Grid Integration of Gigawatt-Scale Hydrogen Hubs: A Multi-Timescale Stability Analysis and Connection Requirements for Weak Grid Environments

Mohamed Shamseldein

eess.SY ·submitted 2026-08-17 18:12 UTC · v1
publishedcode/data

Abstract

The global transition toward green hydrogen is driving the deployment of gigawatt-scale electrolysis centers, introducing a novel, converter-dominated load class to the bulk power system. Unlike conventional industrial loads, these facilities utilize extensive power electronics interfaces with fast dynamics comparable to Inverter-Based Resources (IBRs). This paper presents a comprehensive grid impact assessment of large-scale hydrogen hubs, focusing on harmonic injection, voltage stability in low Short Circuit Ratio (SCR) environments, and frequency response capabilities. Adopting a "full-spectrum" open-source modeling approach, the study utilizes PandaPower for large-scale steady-state contingency assessment; ANDES for electromechanical dynamic simulations to evaluate Fast Frequency Response (FFR); and ParaEMT for high-fidelity electromagnetic transient analysis of harmonic distortion and Low Voltage Ride-Through (LVRT). A critical finding of this study is that standard load models, including the generic PERC1 (data center) model, are insufficient for hydrogen hubs. The paper recommends specific structural modifications to the PERC1 model - specifically regarding process safety latches and restart voltage thresholds - to accurately capture the risk of prolonged plant tripping. Based on these findings, the paper proposes a set of standardized connection requirements to ensure secure integration.

Journal ref
CIGRE Science & Engineering, No. 42 (October 2026)

Closest papers

Nearest neighbours by meaning across the whole index.

Modeling and Parametrization of Large-scale Hydrogen Electrolyzers for Transient and Frequency Stability Analysis

eess.SY ·2026-10-29 ·Mahmoud K. Abdelhamid, Lukas Sigrist, Álvaro Ortega
similarity 0.65
Abstract

Hydrogen Electrolyzers (HEs), particularly Proton Exchange Membrane (PEM)-based systems, are flexible loads capable of providing grid ancillary services and enhancing the stability of renewable-dominated power systems due to their fast electrical response. However, the literature often lacks clear guidance on the structure, modeling, and parametrization of large-scale HEs for transient and frequency stability analyses. This paper presents a detailed configuration for utility-scale HE plants, using the stack as the fundamental unit, supported by a realistic parametrization based on commercial components. Furthermore, this work extends the Generalized ESS Model (GEM), a linearized state-space model previously utilized with other converter-interfaced energy storage systems, to PEM HEs for the first time. To facilitate plant scalability, a robust method for scaling GEM matrices across different capacities is proposed. Finally, a measurement-based methodology is developed to estimate the GEM parameters and subsequently extract the equivalent electrical circuit parameters. Comprehensive simulations on the WSCC system under various disturbances validate the accuracy of the derived GEM, the effectiveness of the scaling approach, and the robustness of the parameter identification methodology.

0.23

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.61
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.22

GFM Control Automatic Compliance Toolbox

eess.SY ·2026-11-08 ·Tejas Kunbi, Rahul Rane, Dan Wu, Aleksandra Lekić
similarity 0.61
Abstract

The increasing penetration of converter-interfaced generation reduces system inertia, short-circuit strength, and voltage support. European grid codes, including the ENTSO-E Network Code on Requirements for Generators and the ACER Demand Connection Code, now define disturbance-based validation procedures for grid-forming (GFM) generation and converter-based demand. Commercial RMS tools, however, lack an integrated workflow aligned with these recent requirements. This paper presents an automated Python-PowerFactory compliance toolbox and an RMS test bench for a co-located system comprising a 1 MW GFM photovoltaic (PV) plant, a 0.3 MW GFM battery energy storage system (BESS), and a 1 MW converter-interfaced dynamic load at a 20 kV point of common coupling fed from a 110 kV grid. Extended virtual synchronous machine models and a DCC-oriented load model are tested in batch, with results automatically extracted and plotted for assessment. Results show compliant RMS performance for the slower, electromechanical tests, while the paper identifies which tests require complementary electromagnetic transient (EMT) verification.

0.34

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.60
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data Centers

eess.SY ·2026-11-05 ·Junyuan Zheng, Salish Maharjan, Min Lwin, Soummya Roy, Zhaoyu Wang +3 more
similarity 0.59
Abstract

Large data centers are emerging as power-electronic loads whose response to grid voltage disturbances can affect bulk-system stability. This paper presents the composition and control characteristics of a proprietary electromagnetic transient (EMT) model of a modern data center comprising an uninterruptible power supply (UPS) with battery energy storage, induction-motor cooling loads, a computer room air handler (CRAH) driven by a variable-frequency drive (VFD), and an aggregated server load. A voltage-based state machine coordinates three aspects of the facility response: the UPS operating mode (eco, double conversion, or battery), the supply path of the CRAH, and a ramped reconnection of the grid-side UPS converter after the disturbance clears. A 100 MW facility is implemented in PSCAD/EMTDC and benchmarked against the PSSE PERC1 aggregate data center model under a symmetrical three-phase fault and low- and high-voltage ride-through (LVRT/HVRT) events. The two models agree closely in their voltage and active-power trajectories, while the EMT model also resolves the converter and motor-reacceleration transients that the phasor-domain model cannot.

0.50

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.57
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters

eess.SY ·2026-09-09 ·Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt +3 more
benchmark similarity 0.57
Abstract · Best Paper Award in the 2026 5th IEEE International Conference on Power Systems and Electrical Technology

This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.

0.20

Open-Source Multi-Fidelity EMT Modeling of Data Center Loads for Power System Studies

eess.SY ·2026-11-06 ·Xingyu Zhao, Yingyi Tang, Junbo Zhao
code/data similarity 0.56
Abstract

Characterizing data center-grid interactions under rapid load fluctuations requires electromagnetic transient (EMT) models that capture fast converter and control dynamics. This paper develops a modular multi-fidelity EMT model of data center loads in PSCAD. The modular design supports flexible assembly of subsystem models for different power supply configurations. The multi-fidelity design incorporates switching models, average-converter models, and reduced-order models to balance simulation accuracy and computational efficiency according to analysis needs. The model also provides a systematic controller tuning procedure and supports control mode switching. Comparative simulations demonstrate how this data center load model responds to both grid-side and load-side disturbances and assess the accuracy and computational efficiency of models with three fidelity levels. The model is publicly available on GitHub.

0.34