CS Paper Radar

Ranking the Parameters Shaping Grid Dynamics

Ahmad F. Taha

eess.SY ·submitted 2026-10-31 18:28 UTC · v1
benchmark

Abstract

Generator and transmission line parameters do not shape the time-domain behavior of a power system equally; a parameter that dominates one dynamic property can be almost invisible to another. This paper studies how the physical parameters of a detailed and general nonlinear differential algebraic equation (DAE) grid model shape the properties that decide whether system states such as frequencies, voltages, and angles can be inferred, observed, controlled, and kept stable. The rankings are conditional as they depend on where grid sensors and actuators sit, on the operating region and the disturbance, on the network topology, and on other settings that the operator chooses. The framework combines DAE trajectory sensitivities, variational Gramians, and stability margin sensitivities to measure how much each parameter reshapes the network dynamics. On three benchmark systems, the rankings show where dynamic leverage concentrates and where the control-theoretic metrics disagree, and they point to how parameter studies can guide calibration, sensor and actuator placement, and security assessment. The proposed methods herein are also scalable and can be tested on grids with tens of thousands of buses.

Closest papers

Nearest neighbours by meaning across the whole index.

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.59
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16

System-Level Factors Influencing AGC Cyber-Attack Success and RAS Vulnerability in Multi-Area Grids

eess.SY ·2026-10-30 ·Abdulmannan Ajabnoor, Zhi Jin Zhang, Maryam Saeedifard, Dominic Groß
published similarity 0.59
Abstract

Automatic generation control (AGC) stabilizes frequency and scheduled power exchanges among interconnected areas, yet its reliance on communication networks introduces cyber-vulnerabilities. This work examines coordinated AGC cyber-attacks in the presence of remedial action schemes (RAS) and identifies operating conditions under which an attacker can drive grid frequency beyond safe limits while evading RAS. A feedback-based attack policy is used to manipulate AGC signals and steer system frequency toward unsafe trajectories. Then, a large nested-loop parametric sweep---spanning attacked-area inertia relative to its interconnected neighboring area, AGC capacity versus maximum tie-line transfer, AGC update rate, load damping, and bi-directional power transfers---generates over 1.45 million scenarios. These are classified using a decision tree to establish guidelines to distinguish successful from unsuccessful attacks based on frequency deviations. The resulting vulnerability guidelines are validated on a three-area system using phasor-domain simulations with IEEE 9-bus area models, detailed turbine--governor dynamics, and under/over-frequency load and generation shedding. Results show that specific combinations of AGC capacity, inertia distribution, and pre-attack tie-line loading increase the likelihood of successful attacks, offering operators actionable criteria for identifying vulnerable operating conditions.

0.41

Beyond Binary Controllability: Reachability Margins for Power Systems via Scalable Screening

eess.SY ·2026-11-02 ·Abdallah Alalem Albustami, Ahmad F. Taha, Mohamad H. Kazma
benchmark similarity 0.59
Abstract

This paper studies unreachability screening for power systems, focusing on the inadequate control authority that arises under stressed grid conditions. Its main result is an infeasibility \textit{margin} for linearized differential algebraic equation models that quantifies how far a prescribed terminal target lies from the reachable set in finite time. The paper specifically develops a conic benchmark method together with two first order methods based on projected subgradients and bundle updates for scalably repeated screening. Studies on IEEE benchmark networks show reduced terminal reachability under stressed conditions and tighter actuation limits, while first order methods remain accurate and substantially faster on large systems. Comparisons with standard reachability methods such as CORA further demonstrate the usefulness and scalability of the proposed infeasibility margins. All results and codes are included in a Github repository.

0.27

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.58
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.35

Trajectory Sensitivity-Based Dynamic Assessment of an AI Data Center Under Contingencies

eess.SY ·2026-10-07 ·Arnav Bagga, Saskia A. Putri, Abhishek Banerjee, Xiaofan Wu
similarity 0.57
Abstract · 7 pages, 5 figures

Artificial Intelligence (AI) data centers are emerging as converter-dominated, parameter-rich electrical systems whose dynamic response depends on fast workload-driven demand variations, tightly regulated data-hall converters, and coordinated on-site sources. Assessing such systems by repeatedly solving nonlinear time-domain models for every outage, load realization, and parameter perturbation is computationally expensive and provides limited insight into response sensitivity. This paper presents a trajectory sensitivity (TS)-based dynamic assessment framework for a self-contained AI data center supplied by a 2 kV DC microgrid with a grid-tied interface. The model includes time-varying data-hall load profiles, a voltage source converter (VSC), battery energy storage systems (BESS) units, supercapacitors, and synchronous-generation-side sources. For each disturbance, firstly, TS are computed along the nonlinear disturbance trajectory, capturing the local effect of source trips, data-hall outages, converter controls, and load ramps. Later, the computed TS data is used to estimate system trajectories under simultaneous parameter perturbations. Validation against full nonlinear ODE simulations with $\pm 15\%$ perturbations shows close agreement. In addition, the TS-based approach reduces computational time of dynamic-response evaluations from seconds to milliseconds, demonstrating its potential as a scalable screening tool for AI data center dynamics.

0.17

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.57
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Modeling and Stability of Power Systems With Coupled Data Center and Grid Dynamics

eess.SY ·2026-11-17 ·Guido Cavraro
similarity 0.56
Abstract

The growing deployment of data centers poses challenges for power-system operation. However, data centers possess flexible resources that can be leveraged to mitigate their impact on the grid and provide grid services. This paper develops a linear-affine dynamic model of a transmission network with multiple data centers, explicitly coupling electromechanical grid dynamics with data center power demand and computational backlog. Grid-aware computing policies are incorporated to represent how data centers adjust their computational power in response to grid frequency deviations and workload backlog. The proposed framework provides a tractable means of investigating the interactions between multiple data centers and the transmission grid and assessing the potential of flexible computing to support power-system stability.

0.26

Compositional Data-Driven Small-Signal Stability Assessment of Power Systems via Output Differential Passivity

eess.SY ·2026-11-16 ·Peng Yang, Xiaohui Zhang, Xi Ru, Feng Liu
similarity 0.56
Abstract · 14 pages

This paper proposes a compositional data-driven small-signal stability assessment framework for interconnected power systems based on output differential passivity (ODP). Without requiring explicit device models, local ODP matrices and scalar indices are estimated directly from measurement trajectories. When internal states are available, trajectory-based linear matrix inequalities (LMIs) are constructed from input-state measurements to estimate the local ODP matrices and scalar indices. When internal states are unavailable, an extended-state representation is constructed from input-output measurements, enabling the same assessment using only external signals. The estimated ODP matrices are combined with the network coupling matrix for compositional assessment of power system stability, while their scalar indices enable decentralized assessment. To address the computational and numerical challenges of trajectory-based LMIs, we introduce right-inverse whitening (RIW) to remove redundant behavioral coordinates and improve computational efficiency, and apply instrumental-variable (IV) preprocessing to alleviate numerical ill-conditioning and mitigate noise effects. Case studies on a modified IEEE 39-bus power system show that ambient measurements satisfy the required informativity conditions and that both formulations yield estimates close to model-based references under the tested noise levels. The reusable local ODP estimates also enable modular stability reassessment after controller updates.

0.31