Harmonic Stability of Power Systems: A Control-Theoretic Definition and Assessment Criteria

N. Bhoir, A. Sarkar, J. E. Machado, J. Schiffer

eess.SY ·submitted 2026-08-20 12:49 UTC · v1

Abstract

Harmonic interactions have become a defining dynamic stability phenomenon in converter-based power systems (CBPSs). However, a formalization of the notion of harmonic stability in the context of nonlinear dynamical systems is not available thus far. In this paper, we propose a definition of harmonic stability formulated as a combination of two standard stability notions, namely, bounded-input bounded-output (BIBO) and internal stability properties with respect to any nominal periodic trajectory. Moreover, we rigorously show that the local harmonic stability of any nominal periodic trajectory of nonlinear CBPSs is implied by the stability properties of its linear time-periodic (LTP) approximation. In addition, to enable computationally tractable stability assessment, we develop a framework based on harmonic state-space (HSS) representations of LTP models. In particular, we provide time-invariant linear matrix inequality (LMI) conditions to certify harmonic stability. The proposed methodology is illustrated on a grid-following converter system, where the HSS-based analysis numerically confirms harmonic stability around the periodic operating trajectory.

Closest papers

Nearest neighbours by meaning across the whole index.

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.58
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16

Compositional Data-Driven Small-Signal Stability Assessment of Power Systems via Output Differential Passivity

eess.SY ·2026-11-16 ·Peng Yang, Xiaohui Zhang, Xi Ru, Feng Liu
similarity 0.58
Abstract · 14 pages

This paper proposes a compositional data-driven small-signal stability assessment framework for interconnected power systems based on output differential passivity (ODP). Without requiring explicit device models, local ODP matrices and scalar indices are estimated directly from measurement trajectories. When internal states are available, trajectory-based linear matrix inequalities (LMIs) are constructed from input-state measurements to estimate the local ODP matrices and scalar indices. When internal states are unavailable, an extended-state representation is constructed from input-output measurements, enabling the same assessment using only external signals. The estimated ODP matrices are combined with the network coupling matrix for compositional assessment of power system stability, while their scalar indices enable decentralized assessment. To address the computational and numerical challenges of trajectory-based LMIs, we introduce right-inverse whitening (RIW) to remove redundant behavioral coordinates and improve computational efficiency, and apply instrumental-variable (IV) preprocessing to alleviate numerical ill-conditioning and mitigate noise effects. Case studies on a modified IEEE 39-bus power system show that ambient measurements satisfy the required informativity conditions and that both formulations yield estimates close to model-based references under the tested noise levels. The reusable local ODP estimates also enable modular stability reassessment after controller updates.

0.30

Characterisation of the DQsym Framework Against Harmonic State-Space and Dynamic Phasor Models for Modular Multilevel Converters

eess.SY ·2026-11-13 ·Saif Alsarayreh, Robert Dimitrovski, Aleksandra Lekic'
similarity 0.58
Abstract · Submitted to the 25th IET International Conference on AC and DC Power Transmission

Modern power systems rely on power converters that exhibit multifrequency periodic dynamics, such as modular multilevel converters (MMCs). Such converters are commonly analysed using harmonic state-space (HSS) and dynamic phasor (DP) representations. Both approaches rely on building state matrices based on the system topology, whose size grows with the number of harmonics retained in the model. This paper shows that a symmetrical direct-quadrature (dq) dynamic phasor formulation for time-domain simulation, named DQsym, has a smaller solver state matrix than HSS and DP, and whose size is independent of the truncation order K. This reduction results from evaluating harmonic coupling outside the state matrix, in the nonlinear signal blocks. The open-loop MMC model used in this paper is derived in three harmonic-domain (HD) formulations and validated against a three-phase time-domain reference model. The models are compared in terms of state-space size and sparsity, harmonic content, steady-state accuracy and eigenvalues. For truncation at K = 4, the DQsym solver has 45 states against 135 for HSS and DP, stays within about 4% of the reference, and, once closed with its coupling blocks, yields eigenvalues identical to those of HSS and DP.

0.23

Scalable Small-Signal Stability Assessment of Power Systems Based on Frequency-Domain Quadratic Constraints

eess.SY ·2026-09-28 ·Xiaoying Liu, Linbin Huang, Hangyu Chen, Huanhai Xin
similarity 0.55
Abstract

