Modeling and Parametrization of Large-scale Hydrogen Electrolyzers for Transient and Frequency Stability Analysis

Mahmoud K. Abdelhamid, Lukas Sigrist, Álvaro Ortega

eess.SY ·submitted 2026-10-29 11:02 UTC · v1

Abstract

Hydrogen Electrolyzers (HEs), particularly Proton Exchange Membrane (PEM)-based systems, are flexible loads capable of providing grid ancillary services and enhancing the stability of renewable-dominated power systems due to their fast electrical response. However, the literature often lacks clear guidance on the structure, modeling, and parametrization of large-scale HEs for transient and frequency stability analyses. This paper presents a detailed configuration for utility-scale HE plants, using the stack as the fundamental unit, supported by a realistic parametrization based on commercial components. Furthermore, this work extends the Generalized ESS Model (GEM), a linearized state-space model previously utilized with other converter-interfaced energy storage systems, to PEM HEs for the first time. To facilitate plant scalability, a robust method for scaling GEM matrices across different capacities is proposed. Finally, a measurement-based methodology is developed to estimate the GEM parameters and subsequently extract the equivalent electrical circuit parameters. Comprehensive simulations on the WSCC system under various disturbances validate the accuracy of the derived GEM, the effectiveness of the scaling approach, and the robustness of the parameter identification methodology.

Closest papers

Nearest neighbours by meaning across the whole index.

A Closed-Loop Model of an Anion Exchange Membrane Electrolyser Based on Operational Data

eess.SY ·2026-09-16 ·Maiken Borud Omtveit, Lisa Marie Dannappel, Shi You, Kjetil Uhlen
similarity 0.66
Abstract · 5 pages, IEEE ISGT 2026

The main contribution of this work is to identify model parameters for an Anion Exchange Membrane (AEM) system directly from measured operational data, enabling their use in power system studies. Due to the relatively low technology readiness level (TRL) of AEM electrolysers, only limited literature reports operational parameters supported by openly available experimental data. By capturing the realistic dynamic behaviour and power consumption of the AEM electrolyser, this model allows for more accurate evaluation of system topologies and control strategies for green hydrogen production. This paper presents a model of an AEM electrolyser based on experimental data from Enapter modules installed in the Power-to-X (PtX) Laboratory at the Technical University of Denmark [1]. The model comprises a polarisation curve and a model of current dynamics during operation. It is validated against operational data and can be applied in grid-balancing studies as well as in assessments of how electrolyser dynamics influence the power system. The results suggest that the AEM technology is suitable for services such as smoothing wind farm power output and provide system services to support frequency balancing. The findings highlight the importance of considering the constraints of the process when designing for flexible load operation, and consideration of the interaction between the power control and process control systems.

0.18

Grid Integration of Gigawatt-Scale Hydrogen Hubs: A Multi-Timescale Stability Analysis and Connection Requirements for Weak Grid Environments

eess.SY ·2026-08-17 ·Mohamed Shamseldein
publishedcode/data similarity 0.65
Abstract

The global transition toward green hydrogen is driving the deployment of gigawatt-scale electrolysis centers, introducing a novel, converter-dominated load class to the bulk power system. Unlike conventional industrial loads, these facilities utilize extensive power electronics interfaces with fast dynamics comparable to Inverter-Based Resources (IBRs). This paper presents a comprehensive grid impact assessment of large-scale hydrogen hubs, focusing on harmonic injection, voltage stability in low Short Circuit Ratio (SCR) environments, and frequency response capabilities. Adopting a "full-spectrum" open-source modeling approach, the study utilizes PandaPower for large-scale steady-state contingency assessment; ANDES for electromechanical dynamic simulations to evaluate Fast Frequency Response (FFR); and ParaEMT for high-fidelity electromagnetic transient analysis of harmonic distortion and Low Voltage Ride-Through (LVRT). A critical finding of this study is that standard load models, including the generic PERC1 (data center) model, are insufficient for hydrogen hubs. The paper recommends specific structural modifications to the PERC1 model - specifically regarding process safety latches and restart voltage thresholds - to accurately capture the risk of prolonged plant tripping. Based on these findings, the paper proposes a set of standardized connection requirements to ensure secure integration.

