Holonic Graceful Transitions Across Centralized, Decentralized, Distributed, and Local Control in DER-rich Cyber-Power Distribution System

Md Fazley Rafy, Niloy Patari, Anurag K. Srivastava

eess.SY cs.NI ·submitted 2026-08-15 20:07 UTC · v3

Abstract

The increasing penetration of distributed energy resources (DERs) in distribution system necessitates adaptive coordination frameworks. These frameworks must remain optimal during normal operation and resilient under cyber physical disturbances. Existing coordinated control approaches are typically deployed as static architectures with limited ability to adapt when communication degrades, local instability emerges, and operating conditions become spatially heterogeneous. This work addresses the gap by proposing a DER service-independent edge autonomous holonic adaptive coordination framework. In this framework, each DER controller executes its own control actions and transitions among centralized, distributed, decentralized, and local autonomous coordination modes without always relying on static coordination commands from the grid operator. The framework preserves coordination continuity across modes by retaining local controller states while reconfiguring only the coordination topology, information exchange pattern, and fallback action associated with the active DER service. Graceful transitions are enabled through dwell timers, rate limiting, and safety overrides to prevent dynamic instability during mode changes. Volt VAR control is used as a representative distribution automation application to validate the proposed architecture in a cyber-physical Hardware-in-the-loop (HIL) testbed. The proposed approach is evaluated under diverse cyber-physical event-based scenarios, showing region-confined adaptation under localized disturbance, reduced coordination traffic during coordination switching, and node-confined mitigation under cyber attack through edge anomaly detection and neighbor-corroborated impact estimation.

Comment
Need full revision of the paper due to strong comments from reviewers

Closest papers

Nearest neighbours by meaning across the whole index.

System-Level Factors Influencing AGC Cyber-Attack Success and RAS Vulnerability in Multi-Area Grids

eess.SY ·2026-10-30 ·Abdulmannan Ajabnoor, Zhi Jin Zhang, Maryam Saeedifard, Dominic Groß
published similarity 0.57
Abstract

Automatic generation control (AGC) stabilizes frequency and scheduled power exchanges among interconnected areas, yet its reliance on communication networks introduces cyber-vulnerabilities. This work examines coordinated AGC cyber-attacks in the presence of remedial action schemes (RAS) and identifies operating conditions under which an attacker can drive grid frequency beyond safe limits while evading RAS. A feedback-based attack policy is used to manipulate AGC signals and steer system frequency toward unsafe trajectories. Then, a large nested-loop parametric sweep---spanning attacked-area inertia relative to its interconnected neighboring area, AGC capacity versus maximum tie-line transfer, AGC update rate, load damping, and bi-directional power transfers---generates over 1.45 million scenarios. These are classified using a decision tree to establish guidelines to distinguish successful from unsuccessful attacks based on frequency deviations. The resulting vulnerability guidelines are validated on a three-area system using phasor-domain simulations with IEEE 9-bus area models, detailed turbine--governor dynamics, and under/over-frequency load and generation shedding. Results show that specific combinations of AGC capacity, inertia distribution, and pre-attack tie-line loading increase the likelihood of successful attacks, offering operators actionable criteria for identifying vulnerable operating conditions.

0.41

Decentralized Stability Certificates for Interoperability in Power-Electronics-Dominated Power Systems

eess.SY ·2026-10-19 ·Linbin Huang, Verena Häberle, Ruohan Leng, Huanhai Xin, Hua Geng +2 more
similarity 0.57
Abstract

The rapid integration of power electronics converters has fundamentally altered the power grid's dynamic landscape, making modularity of operation and interoperability of heterogeneous devices two critical hurdles for power system reliability. In control language, these challenges can be paraphrased as decentralized certificates on the input/output behavior of every device, assured by local control, so that stability and guaranteed performance of the interconnected system emerge. For the power system application, such certificates should eventually be part of the rule book, the so-called grid code, and thus be generic and minimally restrictive for the control architecture of each device. Classical system-theoretic angles of attack to these questions go back to dissipativity concepts, which have historically been co-developed in automatic control, circuit theory, and power systems. Since standard dissipativity (e.g., passivity or small gain) criteria fall short in terms of conservatism, a range of more flexible and advanced tools have been developed to assure less conservative decentralized certificates guaranteeing stability under interconnection as well as dynamic performance following a disturbance. In this article, we review a range of methods that have been put forward to tackle these questions, compare and validate them, and point towards practically relevant research gaps which are amenable to control-theoretic approaches. Moreover, we provide a tutorial exposition of practically relevant power systems/electronics issues accessible to control engineers.

0.17

Impact of Grid-Interactive Data Center Microgrids on Grid Reliability

eess.SY ·2026-11-11 ·Kiran Kumar Challa, Kumarsinh Jhala
hot direction similarity 0.56
Abstract · 5 Pages, 9 Figurs, Conference

Traditional data centers, operating as passive loads with standby backup resources, present significant challenges for grid integration due to their scale, rapid load fluctuations, and limited operational flexibility. This article investigates the transformative potential of grid-interactive data center microgrids, which integrate battery energy storage, on-site generation, and intelligent microgrid controllers to actively support both facility and grid operations. The proposed simulation framework enables the study comparing conventional and grid-interactive architectures under a range of steady-state and contingency scenarios. Results reveal that grid-interactive microgrids can substantially reduce peak grid demand, improve voltage stability, and improve system reliability especially when data center and system load peaks coincide. The findings highlight the critical role of coordinated resource management in enabling the reliable and efficient integration of large data center loads, and provide a practical methodology for assessing their system-level impacts.