Small-signal stability analysis of power electronics-dominated power systems is becoming increasingly challenging due to the large-scale integration of heterogeneous grid-following (GFL) and grid-forming (GFM) converters. Classical centralized methods, such as eigenvalue analysis and the generalized Nyquist criterion, provide direct stability assessment tools but exhibit limited scalability as the system size increases. This motivates scalable analysis methods for stability assessment and device-level diagnosis, and calls for less conservative stability conditions. To this end, this paper proposes a scalable small-signal stability assessment method with quantitative stability indices for multi-converter systems based on frequency-domain quadratic constraints (FQCs). It is shown that several existing stability conditions, including geometric conditions based on the Davis-Wielandt (DW) shell, numerical range, $x$-$z$ graph, scaled relative graph (SRG), mixed gain-phase condition, and passivity condition, are special cases of the FQC-based stability condition. This FQC-based formulation also clarifies the requirements for decentralized verification of these existing stability conditions. To further reduce conservatism, a full-multiplier FQC-based stability condition is developed, based on which an optimization problem is formulated for scalable stability certification and device-level diagnosis using quantitative stability indices without relying on graphical inspection. Combined with the mixed gain-phase condition, this optimization problem forms a hierarchical screening-diagnosis procedure that improves efficiency. Case studies demonstrate that the proposed method is less conservative than existing criteria and can effectively identify problematic devices associated with potential instability risks.

0.40

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.55
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

An Analytical Review of Model Order Reduction Methodologies of Converter-Dominated Power Systems for Stability Studies

eess.SY ·2026-10-02 ·Goran Grdenić, Marco Fraccaro, Josipa-Pina Milišić
similarity 0.55
Abstract · 53 pages, 4 figures

The rapid integration of renewable energy sources is transforming modern electric power systems into converter-dominated networks characterized by complex multi-timescale dynamics and new stability interactions over a wide frequency range. Accurate analysis of these phenomena requires high-fidelity models of transmission networks and power electronic converters, which often result in large-scale differential-algebraic systems with significant computational burden. This paper provides an analytical review of model order reduction techniques for converter-rich power systems, with particular emphasis on the key equations employed in the reduction process. Advantages and limitations of commonly used strategies, including timescale-based singular perturbation, projection-based, operator-based, data-driven, and machine-learning based methods, are discussed. The synthesis highlights key challenges related to harmonic interactions and multi-frequency dynamics, and outlines directions for the development of computationally efficient yet dynamically accurate reduced-order models for future power systems.

0.29

Data-Driven Static Output-Feedback Control for Multi-Agent Systems

eess.SY math.OC ·2026-10-02 ·Paul Serna-Torre, Adam Sedlak, Patricia Hidalgo-Gonzalez
similarity 0.54
Abstract

This work proposes a data-driven framework that synthesizes output-feedback control for linear time-invariant multi-agent systems (MAS). We first develop two algorithms that use offline data samples of state and input trajectories to determine a Nash equilibrium (NE) for MAS. Next, we formulate a semidefinite program that, given the NE solution, computes the static output-feedback controllers for the agents in MAS. Compared to prior work, virtues of our framework include weaker controllability assumptions, the absence of online information and data-driven estimation of states. Next, we use the proposed framework to design control schemes for voltage and frequency regulation for nonlinear multi-nodal electrical networks with grid-forming and grid-following inverters. Thus, compared to prior work that implements their data-driven frameworks in small-scale numerical examples, we validate the performance of our data-driven framework in high-fidelity nonlinear models of MAS. This implementation in realistic MAS provides insights that small-scale numerical examples may fail to capture. Results show successful grid stabilization and provision of regulation services from the inverters in the grid using our proposed framework. It can attain up to 78% less overshoot and 30% faster settling time than traditional strategies such as proportional-integral control.

0.30

Constructive Port-Hamiltonian Energy Shaping Design of Dispatchable Virtual Oscillators in Grid-Forming Converters

eess.SY ·2026-09-01 ·Lu Gao, Lihui Yang, Feng Ji, Dong Liu, Longze Kou
similarity 0.54
Abstract

Port-Hamiltonian (PH) theory offers a passivity-based framework for grid-forming control, yet conventional dispatchable virtual oscillator control (dVOC) does not naturally admit a dissipative PH realization, since its amplitude egulation, synchronization, and power dispatch are inherently coupled without a unified energy interpretation. This paper formulates the outer-loop dynamics as a dissipative PH system, thereby unifying amplitude regulation, synchronization, and power dispatch within one energy structure. The formulation rests on the key property that logistic-type radial regulation, characterized by an inherent saturation-like nonlinearity, permits an exact gradient decomposition compatible with the quadratic energy storage. On this basis, a unified shaped Hamiltonian is constructed, which encapsulates both amplitude restoration and power dispatch. Radial gain matching derived from this Hamiltonian yields explicit closed-form arameter inequalities that guarantee almost-global asymptotic stability and local exponential convergence. Moreover, tuning the power-error weighting coefficient actively shapes the energy landscape, thereby eliminating the undesirable low-voltage power-flow solution from the stationary set and ensuring convergence to the desired high-voltage equilibrium point. The Hessian singularity condition further provides the critical weight threshold that guarantees uniqueness of the high-voltage equilibrium. Numerical simulations validate the proposed method.

0.24