CS Paper Radar

Identifiability-Guided Composite Load Modeling of AI Data Centers

Ding Lin, Jianhui Wang, Meng Yue, Tianqiao Zhao

eess.SY ·submitted 2026-10-14 04:28 UTC · v2

Abstract

The rapid growth of AI data centers introduces large, workload-dependent loads whose protection and reconnection behavior can affect power-system transient stability. Calibrating dynamic models of such loads is challenging because treating all associated elements as freely estimable may lead to weakly identified or physically confounded parameterizations. This paper proposes an identifiability-guided calibration framework for a composite load model with separate IT, cooling, and auxiliary branches. A nuisance-projected Fisher-information criterion characterizes the local identifiability of the cooling-motor composition, while a workload non-equivalence result shows that voltage-only recalibration cannot reproduce workload-dependent responses. Guided by these results, a grey-box estimator trained with branch-level supervision learns the workload-to-power relation and the cooling composition, while retaining a prescribed UPS protection law and an externally anchored reconnect-ramp duration. The learned workload relation is then distilled into a closed form for transient-stability simulation. Evaluation using 300,000 MIT Supercloud GPU power-utilization samples and 12,600 IEEE 39-bus fault scenarios yields an aggregate active-power $R^2$ of 0.948, compared with 0.856 for an LSTM baseline. Removing branch-level supervision preserves relatively high aggregate accuracy but substantially degrades cooling-component recovery. Under unseen deep voltage sags, the proposed model achieves a transient $R^2$ of 0.750, compared with 0.033 for the LSTM. Closed-loop simulations further show that cooling composition and protection behavior can affect retained-load states and voltage responses near protection thresholds.

Closest papers

Nearest neighbours by meaning across the whole index.

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.65
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.20

Grid Demand Flexibility Assessment of AI Data Centers via Batch Workload Temporal Shifting

eess.SY ·2026-09-29 ·Suntao Su, Liang Du, Shengyi Wang
similarity 0.61
Abstract · 5 pages, 5 figures, conference

The rapid growth of artificial intelligence (AI) data centers has introduced new challenges to power system operation. As their power demand becomes larger and more variable, quantitatively characterizing their demand flexibility is increasingly important for effective power system coordination. However, heterogeneous workload characteristics and resource requirements make this flexibility difficult to characterize directly. This paper proposes a framework for assessing the grid-compatible demand flexibility of AI data centers via batch workload temporal shifting. An averaging-based resource usage processing method is developed to map fine-resolution CPU, GPU and memory usage into unified time intervals compatible with power system operation. A workload temporal scheduling model is then formulated to shift batch workloads while preserving execution continuity, delay constraints, and server resource capacities, and is coupled with a utilization-dependent server power model to translate workload scheduling decisions into server power demand. Two complementary flexibility metrics are evaluated: short-term peak demand shaving and the maximum duration of sustained power reduction. Numerical results based on real GPU cluster traces demonstrate that workload temporal shifting can provide quantifiable and grid-compatible demand flexibility for AI data centers with limited disruption to computing workloads.

0.13

Mitigating the Grid Impact of Gigawatt-Scale AI Data Centers via High-Fidelity Model Flexibility

eess.SY math.OC ·2026-11-18 ·Eihab E. E. Ahmed, Saeed Manshadi
hot direction similarity 0.61
Abstract

Gigawatt-scale artificial intelligence data centers (AIDCs) are being connected at a single point of interconnection (POI) faster than transmission can be reinforced, yet studies of their flexibility rely on DC power flow and simplified load envelopes that omit voltage, cooling dynamics, and workload deadlines. This paper addresses this gap by embedding a high-fidelity AIDC model, with separate inference and training pools, hall thermal mass, PV, a battery energy storage system (BESS) with reactive capability, and a STATCOM, in a five-minute multi-period AC optimal power flow. Simulations on the RTS-GMLC test system show that active-power flexibility mitigates local price spikes and relieves congestion, whereas reactive support from the BESS inverter or a STATCOM is needed to keep the POI voltage away from sagging around its 0.95~pu limit. Sensitivity analyses show that cost-driven charging of large batteries can induce new morning congestion and that storage largely substitutes for wider workload deferral.

