling over the day. The challenge for system operators is how to balance these two functions in real time, when updated net load forecasts are available for a limited lookahead horizon. U.S. electricity markets are seeking ways to manage state-of-charge (SoC) within their energy markets to more efficiently utilize these resources. We propose a method to manage energy storage SoC in a real-time market by extending Hogan's (2013) scarcity pricing framework. A day-ahead SoC schedule is modified using existing multi-interval real-time unit commitment engines as net load forecasts change. To address 30-minute-ahead forecast errors, an updated 5-minute SoC target and a dynamically updated shortage price for violating the constraint are provided to each economic dispatch. We simulate PJM's energy markets for 365 days and demonstrate reliability improvements relative to a strategy that enforces the day-ahead schedule. We show cost reductions and improved price formation relative to a strategy that updates target quantities but uses an administratively chosen shortage penalty.

0.30

Large-Scale Data Center Integration in Power Systems: Uncertainty and Multi-Scale Variation

eess.SY ·2026-10-09 ·Le Xie, Dongjoo Kim, Qian Zhang, Grant Ruan, Paul L. Joskow
published similarity 0.64
Abstract · Accepted for publication in Proceedings of the IEEE. Copyright 2026 IEEE. Personal use of this material is permitted. Permission from IEEE m…

Hyperscale artificial intelligence (AI) data centers are emerging as a structurally new class of electricity demand. Unlike conventional loads, they materialize as spatially concentrated, transmission-level point loads with rapid deployment timelines and converter-dominated dynamics. Their integration is governed by two defining properties: forecast uncertainty in load realization and multi-scale temporal variation spanning sub-seconds to planning horizons. We develop a unified framework that links reliability and affordability to these dimensions through a four-quadrant structure: (reliability, affordability) $\times$ (uncertainty, variation), which integrates probabilistic resource adequacy, generation and transmission expansion, operational security, and market design. Measured traces from a public generative-AI workload dataset show strongly tonal GPU power spectra rather than smooth broadband behavior: harmonic combs at the training-step cadence, and a distinct sub-second periodicity in inference. Across these traces the dominant variance band shifts with workload type (seconds for training and offline inference; tens of seconds and longer for online inference). We report this as a characterization of the measured workloads rather than a universal signature, and take it to indicate that such loads warrant a spectral description rather than a peak-demand one. These signatures directly affect reserve requirements, ramping products, voltage stability, ride-through performance, and harmonic interactions in converter-rich grids. Taken together, the analytical framework and empirical results establish a system-level basis for assessing the reliability and cost implications of large AI data center integration across planning and operational horizons.

0.27

Speed-to-Power Dominates Energy Costs for AI Data Centers: Technoeconomic Analysis of Powering AI in the Continental United States

cs.AI eess.SY ·2026-11-12 ·Alex C. Newkirk, Daniel L. Gerber, Erica R. H. Fuchs, Alex Hubbard, M. Granger Morgan +3 more
code/datahot direction similarity 0.64
Abstract · 80 pages incl. SI

The rapid growth of artificial intelligence is driving demand for new data centers at large scale and on short deployment timelines. To power them, firms connect to the commercial grid or contract generation directly, but interconnection and gas-turbine delays now incentivize on-site generation. We compare grid-connected and off-grid data center energy infrastructure (AC- and DC-coupled solar-plus-storage, islanded natural gas, and grid interconnection) across the continental U.S. Using an open-source technoeconomic framework built on empirically calibrated AI training loads, climate-driven cooling, stage-by-stage power conversion, and physics-based battery degradation, we model designs providing equivalent energy services. Our central contribution is a speed-adjusted cost of energy that values the compute unlocked by faster construction, making options with different deployment timelines directly comparable on one physically consistent basis. We find DC coupling reduces lifetime energy costs by 18% ($0.09/ kWh) on average versus AC counterparts by eliminating inverters and improving efficiency. Though rarely cheapest on unadjusted energy cost, DC-coupled microgrids' faster deployment makes them the lowest-cost modeled option in 85% of U.S. locations once foregone compute is valued, or 55% under accelerated natural gas timelines. For AI infrastructure, deployment speed rather than unit energy cost determines the economically preferred path to power.