0.26

Emergency Control of Transmission Voltages by Coordinating DERs From Multiple Substations

eess.SY ·2026-09-28 ·Francisco Escobar, Gustavo Valverde
top venue similarity 0.55
Abstract · Accepted in IEEE Transactions on Power Systems

Voltage stability can be endangered in transmission networks that operate under high strain and exhibit a large separation between generators and loads. During emergencies associated to voltage instability, one promising supporting countermeasure is to control large populations of Distributed Energy Resources (DERs) connected to medium- and low-voltage networks, so that they locally reduce the net load by modifying their power generation or consumption. However, it is challenging to achieve this control while anticipating interactions with legacy voltage regulators, coordinating efforts across substations, and exchanging small amounts of information with DERs. In this paper, we propose a control scheme that coordinates DER aggregations with the load tap changers of substation transformers, asks them to contribute power depending on the substation they are connected to, and relies on lightweight communication. Our simulations show that the proposed control can successfully coordinate DERs and load tap changers to enhance long-term voltage stability.

0.46

Optimal Coordination of Multiple Ancillary Service Provisions in Active Distribution Networks

eess.SY ·2026-11-14 ·Xinbao Jia, Yi Guo, Ognjen Stanojev, Zhen Chen, Yuning Jiang +1 more
similarity 0.55
Abstract · 16 pages

We propose a multi-rate model predictive control (MPC) framework for coordinating primary frequency control (PFC), automatic generation control (AGC), and voltage control (VC) in active distribution networks. The framework allocates distributed energy resource (DER) flexibility among these three ancillary services while retaining their different update rates. To account for the intertemporal flexibility of electric vehicle aggregations and aggregations of buildings with thermostatically controlled loads (TCLs), we incorporate time-varying power-energy envelopes into our multi-rate MPC formulation. These constraints couple the combined PFC and AGC response to the demand-side flexibility available later in the prediction horizon. Furthermore, the input-multirate structure enables coordinated ancillary service provision by DERs with different response dynamics. The controller optimizes the three services together, allowing fast regulation to be coordinated with the developing slow response within the available DER flexibility. We demonstrate the coordinated provision of the three ancillary services through closed-loop simulations on a modified IEEE 33-bus system using a nonlinear differential-algebraic model.

0.25

Tie-Line Scheduling Using Real-Time Contraction Metrics: Hierarchical Reachable Sets for Multi-Area Inverter-Dominated Grids

eess.SY ·2026-11-16 ·Richard Sherman
similarity 0.54
Abstract

Managing transmission congestion in multi-area power grids dominated by inverter-based resources (IBRs) requires bridging a severe timescale and modeling divide. Supervisory congestion optimizers -- such as Online Feedback Optimization (OFO) and two-tiered differentiable Model Predictive Control (MPC) -- rely on linearized, convex algebraic grid approximations that cannot guarantee dynamic stability during sub-second converter transients. Conversely, fast distributed consensus schemes like Alternating Direction Method of Multipliers (ADMM) depend on convex plant assumptions and iterative message exchanges that lag behind rapid tie-line surges. This paper replaces convex ADMM emergency consensus with a Distributed Nonlinear Separable Control Contraction Metric (SCCM) architecture spanning three nested tiers: the Device layer, the Area layer, and the Grid tie-line layer. By pairing online Prediction Error Method and Moving Horizon Estimation (PEM-MHE) parameter tracking with offline convex Linear Matrix Inequality (LMI) synthesis, the controller executes a closed-form nonlinear feedback law online without solving real-time optimization problems. We derive the Pontryagin attainable (reachable) ellipsoids for each layer, prove hierarchical tube containment via Schur-complement matrix inequalities, and project the certified Grid reachable tube through Power Transfer Distribution Factors (PTDFs) to supply guaranteed safe thermal limits to the supervisory coordinator. Validation on modified IEEE 39-bus (100% IBR, zero synchronous generators) and 3-area IEEE 118-bus systems demonstrates an 82.8% reduction in cumulative tie-line thermal overload while maintaining strict exponential contraction ($λ_{\max} \le -2.43$) even under a 3 s communication blackout.

0.29

A-CPES: A Reference Framework for Agentic AI in Cyber-Physical Energy Systems

cs.AI ·2026-08-24 ·Xiaoyu Zhang, Qiuye Sun, Jiachen Xu, Zhongming Yao, Yushuai Li
position similarity 0.53
Abstract · 5 pages, 1 figure

Energy system operation contains a loop of work that automation has never taken over: posing the optimization problem the current cycle should solve, disposing of infeasibility, sequencing a solution into interlocked switching orders, assembling evidence no single model holds, negotiating adjustable capacity with many parties, and settling experience into practice. Licensed dispatchers carry all of it in person, and the rising share of variable renewable generation is making that loop turn faster than their number can grow. Agentic AI supplies the abilities it requires, but enters as the outer loop of control: it calls SCED and the other decision models rather than being called by them. We propose A-CPES, three nested rings, an authorization and accountability frame around an agentic control outer loop around a six-layer CPES core. We argue the loop is indivisible, tune where and how tightly it may close, state eight structural failure modes as falsifiable predictions, and specify six governance modules that rebuild the authorization frame until it covers the loop, before the loop starts turning.

0.17

Quantifying the Unintentional Islanding Risk: A Comparative Study on Active Distribution Network

eess.SY ·2026-09-10 ·Harshit Nayak, Edoardo Daccò, Jose Luis Rueda Torres, Davide Falabretti
similarity 0.53
Abstract

The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.

0.28