CS Paper Radar

Privacy-Preserving Coordinated Operation of Power Grids and AI Data Centers: A Checkpoint-Aware Three-Phase Scheme

Ziang Liu, Ruizhang Yang, Xin Cui, Francis Yunhe Hou

eess.SY ·submitted 2026-09-22 13:07 UTC · v1

Abstract

The rapid growth of large language model training and serving is driving AI data centers (AIDCs) toward gigawatt scale. Unlike conventional commercial loads, AIDCs possess significant operational flexibility through dynamic voltage and frequency scaling (DVFS) of training and inference workloads, while periodic model checkpointing can induce abrupt power drops and rebounds that erode operating reserves and increase transmission congestion risks. Coordinating AIDC operation with grid scheduling under these unique operational characteristics is challenging because grid and AIDC operators are generally unwilling to share proprietary data and decision-making authority. This paper proposes a hierarchical privacy-preserving coordinated operation scheme between the power grid and AIDCs to address this gap. The proposed scheme contains three phases. In Phase I, the grid operator computes a certified inner approximation of the AIDCs security region for subsequent coordination. In Phase II, the AIDC operator coordinates training and inference AIDCs to optimize workload allocation within the certified security region and generate power schedules and checkpoint alerts. In Phase III, the grid operator solves a checkpoint-aware two-stage robust optimal power flow (OPF) considering renewable generation and checkpoint uncertainties. By exchanging only compact interface information, the framework preserves the privacy of both grid and AIDCs, avoids frequent iterative communication, and enables secure coordination with guaranteed feasibility. Numerical studies on a modified IEEE 14-bus system and a modified NYISO system demonstrate the effectiveness, robustness, and security of the proposed framework.

Comment
10 pages

Closest papers

Nearest neighbours by meaning across the whole index.

Data Center Load Accommodation under QoS and Checkpoint-Induced Frequency Security Constraints

eess.SY ·2026-10-16 ·Ruolan Cui, Ziang Liu, Chenxi Hu, Francis Yunhe Hou
benchmark similarity 0.71
Abstract · 10 pages

The rapid growth of artificial intelligence workloads is accelerating the expansion and grid interconnection of data centers (DCs). Existing data center load accommodation (DCLA) assessments primarily focus on grid and resource adequacy and often imply that greater workload flexibility always increases accommodable capacity. However, workload flexibility has a dual effect. Workload deferral and temporal shifting can alleviate network congestion, whereas synchronized checkpointing of training workloads can cause large and rapid load reductions, threatening frequency stability. Therefore, DCLA cannot be determined solely by grid adequacy. This paper develops an optimal DCLA method that jointly accounts for workload quality of service (QoS), checkpoint-induced frequency security (FS), and grid adequacy. First, a QoS-aware model characterizes workload-dependent flexibility while ensuring service feasibility. Second, checkpoint-induced FS constraints are developed for periodic and event-triggered power variations, with key frequency-security limits reformulated in algebraic form. Third, a two-stage lexicographic model is developed to maximize DCLA and minimizes the required energy storage (ES) deployment, and then optimizes system operation under the given DC and ES siting and sizing decisions. Case studies show that the proposed method avoids a 40.3% overestimation of DCLA compared with the grid-adequacy benchmark. QoS is the primary limiting factor, while checkpoint-induced frequency-security constraints become more restrictive as training workloads increase. These findings highlight that reliable DCLA should account for both its grid-support value and the associated QoS and FS risks.

0.16

Execution-Feasible Dispatch of LLM Pre-training Loads for Renewable-Dominant AI Data Centers

cs.DC ·2026-10-09 ·Xi Tong, Ershun Du, Haiyang Jiang, Long Chen, Qin Wang
similarity 0.67
Abstract · 12 Figures, 6 Tables

AI data centers (AIDCs) are emerging as large power-system loads, making their operational flexibility increasingly valuable. Existing studies often treat AIDC demand as continuously adjustable or generically delay-tolerant, which overstating the flexibility of large language model (LLM) pretraining. This paper proposes an execution-feasible dispatch framework for LLM pre-training in renewable-dominant AIDCs. LLM descriptors are first converted into checkpoint-domain daily workloads, then mapped to feasible 3D-parallel GPU modes with explicit throughput, GPU-capacity, memory, and IT-power limits. The resulting checkpoint- and mode-constrained load states are embedded into a day-ahead power dispatch model. Case studies on a 2048 GPUs AIDC with two LLaMA pretraining tasks show that checkpoint-aware 3D dispatch reduces operating cost by 20.02% and renewable curtailment from 1.077 to 0.014 MWh relative to fixed continuous training. Related results also show that checkpoint records alone do not create load flexibility,practical grid-interactive flexibility arises from checkpoint waiting combined with execution-feasible 3D-mode compensation.

