CS Paper Radar

Interactive Power Flow in the Browser

Samuel Talkington, Frederik Geth, Qian Zhang, Le Xie, Skyler Liu

eess.SY cs.HCcs.MS ·submitted 2026-10-01 15:57 UTC · v1
publishedcode/data

Abstract

This paper introduces tellegen, an open source framework for interactive power flow (PF) and optimal power flow (OPF) studies that run in the browser. This provides intuitive and democratized access to power system analysis tools compiled to WebAssembly. A user can drag and drop a case file, click and drag to change a nodal demand or line rating, preview the impacts via sensitivity analysis, and obtain an exact re-solve on release. User case files and results stay entirely on the device: tellegen transmits zero Critical Energy/Electric Infrastructure Information (CEII). The framework comprises a core numerical engine for PF and OPF, reusable browser components, saved studies, and structured WebMCP tools for agentic interaction. We evaluate the transmission OPF solver by comparing objectives with PGLib baselines; the distribution PF solver by comparing voltages and currents with OpenDSS; and the WebAssembly execution times by comparing with PowerModels.jl. On realistic synthetic grids, WebAssembly OPF solves take only 25-43% longer than native binary solves. The implementation shows how an engineer can distribute an executable numerical study as a URL, reducing installation and hosting requirements while keeping case data local.

Comment
9 pages, 3 figures, 6 tables. To appear in the Inaugural ACM Conference on Digital Transformation (ACM DXConf 2026), Ann Arbor, MI, USA

Closest papers

Nearest neighbours by meaning across the whole index.

Integrating Agentic Artificial Intelligence with High-Performance Computing for Grid Planning

eess.SY ·2026-09-03 ·Samim Konjicija, Slaven Peles
published similarity 0.62
Abstract · 6 pages, 3 figures, 3 tables. To appear in proceedings of EnergyCon 2026

We present AgentiGrid, an agentic artificial intelligence (AI) framework that integrates large language models (LLMs) intelligence and high-performance computing (HPC) to streamline and accelerate the multi-scenario power flow studies. AgentiGrid is an autonomous decision-making agent that proposes parameter modifications, invokes analyses through HPC analysis toolkit ExaGO, interprets results, and determines subsequent actions. ExaGO provides multiple power flow applications that can perform deterministic, stochastic and security constrained optimal power flow analyses. AgentiGrid provides backends to multiple LLMs (OpenAI, Anthropic, Ollama, and Ollama cloud) augmented with context specific and task specific prompts. Key features include interactive mid-search steering, goal-type-aware post-search analysis, and concurrent variant exploration for power flow optimization. A Streamlit-based graphical launcher provides real-time visualization of iteration progress and generates reports in natural language. AgentiGrid is capable of autonomously converging transmission constrained alternating current optimal power flow in under 20 iterations, with near-perfect reliability

0.44

PowerZooJax: A JAX-based Power System Benchmark for Reinforcement Learning

cs.AI cs.LGeess.SY ·2026-09-28 ·Zhanhua Pan, Xiao Liu, Zhilong Cao, Jianhong Wang, Dawei Qiu
benchmarkcode/data similarity 0.58
Abstract · 42 pages

Power system operation is a safety-critical sequential decision-making problem, making it a natural testbed for reinforcement learning (RL). However, existing RL environments for power systems are often narrow in scope and computationally limited by CPU-based simulation workflows, making large-scale evaluation difficult. We introduce PowerZooJax, a JAX-based benchmark suite for RL in power system operation. It provides five constrained Markov decision process tasks spanning generation, transmission, distribution, distributed energy resources, and data center microgrid. By rewriting power flow, economic dispatch, market clearing, and device dynamics as JAX computation graphs, PowerZooJax keeps the entire training and evaluation loop on the GPU. Experiments show substantial speedups over CPU-based simulations and demonstrate standardized evaluation of policy returns, safety violations, and out-of-distribution stress conditions. Our open-source benchmark is available at: https://github.com/powerzoojax/PowerZooJax.

