Cyber-physical smart-grid detectors are typically treated as black boxes and validated exclusively on clean, temporally shuffled datasets, which risk overly optimistic performance claims. This work presents a multi-testbed evaluation study built around an interpretable, time-windowed fusion Random Forest, adopting the pessimistic result whenever evaluation protocols disagree. (i) On a public paired cyber-physical dataset, shuffled cross-validation is optimistic: macro-F1 falls from 0.96 to 0.88 +/- 0.06 under rolling-origin temporal evaluation. A topology-free graph convolutional network (GCN) serving as a control confirms that this lightweight model is competitive on these splits. (ii) The adaptive and adaptive-joint feature-space attacks, which are infeasible as realistic grid manipulations, degrade macro-F1 to 0.67 and 0.34, respectively. Adversarial training and randomized smoothing partially restore performance, and a physics-constrained evolution-strategy evasion on the IEEE 14-Bus testbed shows the same vulnerability pattern. (iii) On real IEC-104 traffic, the cyber view reliably catches structural attacks (recall of 0.87 to 0.98) but largely fails on semantic value manipulation (recall of 0.11 to 0.35). An observability taxonomy on the IEEE 14-Bus system reveals that stealthy false data injection defeats all three observation views. (iv) On a full AC weighted least-squares state-estimation testbed, a forecasting-aided temporal test is evaded by slow ramps precisely where a rate-invariant physics-manifold test sustains detection at a common 5% false-alarm target. A full end-to-end evaluation on IEEE 118-Bus confirms the ordering but bounds its strength: the manifold test detects every trial down to 0.05 degree/step and 0.48 at 0.02 degree/step, against 0.14 for the temporal test. All code and benchmarks are released.

Closest papers

Nearest neighbours by meaning across the whole index.

Adversarially-Informed Node Criticality Identification in Power Grid Measurements

eess.SY math.OC ·2026-08-27 ·Koto Omiloli, Olugbenga Moses Anubi
similarity 0.65
Abstract

Power grid state estimation relies on sensor measurements that are increasingly vulnerable to adversarial corruption in cyberphysical environments, potentially leading to significant deviations in system observations. This motivates the need to identify critical measurement nodes whose compromise results in the most severe system-level impact. However, existing node criticality methods primarily rely on structural or steady-state analyses and do not explicitly account for adversarial effects on system behavior. To address this gap, this paper proposes an adversarially informed framework for identifying critical measurement nodes in linearized power systems. Within this framework, a structured attack generation mechanism is developed to construct stealthy and effective false data injection attacks (FDIAs) against an H-infinity resilient state estimator. Node criticality is then evaluated using coalition-based marginal contributions of compromised sensor subsets, estimated via permutation sampling over a prescribed set of admissible nodes, with the resulting importance scores mapped to the corresponding physical buses. Simulation results on the IEEE 14-bus system show that adversarially identified nodes induce larger deviations in frequency, voltage angle, and net power compared to randomly selected nodes, demonstrating the effectiveness of the proposed framework.

0.23

EvEMTBench: An Open Benchmark for Machine Learning in Power System Protection

eess.SY cs.LG ·2026-09-23 ·Julian Oelhaf, Georg Kordowich, Christian Bergler, Andreas Maier, Johann Jäger +1 more
benchmarkcode/data similarity 0.65
Abstract · 15 pages, 3 figures. Supplementary information included. Code: https://github.com/EvEMTBench/evemtbench-benchmark

Studies of machine-learning-based power system protection are difficult to compare because task definitions, measurement access, data partitions, metrics, and generalization conditions often differ. EvEMTBench addresses this gap with an open, executable, and versioned benchmark that fixes these evaluation choices while leaving model design open. Across four grids spanning 20-345 kV, it defines 12 protection and event-analysis functions instantiated as 24 scored tasks and supports structured evaluation across observability conditions, predefined distribution shifts, and zero-shot and fine-tuned cross-grid transfer. Committed partitions, leakage controls, and reproducible reporting provide a common basis for comparing future methods. A reference evaluation spanning trivial, conventional, feature-based, and deep-learning baselines shows that wider observability is not uniformly beneficial, shifted conditions can reveal failures not apparent in-distribution, and cross-grid transfer is substantially stronger for fault detection than for fault localization. Protection-relevant diagnostics identify failure modes not apparent from primary metrics alone. EvEMTBench therefore makes generalization in machine-learning-based protection an explicit and reproducible evaluation problem.

0.22

Robust Industrial Cyber Physical Classification Using Neuromorphic Temporal Embeddings and Hybrid SNN XGBoost Under Machine Unlearning Attacks

cs.LG cs.CRcs.NE ·2026-09-09 ·Ammar Kamoona, Sajad Koushkbaghi, Mahdi Jalili, Peter McTaggart, Xinghuo Yu
similarity 0.65
Abstract · 13 pages, first draft

The digitalisation of electrical distribution networks has increased the exposure of power-grid infrastructure to cyber attacks. Existing intrusion detection systems (IDSs), however, often rely on computationally expensive deep learning models that are difficult to deploy at the edge. Periodic retraining also exposes these systems to machine unlearning attacks, where selective data removal can degrade detection performance. We propose a hybrid Spiking Neural Network (SNN) and XGBoost architecture that combines efficient temporal encoding with a lightweight classifier and provides structural resilience to such attacks. The SNN is trained once on clean data and used as a fixed feature extractor, while only the XGBoost classifier is retrained during model updates. Evaluated on two real-world public power-system datasets, the proposed method achieves 99.9\% accuracy (F1-macro 0.999) on the Synchrophasor dataset and 95.0\% accuracy (F1-macro 0.943) on the MSU/ORNL dataset, outperforming standalone baselines. Under selective label-flipping attacks, the hybrid model loses only 0.9\% F1-macro at 10\% poisoning and delays target-class collapse from 60\% to 70\% poisoning compared with raw models. These results demonstrate that neuromorphic temporal encoding can provide both accurate cyber-attack detection and improved resilience to data poisoning in cyber-physical systems.

