Active Filter Design for Buffering Datacenter-Scale Power Fluctuations from Training AI

Dillon Jensen, Grant Wilkins, Obi Nnorom, Hugo Budd, Phil Levis, Juan Rivas

eess.SY ·submitted 2026-09-11 19:57 UTC · v1

Abstract

Training large AI models requires thousands of processors working in parallel. This synchronized load poses a challenge for traditional power delivery architectures, because IT power ramps much faster than grid hardware can compensate. This paper presents a hardware solution to this problem, introducing a novel power delivery architecture which automatically detects changes in load power and compensates using on-rack energy storage, giving time for the grid to respond to the varying load. The architecture is validated experimentally, powering a training load while limiting the grid-side power ramp rate such that it stays within pre-specified range. The prototype presented is rated to deliver up to 10 kW of buffered power in a 400 VDC system, with a bill of materials cost of $3,500 USD. The system design is described in detail. A key advantage of this architecture versus other approaches is that it reliably buffers power fluctuations without requiring any changes to system software, making it compatible with any training workload.

Comment
8 pages, 11 figures

Closest papers

Nearest neighbours by meaning across the whole index.

From Grid to Chip: Power Architecture, Stability, and Flexibility of AI Data Centers

cs.ET cs.AReess.SY ·2026-09-10 ·Yubo Song, Rui Kong, Takuro Umihara, Pooya Davari, Frede Blaabjerg +1 more
hot direction similarity 0.67
Abstract · The manuscript has been submitted for review to IEEE Open Journal of Power Electronics

The rapid growth of artificial intelligence (AI) computing is transforming data centers into large, dynamic electrical loads. Their deployment is primarily constrained by energy availability and grid-connection capacity, which is further aggravated by the ability of power-delivery architectures, control systems, and computing workloads to operate reliably during fast grid disturbances. This article presents a technological perspective on AI data centers as grid-interactive computing systems. First, it reviews grid-integration bottlenecks, evolving connection policies, grid-code requirements, which has fostered new technological trends via spatio-temporal flexibility available through workload orchestration, cooling systems, on-site resources, and energy storage. Second, it maps the evolution of power-delivery architectures from medium-voltage grid interfaces to chip-level, discussing higher-voltage DC distribution, solid-state transformers, wide-bandgap devices, advanced chip-level power delivery, and liquid cooling. Third, it establishes a three-level stability framework spanning rack-level DC-bus dynamics, facility-level converter interactions, and system-level grid-coupled behavior. The framework connects dominant instability mechanisms, including constant power load effects, impedance interactions, forced oscillations, and operating-mode transitions, with suitable modeling, assessment, and mitigation approaches. Synthesizing these topics, this article highlights grid-to-chip co-design as a central requirement for scalable AI infrastructure, linking computing workloads, power-delivery systems, energy buffers, and grid operation.

0.27

AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated Solutions

eess.SY ·2026-10-06 ·Mariam Mughees, Yuzhuo Li, Yize Chen, Yunwei Ryan Li
survey similarity 0.65
Abstract

Artificial intelligence (AI) workloads are creating large, power-electronic loads whose effects on power systems depend on location, temporal variability, controllability, and interactions with other loads and resources. Annual electricity consumption alone cannot capture these effects. This review examines how AI data centers affect power systems stability, renewable-energy integration, and low-carbon planning by tracing the power-delivery chain from accelerators and workloads through rack converters, uninterruptible power supplies (UPS), storage, and microgrids to the transmission point of interconnection. Reported oscillatory events and multi-gigawatt load transfers highlight how facility responses can amplify disturbances, while programmable workloads and controllable power converters offer opportunities for demand flexibility. Challenges and mitigation strategies are organized across device, rack, facility, and power systems levels, spanning millisecond-to-year timescales. A bandwidth-matching framework relates disturbances to the response capabilities of mitigation resources. The review distinguishes computational energy efficiency from power systems and sustainability outcomes: lower energy consumption per token does not necessarily reduce peak demand, electrical disturbances, or carbon emissions. It examines how coordinated workload scheduling, grid-interactive UPS systems, storage, high-voltage DC distribution, and flexible interconnection can support reliability, efficiency, and decarbonization. Key research needs include dynamic load models, high-bandwidth telemetry, carbon-and grid-aware scheduling, and mechanisms for valuing flexible computational demand.

0.08

Communication Delay Robust Control of BESS for AI Training Load Smoothing

eess.SY ·2026-09-18 ·Xue Lyu, Wei Du, Sheik Mohammad Mohiuddin, Brett A. Ross
hot direction similarity 0.64
Abstract · 10 pages, 17 figures

AI training loads can exhibit rapid power fluctuations because their power demand differs significantly between computational and communication phases, creating challenging ramp rates at the data center point of common coupling (PCC). Integrating battery energy storage systems (BESS) in data centers is a promising mitigation option. This paper proposes a hybrid BESS control strategy that combines droop-based grid-forming (GFM) control with instantaneous load current-based compensation to suppress high frequency load fluctuations. The GFM control loop regulates the long-term power exchange of the BESS, while the load-following control provides fast compensation for short-term AI workload fluctuations. Communication delay between the load current measurements and the BESS controller is explicitly modeled, and its impact on smoothing performance is analyzed. To mitigate delay-induced degradation, a predictor-based compensation method is incorporated into the BESS control structure. High-fidelity electromagnetic transient simulations are conducted to validate the proposed approach. Results demonstrate effective smoothing of AI training load fluctuations across different grid strength conditions and under time varying communication delays.