0.20

HXAI: Hierarchical Privacy-Preserving Explainable AI in Distributed Energy Systems

cs.AI ·2026-10-01 ·Poushali Sengupta, Sabita Maharjan, Frank Eliassen, Yan Zhang
similarity 0.66
Abstract · Under Review

Balancing electricity demand and supply is increasingly difficult due to the inherent intermittency of renewable power generation and the stochastic power consumption. Grid operators require fine-grained, decision-relevant insights into household energy consumption to manage peak loads and design responsive tariffs, but increased transparency at this level raises significant privacy concerns. Traditional methods for explainable AI (XAI) can reveal sensitive information, while standard privacy techniques often reduce the usefulness of explanations. To address this issue, we introduce HXAI, a hierarchical framework that preserves privacy while enabling reasonable explainable analysis for grid-level demand management. HXAI consists of two main components: (1) a local model that generates fine-grained explanations within a secure, private environment, and (2) a zonal model that aggregates these explanations to support grid-level analysis while enforcing privacy through flexible privacy-budget management. We explicitly limit cumulative privacy exposure under repeated operator queries and show that the proposed framework preserves decision-relevant information without compromising household privacy. Experiments on both simulated and real-world energy datasets demonstrate that HXAI provides useful insights for zonal load management while ensuring that appliance-level consumption remains local and is never transmitted to grid operators. Our results show that preserving the semantic structure of explanations, rather than minimizing numerical error, is the key to XAI under differential privacy. This framework provides a way to achieve both privacy and explainability in energy management.

0.15

AIDC Microgrid Vulnerability Assessment Under Computing-Power Coordinated Attacks

eess.SY ·2026-08-11 ·Ze Yu, Hongwei Zhen, Chao Shen, Mingyang Sun
similarity 0.65
Abstract

The rapid growth of large language model (LLM) services is expanding AI data centers (AIDCs), increasing electricity demand and associated carbon emissions. Renewable energy integration can mitigate these impacts but also strengthens the coupling between AIDC loads and inverter-interfaced generation, creating cross-domain cyber-physical vulnerabilities. Specifically, adversarial AI requests alter AIDC power demand, whereas inverter control tampering modifies source-side dynamics, and their combined impact on system stability varies with generation forecast and demand response uncertainties. To this end, we propose an uncertainty-aware AIDC microgrid vulnerability assessment framework under computing-power coordinated attacks. First, the framework maps adversarial AI requests to AIDC power variations and represents uncertainties in attack-induced demand responses and photovoltaic (PV) forecasts through confidence-weighted realizations. Then, impedance based stability analysis combines these realizations with bounded inverter parameter tampering to construct attack reachable domains and identify critical attack time windows. Furthermore, a separate criterion identifies fixed coordinated attack vectors that retain destabilizing capability throughout each selected window. Case studies demonstrate that, unlike either attack component applied alone, coordinated attacks within identified critical windows induce sustained inverter frequency oscillations with peak absolute deviations exceeding 20% of nominal frequency, whereas the evaluated out-of-window response remains bounded. The proposed method further identifies critical attack windows and the associated coordinated attack vectors.