0.57

Unit-to-Plant Stability Shaping of Multi-Electrolyzer ReP2H Plants via Interface Design and Dispatch

eess.SY math.OC ·2026-08-24 ·Miao Zhang, Yiwei Qiu, Xiaoyu Wang, Linlin Wu, Yi Zhou +3 more
similarity 0.64
Abstract

Alkaline water electrolysis (AWE) units supplied by insulated gate bipolar transistor rectifiers (IGBT-Rs) may experience oscil-lations caused by coupling between rectifier control and electro-lyzer (ELZ) dynamics. Because this risk varies with unit loading and power allocation, production-oriented dispatch may place a multi-ELZ renewable power-to-hydrogen (ReP2H) plant near or exceed its stability boundary. This paper proposes a stability-oriented framework for control design and plant production dis-patch. A three-port admittance model links the ac port, dc link, and electrolysis stack. Unit-level dc-port analysis quantifies the effects of loading, temperature, Buck bandwidth, and dc-link capacitance, while plant-level aggregation evaluates how unit commitment and power allocation affect stability. Results show that higher loading reduces stability, whereas larger dc-link ca-pacitance and higher Buck bandwidth improve it. Under the same plant loading, different power allocations result in different plant-level stability margins, with balanced allocation generally providing a larger margin than concentrated allocation. The plant-level model thus distinguishes the stability margins of ad-missible schedules. Hardware-in-the-loop (HIL) tests validate these trends and the proposed redistribution rule. The resulting operating regions and dispatch rules can be used to screen unit commitment and power allocation decisions in plant production scheduling.

0.23

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.58
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.56
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.52
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.25

Coordinated Dynamic Operation of Integrated Electrolyzer-Compressor Systems

eess.SY ·2026-08-12 ·Amin Salehi, Janne Seppanen, Mahdi Pourakbari-Kasmaei
similarity 0.52
Abstract

The increasing interaction between power and hydrogen sectors highlights the importance of coordinated operation of electrolyzers and electric-driven compressor stations (EDCSs). This becomes particularly of higher importance under transient disturbances. However, coordinated dynamic interactions of these coupled subsystems remain largely unexplored. This article addresses such gap by developing a dynamic model for an integrated electrolyzer-EDCS system and designing appropriate PID control schemes to address the potential disturbances affecting either component. To this end, linearized models of the electrolyzer and EDCS are first derived to enable systematic controller design. Then, two PID controllers, representing conservative and fast-tracking designs, are developed to coordinate the system response. The developed coordinated model is examined and verified under four different cases. The results demonstrate the effectiveness of the proposed model under disturbances from the compressor driver or the electrolyzer. Controlling the electrolyzer flow in response to EDCS disturbances coordinates system dynamics and mitigates undesirable transient fluctuations. Conversely, under electrolyzer disturbances, regulating the EDCS torque eliminates inconsistent responses in pressure, flow, and rotational speed, while preventing hazardous transient undershoots and overshoots. Overall, the proposed framework guarantees transient stability and operational reliability of the integrated electrolyzer-EDCS system.

0.04

Open-Source Multi-Fidelity EMT Modeling of Data Center Loads for Power System Studies

eess.SY ·2026-11-06 ·Xingyu Zhao, Yingyi Tang, Junbo Zhao
code/data similarity 0.52
Abstract

Characterizing data center-grid interactions under rapid load fluctuations requires electromagnetic transient (EMT) models that capture fast converter and control dynamics. This paper develops a modular multi-fidelity EMT model of data center loads in PSCAD. The modular design supports flexible assembly of subsystem models for different power supply configurations. The multi-fidelity design incorporates switching models, average-converter models, and reduced-order models to balance simulation accuracy and computational efficiency according to analysis needs. The model also provides a systematic controller tuning procedure and supports control mode switching. Comparative simulations demonstrate how this data center load model responds to both grid-side and load-side disturbances and assess the accuracy and computational efficiency of models with three fidelity levels. The model is publicly available on GitHub.

0.34