From Rigid to Adiabatic: Canonical Regularization of AC Networks via Action-Angle Variables

Feng Ji, Lu Gao, Lihui Yang

eess.SY ·submitted 2026-08-29 08:15 UTC · v1

Abstract

Traditional power system analysis relies on timescale separation and the rigid-network assumption, freezing electromagnetic transients into algebraic power-flow equations via Steinmetz's phasor theory. As grid-forming converter penetration increases, magnetic energy dynamics on transmission lines interact with converter control loops on comparable timescales, challenging this rigid-network assumption. Returning to Faraday's law of electromagnetic induction driven by rotating magnetic fields, this paper models the transmission lines' rotating magnetic fields in action-angle canonical coordinates, regularizes the rigid algebraic constraints of power-flow equations into canonical equations on adiabatic symplectic manifolds, and establishes a port-Hamiltonian standard form for AC power grids. Based on the minimal-counterexample principle and using the equal-area criterion's classical two-machine system, this paper reveals a latitudinal instability channel via Bloch-sphere coordinates: Q-V control releases voltage-amplitude freedom, shifting the stability boundary from the equatorial UEP (unstable equilibrium point) to a saddle point, thereby unifying the analytical frameworks of P-delta angle stability and Q-V voltage stability in power system analysis.

Closest papers

Nearest neighbours by meaning across the whole index.

Unifying Power Flow and Electromagnetic Transient Modeling

eess.SY ·2026-09-08 ·Tina Gao, Aayushya Agarwala, Timothy McNamara, Lawrence Pileggi
similarity 0.56
Abstract

Grid tools are separated by timescales: steady-state analysis is performed by power flow (PF), whereas the fastest dynamics are captured by electromagnetic transient (EMT) simulation. Although operating at varying timescales, different tools should produce consistent results when analyzing the same grid conditions. However, the PF steady-state solution does not match the time-to-infinity EMT response. This mismatch exists because simplified device models in PF are inconsistent with the "ground truth" EMT models derived from first principles. As inverter-based resources (IBRs) and data centers strip away inertia and operating reserves, approximations used in PF risk grid security by missing violations. To address this, we introduce a steady-state framework that uses full-physics EMT models for high-fidelity steady-state grid analysis. The challenge lies in systematically formulating algebraic frequency-domain representations of dynamic power devices that are naturally described in state-space form. Our tool, SALT (Steady-state After Last Transients), constructs steady-state representations that exactly capture grid device physics when embedded into transmission networks. The approach exploits the structural properties of power device models and the single-harmonic, balanced nature of the transmission system. Results demonstrate SALT achieves EMT steady-state accuracy while delivering a 1x10^6 times speedup. We demonstrate that SALT can capture security threats in contingency scenarios without exception --- whereas PF-based analyses reported 75% fewer rated line violations, 18% fewer Q-limit violations, and 7% fewer voltage violations.

0.20

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.56
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Grid-forming Control of Offshore Wind through a Diode-Rectifier HVDC System: a 2 GW Case Study

eess.SY ·2026-11-08 ·Ishi Nigam, Saif Alsarayreh, Tuanku Badzlin Hashfi, Miloš Cvetković, Joris van Doorn +1 more
similarity 0.55
Abstract

Diode-rectifier-unit (DRU)-based high-voltage direct current (HVDC) transmission considerably reduces the volume and weight of the offshore converter platform for remote wind farms and, hence, its cost, but shifts the task of forming and regulating the offshore AC network to the wind-turbine converters. This paper examines which grid-forming control strategy is the most suitable for DRU power transfer. The DRU commutation relationship shows that the delivered active power depends on the offshore voltage magnitude (but not on the converter voltage angle), so the angle-based active-power loop of virtual synchronous machine control is not closed through the rectifier. A $P-V/Q-ω$ grid-forming architecture, which regulates active power via the voltage magnitude and derives frequency from the reactive power error, is therefore adopted. Electromagnetic transient simulations of a 1GWaggregated grid-forming turbine on a 66 kV collector network with a $\pm$525 kV bipolar DRU link show that the commanded power is delivered over 800 to 1000MW with the offshore voltage held near nominal. The paper also examines how grid-forming operation changes the allocation of control duties within the Type-4 turbine: once the grid-side converter forms the network, DC link regulation must move to the machine-side converter, which limits the achievable bandwidth of the DC-link control. Extending the system to 2 GW with two 500 MW grid-following units achieves full power transfer in simulation, but with the grid-forming converter loaded beyond its continuous rating and a steady-state offshore frequency deviation of approximately 1.8 Hz.