0.30

From Grid to Chip: Power Architecture, Stability, and Flexibility of AI Data Centers

cs.ET cs.AReess.SY ·2026-09-10 ·Yubo Song, Rui Kong, Takuro Umihara, Pooya Davari, Frede Blaabjerg +1 more
hot direction similarity 0.61
Abstract · The manuscript has been submitted for review to IEEE Open Journal of Power Electronics

The rapid growth of artificial intelligence (AI) computing is transforming data centers into large, dynamic electrical loads. Their deployment is primarily constrained by energy availability and grid-connection capacity, which is further aggravated by the ability of power-delivery architectures, control systems, and computing workloads to operate reliably during fast grid disturbances. This article presents a technological perspective on AI data centers as grid-interactive computing systems. First, it reviews grid-integration bottlenecks, evolving connection policies, grid-code requirements, which has fostered new technological trends via spatio-temporal flexibility available through workload orchestration, cooling systems, on-site resources, and energy storage. Second, it maps the evolution of power-delivery architectures from medium-voltage grid interfaces to chip-level, discussing higher-voltage DC distribution, solid-state transformers, wide-bandgap devices, advanced chip-level power delivery, and liquid cooling. Third, it establishes a three-level stability framework spanning rack-level DC-bus dynamics, facility-level converter interactions, and system-level grid-coupled behavior. The framework connects dominant instability mechanisms, including constant power load effects, impedance interactions, forced oscillations, and operating-mode transitions, with suitable modeling, assessment, and mitigation approaches. Synthesizing these topics, this article highlights grid-to-chip co-design as a central requirement for scalable AI infrastructure, linking computing workloads, power-delivery systems, energy buffers, and grid operation.

0.27

AI-driven Thermal-aware Data Center Capacity Planning

cs.LG ·2026-10-01 ·Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai +1 more
published similarity 0.60
Abstract · Presented at DesignCon 2026

The emerging of large language models (LLMs) has posed significant challenges to the thermal management of data center. Intense GPU computation for LLMs results in localized hotspots. Moreover, spiking thermal loads during training and inference bursts make real-time cooling response more difficult to predict and control. Thermal-aware capacity planning of data center requires massive expensive high-fidelity CFD simulations. AI models can perform real-time prediction for unseen designs. However, existing works either have large prediction error, or have over-simplified assumptions for data center operations. This work presents an AI-driven framework that can perform thermal-aware capacity planning for a real-world data center in seconds. The embedded AI model learns from numerous key parameters (rack power, server power, server placement, HVAC settings etc.), and provides temperature prediction within milliseconds. This AI model is tested against high-fidelity CFD simulations, and results show that for unseen data center designs, model can achieve high accuracy with 10000X speedup. Driven by the AI model, the authors design the thermal-aware capacity planning framework. This framework can help data center designers and operators instantaneously optimize both workload distribution and HVAC cooling efficiency.

0.13

AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated Solutions

eess.SY ·2026-10-06 ·Mariam Mughees, Yuzhuo Li, Yize Chen, Yunwei Ryan Li
survey similarity 0.59
Abstract