0.41

RestoreBench: Can AI Agents Restore Power Flow Convergence?

cs.AI eess.SY ·2026-08-31 ·Riccardo Mansutti, Andrea Pomarico, Robert Jakob, Qian Zhang, Alberto Berizzi +1 more
benchmarkcode/data similarity 0.58
Abstract

Large Language Model (LLM) agents increasingly automate multi-step engineering workflows through tool use, interpretation of intermediate results, and iterative planning. Diagnosing and resolving non-convergent power flow cases is a promising yet largely unexplored application, as it requires engineering judgment, experimentation, and decision-making within constrained action spaces. We introduce a benchmark that evaluates these capabilities across multiple LLMs and three architectures: \emph{chatbot}, \emph{single agent}, and \emph{multi-agent} systems. The evaluation covers two power grids and 46 cases per grid, each requiring one or more corrective actions to restore convergence. The benchmark defines the simulation environment, observation and action spaces, and evaluation metrics, providing a reproducible foundation for developing agentic AI systems for power system planning and operation. The code is available at https://github.com/Mansutti081/RestoreBench

0.40

Joule-Profiler: Profiling the Energy Consumption of Build Automation Tools Made Easy

cs.SE cs.DCcs.PF ·2026-09-25 ·Jérémy Woirhaye, François Gibier, Romain Rouvoy
code/data similarity 0.56
Abstract · 4 pages, 2 figures. Submitted to the ICSE 2027 Tool Demonstration and Data Showcase Track

Build pipelines are integral to modern software development, yet their energy footprint remains largely invisible to practitioners. Existing CI energy tools either rely on model-based estimation (due to hardware access restrictions in cloud runners) or report only total pipeline energy without decomposing it into meaningful phases. Joule-Profiler is an open-source command-line tool for Linux that measures hardware energy consumption via Intel RAPL (CPU), NVML (NVIDIA GPU), and attributes it to user-defined program phases by monitoring standard output. In this tool paper, we demonstrate Joule-Profiler in the context of Maven build pipelines using Google Gson as a case study. By applying a token pattern-matching Maven plugin invocations, we analyze builds across the 5 most recent Gson releases into per-phase energy profiles, comparing cold builds (empty local repository) and warm builds (cached dependencies).

0.30

GENCO - A Unified Neural Solver Embedded in a Development Framework for Steady-State Grid Analysis

cs.AI ·2026-08-10 ·Alban Puech, Matteo Mazzonelli, Tamara R. Govindasamy, Mangaliso Mngomezulu, Héctor Maeso-García +17 more
code/datahighly cited similarity 0.56
Abstract

Foundation models are transforming business workflows and boosting productivity, yet they remain largely absent from engineering domains such as power system analysis, where strict physical consistency must be enforced. We present GENCO (GEometric Neural Corrective Optimizer), a unified neural solver for steady-state transmission grid analysis that handles power flow (PF), optimal power flow (OPF), and state estimation (SE) within a single architecture and shared grid representation. To support advances in neural power system solvers, we introduce the open-source GridFM Development Framework, which standardizes synthetic data generation and training in a low-code environment. We also release large-scale datasets with millions of PF and OPF scenarios across diverse grid topologies to support reproducible benchmarking. We evaluate GENCO on the PFDelta and OPFData benchmarks against state-of-the-art neural solvers and classical solvers, including Newton-Raphson and IPOPT, as well as on real-world Hydro-Québec SCADA data. For large-scale PF, GENCO recovers the full AC operating state, including voltage magnitudes and reactive power that DC-PF cannot provide, while matching DC-PF-level active power-balance residuals. It achieves up to 30x speedups over Newton-Raphson at only 2x the runtime of DC-PF. For OPF, it achieves up to 85x speedups over IPOPT while improving feasibility, optimality, and runtime over DC-OPF. For SE, GENCO is more robust than classical weighted least squares to noisy measurements and grid parameter errors, and always returns a high-quality estimate even when weighted least squares fails to converge. Together, the unified architecture and development framework provide a new approach to large-scale steady-state grid analysis, lowering the barrier to entry for power system engineers and marking a step toward Grid Foundation Models.