0.04

Privacy-Preserving Coordinated Operation of Multi-Player Industrial Network Using Secure Aggregation

cs.CE ·2026-09-14 ·Akshdeep Singh Ahluwalia, Zachary Wilson, Jeffrey E. Arbogast, Can Li
benchmark similarity 0.64
Abstract · Abstract shortened to meet arXiv's 1,920-character metadata limit

Electrified chemical industries with operational flexibility can reduce operating costs by shifting production and distribution decisions in response to time-varying electricity prices. However, chemical plants operate within process networks where coordinated demand response can exploit flexibility across multiple stakeholders. Centralized coordination requires access to stakeholders' local scheduling models and proprietary operational data, often incompatible with data-privacy requirements. Distributed optimization with an independent central coordinator (ICC) avoids direct model sharing, but iterative exchange of coupling variables can still reveal private model parameters. We propose a privacy-preserving distributed coordination framework for coordinated demand response in industrial networks. The framework integrates secure aggregation with an ICC-based alternating direction method of multipliers (ADMM) algorithm, so plant-level messages are numerically masked and become useful to the ICC only after aggregation. We test the framework on a multi-plant industrial gas network in which three air-separation units jointly schedule production and shipments to shared customer regions. To support stable participation, we incorporate a two-phase revenue-sharing mechanism that reallocates savings so every plant improves relative to its decentralized status quo. In a 31-day rolling-horizon simulation with synthetic data representing heterogeneous electricity prices and demand, the coordinated policy reduces total network cost by 19.77% relative to decentralized operation and achieves a full-month cost within 3.08% of a centralized social-welfare-maximization benchmark. We further quantify a conservative worst-case collusion mode, showing how unmasked iterates and auxiliary information can expose private objective parameters.

0.25

Profile Screening and Frequency-Secure Operating Limit Derivation for Data Center Microgrids

eess.SY ·2026-11-17 ·Zishuo Yang, Yu Ma, Jong Ha Woo, Aaditya Pandey, Wenyuan Tang +2 more
similarity 0.62
Abstract

Rapid power variations from artificial intelligence (AI) workloads pose frequency-security challenges for islanded data-center microgrids. This paper proposes a generator step- response-based framework to rapidly screen candidate load pro- files and derive frequency-secure operating limits for IT workload scheduling. Identified generator responses are superimposed to assess the cumulative frequency effects of successive load changes without repeated dynamic simulations. The framework identifies potentially unsafe intervals and determines allowable load magni- tudes, ramp rates, and minimum event spacing, while accounting for prediction uncertainty and governor limits. Validation on a 2.5 MVA islanded microgrid with eight generator configurations and 14 synthetic AI workload profiles shows that 94.75% of 40,208 assessment windows receive decisive screening labels, with no frequency-violating windows classified as secure.

0.37

Grid-Forming AI Data Centers: Coordinated Grid Support Control from IT Loads and Energy Storage

eess.SY ·2026-11-13 ·Xuechun Zhang, Zhiyi Zhao, Fei Teng, Zhen Wang
hot direction similarity 0.62
Abstract

To exploit the grid-support capability of AI data centers (AIDCs), this paper proposes a grid-forming (GFM) control scheme which coordinates the IT loads and energy storage (ES) in the AIDC. First, the framework of a grid-connected AIDC is presented, with the multi-stage power conversion from the grid to the IT loads presented. A dual GFM scheme is then proposed for the back-to-back converters to provide grid support through coordinated power adjustments from IT loads and ES. In addition, an aggregated power response model is established to characterize the IT-load flexibility considering multiple IT servers executing diverse tasks. Time-domain simulations of a 100 MW grid-connected AIDC demonstrate that the proposed control scheme can effectively support the grid.

0.25

Mitigating the Grid Impact of Gigawatt-Scale AI Data Centers via High-Fidelity Model Flexibility

eess.SY math.OC ·2026-11-18 ·Eihab E. E. Ahmed, Saeed Manshadi
hot direction similarity 0.62
Abstract

Gigawatt-scale artificial intelligence data centers (AIDCs) are being connected at a single point of interconnection (POI) faster than transmission can be reinforced, yet studies of their flexibility rely on DC power flow and simplified load envelopes that omit voltage, cooling dynamics, and workload deadlines. This paper addresses this gap by embedding a high-fidelity AIDC model, with separate inference and training pools, hall thermal mass, PV, a battery energy storage system (BESS) with reactive capability, and a STATCOM, in a five-minute multi-period AC optimal power flow. Simulations on the RTS-GMLC test system show that active-power flexibility mitigates local price spikes and relieves congestion, whereas reactive support from the BESS inverter or a STATCOM is needed to keep the POI voltage away from sagging around its 0.95~pu limit. Sensitivity analyses show that cost-driven charging of large batteries can induce new morning congestion and that storage largely substitutes for wider workload deferral.

0.30