Artificial intelligence (AI) workloads are creating large, power-electronic loads whose effects on power systems depend on location, temporal variability, controllability, and interactions with other loads and resources. Annual electricity consumption alone cannot capture these effects. This review examines how AI data centers affect power systems stability, renewable-energy integration, and low-carbon planning by tracing the power-delivery chain from accelerators and workloads through rack converters, uninterruptible power supplies (UPS), storage, and microgrids to the transmission point of interconnection. Reported oscillatory events and multi-gigawatt load transfers highlight how facility responses can amplify disturbances, while programmable workloads and controllable power converters offer opportunities for demand flexibility. Challenges and mitigation strategies are organized across device, rack, facility, and power systems levels, spanning millisecond-to-year timescales. A bandwidth-matching framework relates disturbances to the response capabilities of mitigation resources. The review distinguishes computational energy efficiency from power systems and sustainability outcomes: lower energy consumption per token does not necessarily reduce peak demand, electrical disturbances, or carbon emissions. It examines how coordinated workload scheduling, grid-interactive UPS systems, storage, high-voltage DC distribution, and flexible interconnection can support reliability, efficiency, and decarbonization. Key research needs include dynamic load models, high-bandwidth telemetry, carbon-and grid-aware scheduling, and mechanisms for valuing flexible computational demand.

0.08

Large-Scale Data Center Integration in Power Systems: Uncertainty and Multi-Scale Variation

eess.SY ·2026-10-09 ·Le Xie, Dongjoo Kim, Qian Zhang, Grant Ruan, Paul L. Joskow
published similarity 0.59
Abstract · Accepted for publication in Proceedings of the IEEE. Copyright 2026 IEEE. Personal use of this material is permitted. Permission from IEEE m…

Hyperscale artificial intelligence (AI) data centers are emerging as a structurally new class of electricity demand. Unlike conventional loads, they materialize as spatially concentrated, transmission-level point loads with rapid deployment timelines and converter-dominated dynamics. Their integration is governed by two defining properties: forecast uncertainty in load realization and multi-scale temporal variation spanning sub-seconds to planning horizons. We develop a unified framework that links reliability and affordability to these dimensions through a four-quadrant structure: (reliability, affordability) $\times$ (uncertainty, variation), which integrates probabilistic resource adequacy, generation and transmission expansion, operational security, and market design. Measured traces from a public generative-AI workload dataset show strongly tonal GPU power spectra rather than smooth broadband behavior: harmonic combs at the training-step cadence, and a distinct sub-second periodicity in inference. Across these traces the dominant variance band shifts with workload type (seconds for training and offline inference; tens of seconds and longer for online inference). We report this as a characterization of the measured workloads rather than a universal signature, and take it to indicate that such loads warrant a spectral description rather than a peak-demand one. These signatures directly affect reserve requirements, ramping products, voltage stability, ride-through performance, and harmonic interactions in converter-rich grids. Taken together, the analytical framework and empirical results establish a system-level basis for assessing the reliability and cost implications of large AI data center integration across planning and operational horizons.

0.27

Analytical Power-Aware Provisioning for Prefill-Decode Disaggregated AI Inference

cs.DC cs.PFeess.SY ·2026-09-21 ·Mingyuan Yan, Haiyu Wang, Linxuan Biao, H. Jonathan Chao, Sai Qian Zhang +1 more
similarity 0.59
Abstract

Power availability increasingly constrains the operation of AI inference fleets, creating a need for provisioning methods that jointly consider serving capacity and power consumption. Prefill--decode (PD) disaggregation has emerged as a prevalent architecture for large-scale inference serving. However, determining the appropriate numbers of prefill and decode instances is challenging because serving capacity depends jointly on workload characteristics, hardware constraints, queueing, and KV-cache reservations. Existing approaches largely rely on profiling and simulation, providing limited analytical insight into how provisioning decisions shape the tradeoff between serving capacity and power consumption. This paper develops an analytical framework for power-aware provisioning of PD-disaggregated AI inference. Given an inference workload and hardware, the framework models the serving capacity and average power consumption of a provisioned deployment. The serving-capacity model is derived from the joint distribution of input--output lengths and hardware compute and memory limits. In particular, it explicitly captures the coupling between prefill and decode induced by KV-cache reservations, as well as the impact of request queueing. On this basis, the power model determines per-instance power consumption as a function of normalized serving throughput. Together, the models determine the serving capacity--power Pareto front among candidate provisioned deployments, enabling the service provider to choose a provisioned deployment as the workload or available power changes.

0.33