0.28

Grid Demand Flexibility Assessment of AI Data Centers via Batch Workload Temporal Shifting

eess.SY ·2026-09-29 ·Suntao Su, Liang Du, Shengyi Wang
similarity 0.63
Abstract · 5 pages, 5 figures, conference

The rapid growth of artificial intelligence (AI) data centers has introduced new challenges to power system operation. As their power demand becomes larger and more variable, quantitatively characterizing their demand flexibility is increasingly important for effective power system coordination. However, heterogeneous workload characteristics and resource requirements make this flexibility difficult to characterize directly. This paper proposes a framework for assessing the grid-compatible demand flexibility of AI data centers via batch workload temporal shifting. An averaging-based resource usage processing method is developed to map fine-resolution CPU, GPU and memory usage into unified time intervals compatible with power system operation. A workload temporal scheduling model is then formulated to shift batch workloads while preserving execution continuity, delay constraints, and server resource capacities, and is coupled with a utilization-dependent server power model to translate workload scheduling decisions into server power demand. Two complementary flexibility metrics are evaluated: short-term peak demand shaving and the maximum duration of sustained power reduction. Numerical results based on real GPU cluster traces demonstrate that workload temporal shifting can provide quantifiable and grid-compatible demand flexibility for AI data centers with limited disruption to computing workloads.

0.13

Mitigating the Grid Impact of Gigawatt-Scale AI Data Centers via High-Fidelity Model Flexibility

eess.SY math.OC ·2026-11-18 ·Eihab E. E. Ahmed, Saeed Manshadi
hot direction similarity 0.62
Abstract

Gigawatt-scale artificial intelligence data centers (AIDCs) are being connected at a single point of interconnection (POI) faster than transmission can be reinforced, yet studies of their flexibility rely on DC power flow and simplified load envelopes that omit voltage, cooling dynamics, and workload deadlines. This paper addresses this gap by embedding a high-fidelity AIDC model, with separate inference and training pools, hall thermal mass, PV, a battery energy storage system (BESS) with reactive capability, and a STATCOM, in a five-minute multi-period AC optimal power flow. Simulations on the RTS-GMLC test system show that active-power flexibility mitigates local price spikes and relieves congestion, whereas reactive support from the BESS inverter or a STATCOM is needed to keep the POI voltage away from sagging around its 0.95~pu limit. Sensitivity analyses show that cost-driven charging of large batteries can induce new morning congestion and that storage largely substitutes for wider workload deferral.

0.30

A principled approach for energy-efficient training via phase-aware GPU frequency tuning

cs.DC cs.LG ·2026-09-21 ·Miguel Braga, Júlio Pinto, Rahma Nouaji, Olivier Michaud, Bettina Kemme +3 more
similarity 0.61
Abstract

Modern AI model training imposes unprecedented computational demands, making it a key contributor to datacenter energy consumption. Yet a significant fraction of the energy consumed during training does not translate to useful computation due to bottlenecks throughout the training pipeline. We present PAFT, a phase-aware, dynamically adaptable GPU frequency tuning system that reduces energy consumption of training workloads with minimal performance overhead. The key insight behind PAFT is that bottlenecks represent an energy optimization opportunity, rather than purely a performance problem: when GPUs are bound to stall, PAFT opportunistically reduces their clock frequencies to match the pace of bottlenecked devices, saving energy without impacting execution time. PAFT achieves this by continuously monitoring pipeline behavior and applying fine-grained frequency adjustments, adapting to workload and system changes. Experiments conducted on twelve widely used models show that PAFT consistently outperforms all baselines, achieving energy savings of up to 46% with an average overhead of 4%.

0.14

How AI Load Swings Reduce Datacenter Power Conversion Efficiency

cs.AR eess.SY ·2026-10-23 ·Heetarth Joshi, Ali Alenezi, Fang Chen Lin, Prasad Enjeti, Xiaoyang Wang +1 more
similarity 0.61
Abstract

AI training and inference workloads make GPU power swing repeatedly between compute and communication phases. As a result, the cascaded converters in a datacenter rack keep moving between operating points with different efficiencies. This paper uses an energy based, cycle averaged method to quantify that effect along a 240 V AC to 400 V DC to 51 V DC rack power path, using measured efficiency curves of commercially available GaN based PFC and LLC converters. For a 1 Hz, 50% duty-cycle load swinging between 5 kW and 510 W, conversion efficiency falls to 95.97%, compared with 96.82% at the equivalent constant average load, a loss of 0.88%. When 51/48V to 1V point of load conversion to the chip rail is included, it is shown that the loss grows to 1.66% (89.45% vs. 90.96%). These results show that efficiency rated at average load overstates real world performance, and that the penalty grows with each load dependent conversion stage between the grid and the GPU.

0.24

Slasher: Power Flexibility for Cloud Datacenters

cs.DC cs.OSeess.SY ·2026-08-26 ·Liuzixuan Lin, Fiodar Kazhamiaka, Alok Gautam Kumbhare, Chaojie Zhang, Jaylen Wang +8 more
similarity 0.60
Abstract · 18 pages, 15 figures

Datacenters consume many megawatts of power, and regularly encounter scenarios that require modulating their power draw. These scenarios include datacenter infrastructure failures, power grid failures, grid services, and more, spanning a diverse range of requirements in terms of the power magnitude, the scope of the reduction, the notice time, and other dimensions. To address these scenarios, we have built Slasher, a general system for modulating the power of \azure datacenters to handle scenarios ranging from individual racks to regional multi-datacenter grid events. Slasher coordinates datacenter resources with the goal of meeting power targets while minimizing negative impact on hosted workloads. In this paper, we review the main power modulation scenarios, characterize the power reduction levers using data from production cloud datacenters, describe Slasher's system architecture, and formulate the cloud datacenter power modulation control problem. We also develop a high-fidelity datacenter simulator and propose a workload impact model, using them to design and evaluate power control algorithms.

0.31