0.34

Relative-Degree Wall Restricts Passivity-Based Stability Analysis in Inverter-Dominant Grids

eess.SY ·2026-08-30 ·Xiaoyu Peng, Zhongze Li, Xi Ru, Xinghua Chen, Feng Liu
top venue similarity 0.54
Abstract

This letter reveals a fundamental limitation of passivity-based distributed stability analysis in power systems. Under the standard formulation, passivity certification inherently imposes a relative-degree compatibility constraint that excludes many high-fidelity inverter dynamic models (e.g., those that include electromagnetic transients). Potential extensions of passivity frameworks are discussed to break this limitation.

0.43

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part I

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.54
Abstract · 15 pages, 10 figures

The rise of renewable generation in AC power systems calls for small-signal stability assessment methods that do not rely on centralised, system-wide models. In this two-part paper, we present a decentralised stability framework based on frequency-domain conditions imposed on local subsystems (many admitting equivalent graphical interpretations) which collectively imply the stability of the entire grid. The framework generalises many previously reported results, with added flexibility and plug-and-play compatibility provided by the additional degrees of freedom of the imposed conditions, the ability to mix conditions across frequency ranges, conditions on extended subsystems that couple buses to their connecting lines and loads, and a method to incorporate unstable subsystems. Detailed, heterogeneous device and line models are accommodated in the frequency domain using impedance, admittance, and power-flow models, making the framework suitable as a foundation for grid codes that enable plug-and-play functionality in inverter-dominated grids. Part I focuses on stable impedance and admittance representations and Part II extends the results to unstable subsystems, which are shown to be fundamentally present in many grid models. The results of Part I are validated on a modified 9-bus case study, demonstrating the reduced conservatism and significance of the proposed approach.

0.54

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part II: Unstable Subsystems

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.54
Abstract · 15 pages, 13 figures

Part I of this paper presented a decentralised framework for certifying small-signal stability in AC grids using frequency-domain quadratic constraints on individual grid subsystems. Part II extends the framework to a broader class of networks that contain unstable subsystems. In particular, we show that such unstable subsystems arise in many common scenarios, even when the aggregate system is stable and well behaved. Such subsystems must be stabilised by the closed-loop network interconnection, which complicates decentralised stability analysis. A stable hybrid representation resembling the power (PQ) model at low frequencies and the impedance (IV) model at high frequencies is then defined, to which the stability framework of Part I can be applied, allowing plug-and-play compatible conditions to be formulated. Furthermore, we show that at low frequencies, the characteristic loci in the Nyquist plot of the return ratio in this hybrid representation decouple into unbounded and bounded branches along the classical $P$-$δ$ / $Q$-$V$ separation, and give sufficient conditions on each branch for ensuring system stability. The results are validated on the Kundur two-area system, where stability is certified, with a decentralised, plug-and-play compatible grid code covering the frequency ranges in which electromagnetic interactions arise.

0.30

Harmonic Stability of Power Systems: A Control-Theoretic Definition and Assessment Criteria

eess.SY ·2026-08-20 ·N. Bhoir, A. Sarkar, J. E. Machado, J. Schiffer
similarity 0.52
Abstract

Harmonic interactions have become a defining dynamic stability phenomenon in converter-based power systems (CBPSs). However, a formalization of the notion of harmonic stability in the context of nonlinear dynamical systems is not available thus far. In this paper, we propose a definition of harmonic stability formulated as a combination of two standard stability notions, namely, bounded-input bounded-output (BIBO) and internal stability properties with respect to any nominal periodic trajectory. Moreover, we rigorously show that the local harmonic stability of any nominal periodic trajectory of nonlinear CBPSs is implied by the stability properties of its linear time-periodic (LTP) approximation. In addition, to enable computationally tractable stability assessment, we develop a framework based on harmonic state-space (HSS) representations of LTP models. In particular, we provide time-invariant linear matrix inequality (LMI) conditions to certify harmonic stability. The proposed methodology is illustrated on a grid-following converter system, where the HSS-based analysis numerically confirms harmonic stability around the periodic operating trajectory.

0.29

An Energy-Based Framework for Transient Stability of Grid-Forming Converter Networks With Current Limiting

eess.SY ·2026-09-29 ·Wei Zhou, Yunjie Gu
similarity 0.52
Abstract · 10 pages, 6 figures

Existing analyses for the transient stability of grid-forming (GFM) converters under current limiting mainly address single-converter systems, while network-level transient stability analysis remains challenging. This paper develops a network energy construction that incorporates current limiting while retaining a provable dissipation property. This structure enables Lyapunov-based analysis consistent with classical direct method for synchronous-machine based systems, without switching between mode-dependent energy functions. A two-GFM example using a reactive circular current limiter and impedance insertion illustrates the proposed framework. Electromagnetic transient simulations support the theoretical results.

0.25