0.60

Local AI Agents in Power Electronics Simulation: Deployment, Measurements and Costs

cs.AI eess.SY ·2026-11-18 ·Yuzhuo Li, Pasan Gunawardena, Yunwei Li
similarity 0.54
Abstract · 27 pages, 23 figures, 12 tables

Agentic artificial intelligence (AI) is emerging in power electronics, where it drives the simulation loop that engineers used to close largely by hand. In this loop, a converter design, or a study of the network it connects to, is built, run, measured and revised until it satisfies its specification. Such an agent can be served from a cloud API or from an inference device on the premises. For organizations whose designs, customer data or export-controlled material cannot leave the site, and whose simulators are licensed there, local deployment is the natural choice. In such a deployment, the agent becomes an electrical load on the organization's own equipment, i.e., every run consumes power and energy on a local device, generates tokens and takes time. However, existing work focuses mainly on what the agent can achieve with cloud-hosted models. What a local deployment costs in power, energy, tokens and time on real simulation tasks, and what its choices trade against one another, has received little quantitative investigation under comparable conditions. To address this gap, a systematic evaluation framework is presented in this paper. It applies locally served models to agentic power electronics tasks, from the converter level to the system level, and measures their power, energy, token and time costs. Based on these measurements, the capability boundary of a local agent on such tasks and the cost per solved task are characterized. The results are expected to provide practical insight for the use of agentic AI in power electronics and the power systems it serves.

0.26

Energy-Aware Performance Characterization of Kokkos Kernels Across Precision Levels

cs.PF ·2026-10-22 ·Maria Patrou, Andrey Prokopenko, Aditya Kashi, Oscar Hernandez, Jean-Luc Fattebert
publishedbenchmark similarity 0.54
Abstract · 13 pages, 4 figures, Accepted at the 3rd International Workshop on Energy Efficiency with Sustainable Performance: Techniques, Tools, and Be…

Kokkos is a performance-portable programming model used in GPU-accelerated HPC applications comprising kernels with diverse computational and memory behaviors. We characterize kernels from two applications to evaluate how FP32, FP64, and mixed FP32/FP64 affect arithmetic intensity, performance throughput, and GPU energy consumption. We introduce an Energy-Aware Roofline Model that incorporates energy into performance analysis and a Thermal-Aware Inter-Kernel Energy Model that visualizes energy consumption alongside duration, GPU temperature, and execution order. We study both applications with: (1) fine-grained, application-level instrumentation through the Kokkos Performance Tools PAPI Connector and (2) coarse-grained PAPI instrumentation applied to a dedicated-kernel benchmark using vendor-specific power management components. Our analysis shows that precision effects vary by application, kernel, and workload. Mixed FP32/FP64 kernels generally achieve arithmetic intensity comparable to FP32, with modestly lower throughput and, in most cases, a modest increase in energy consumption. FP64 kernels generally exhibit the highest energy consumption among the evaluated precision configurations.

0.35

Steady-State Equivalent Circuit Model for Data Center Loads

eess.SY ·2026-08-18 ·Muhammad Hamza Ali, Peng Sang, Hyeon Woo, Hyein Kang, Sungyun Choi +1 more
similarity 0.54
Abstract

Planners currently represent data centers as aggregate constant-PQ or ZIP loads in steady-state interconnection and contingency studies. These aggregate models are computationally convenient. However, they obscure the electrical relationship between computational workloads, server utilization, and grid-side demand. They ignore the internal power-electronic conversion stages of IT loads and assume homogeneous workload distributions across the compute clusters. This hides operating-point-dependent converter losses and efficiency variations. We propose a steady-state equivalent-circuit model (ECM) for data centers, which explicitly builds circuit models for IT loads, power supply units, cooling, and auxiliary systems. For power supply units, the equivalent circuit model explicitly represents internal power-electronic conversion stages. For IT loads, we develop a utilization-dependent server power model, and we combine it with loss-aware ECMs of power supply units. This approach captures the grid-side impact of heterogeneous workload distributions while preserving compatibility with conventional power-flow analysis. We evaluate this data center ECM in large-scale transmission power flows, using Monte Carlo simulations under heterogeneous and homogeneous cluster utilization. In comparison with the fixed-efficiency constant-PQ model, the ECM predicts that the most stressed line exceeds its thermal limit in about 30% of Monte Carlo samples. The results further show that homogeneous server utilization overstates line-loading variability by 17%-46% relative to heterogeneous server utilization, depending on the intra-cluster workload correlation.

0.47