0.24

Detecting False Data Injection and Unstable Operation in Smart Grid via System-Aware Graph Boundary Learning

cs.CR ·2026-09-28 ·Emad Efatinasab, Denis Donadel, Mirco Rampazzo, Chuadhry Mujeeb Ahmed
similarity 0.65
Abstract

Cyber-physical power systems increasingly rely on data-driven tools to detect instability and support reliable grid operation. However, reliable stability prediction is difficult when unstable operating configurations are rare, sensitive, or unavailable during model development, since collecting such data safely and at scale is often impractical. At the same time, False Data Injection (FDI) attacks can manipulate reported system parameters to trigger false instability alarms or conceal unsafe operation, and such threats in Decentral Smart Grid Control (DSGC) systems remain largely unexplored. These challenges are rarely addressed jointly, leaving a gap between stability prediction and attack detection that this work aims to close. In this paper, we introduce StarGNN, a graph learning framework that learns the stable operating region exclusively from clean stable configurations and uses a single abnormality score to flag reported configurations that should not be trusted as evidence of safe operation, covering both genuine instability and unseen FDI manipulations. Each configuration is represented as a producer-consumer star graph and processed by a role aware graph neural network, with physics constrained pseudo-negatives generated by perturbing reaction time and price response parameters standing in for the unavailable unstable and attack data. A single threshold, calibrated only on held-out stable data, is used without task or attack specific adjustment. Evaluated on nine unseen FDI scenarios, StarGNN detects between 0.780 and 0.973 of attacks on stable configurations and retains a post attack instability recall between 0.972 and 0.999 on unstable ones, with 0.899 recall against a stronger adaptive attacker, showing that stable-only boundary learning can support both stability prediction and attack detection without access to genuine unstable labels or attack samples during training.

0.13

Stealthy, High-Impact False Data Injection Attacks in Smart Grid Using Physics-Constrained GAN with Limited System Knowledge

cs.LG eess.SY ·2026-11-11 ·Md. Mainul Islam, Hasan Kurban, Abdulrahman Takiddin, Muhammad Ismail, Rachad Atat +1 more
hot direction similarity 0.64
Abstract · 11 pages

False data injection (FDI) attacks can distort power system state estimation while retaining plausible measurement patterns. Existing FDI methods trade stealth for impact or vice versa. They often assume access to internal grids, all-bus sensing, or defender models. In this paper, we propose a detector-agnostic physics-constrained generative adversarial network (PCGAN) that learns decoupled power-flow sensitivities from historical measurements of deployed sensors. The learned active-power-angle and reactive-power-voltage-magnitude relationships guide perturbations restricted to compromised channels, while adversarial training promotes realistic spatiotemporal patterns. We implement PCGAN and seven existing FDI attacks on the IEEE 300-bus system using one year of observed hourly demand from PJM Interconnection, a regional transmission organization in the United States, and synthetic bus-level load profiles. We compare their performance across 10%, 30%, 60%, and 100% compromised sensors. Attack stealth is assessed against ten machine-learning (ML) detectors and conventional bad-data detection (BDD) methods, while physical impact is quantified through nonlinear alternating-current weighted least-squares state estimation. PCGAN achieves 84.28% mean ML evasion and 22.31% mean spatial load misperception across the four scenarios. Its mean stealth-impact trade-off score reaches 18.69%, compared with 5.61% for the strongest competing attack. PCGAN also achieves 83.45% chi-square BDD evasion and 86.02% largest-normalized-residual BDD evasion. These results demonstrate a favorable stealth-impact balance under varying sensor-access levels and provide challenging attack cases for evaluating FDI detectors.

0.21

ROAM: Reinforcement Learning Optimized Adaptive Moving Target Defense for Smart Grid

eess.SY ·2026-10-08 ·Mohammad Zakaria Haider, Prabin Mali, Muhammad Nadeem, Sumit Paudyal, Fei Ding +1 more
similarity 0.64
Abstract · This manuscript is under submission at IEEE TIFS

Smart grids rely on distributed phasor measurement units (PMUs) and wide-area communication networks whose data-acquisition pipelines are vulnerable to stealthy false data injection (FDI) attacks that evade conventional bad-data detection (BDD). Moving target defense (MTD) counters this exposure by continuously remapping sensor identities, but existing schemes apply static or pre-scheduled randomization and are each constrained by a single failure mode: seed-based methods are fast yet fragile to key compromise, while machine learning (ML) based prediction methods are resilient yet incur prohibitive latency. Neither adapts its randomization to live threat evidence. This paper presents ROAM, a deep reinforcement learning (DRL) driven MTD framework in which a deep Q-network (DQN) agent continuously re-optimizes the sensor-to-ID mapping at the aggregation layer. At each decision step, the agent selects the deception coverage, flags the specific sensors to remap, and sets the split of the remapped sensors between seed-based and ML-prediction-based recovery, without modifying PMU hardware and while preserving IEEE C37.118 compatibility. On held-out BDD-compliant FDI scenarios across the IEEE 14-, 57-, and 118- bus systems, ROAM keeps the percentage of stealthy attacks below 3% while sustaining detection rates above 93%. Against an adaptive soft actor-critic (SAC) attacker that observes the defender's configuration, ROAM keeps stealthy attacks below 2.6% with detection above 92%. Hardware-in-the-loop testing on an OPAL-RT platform confirms real-time feasibility, with sub-18ms average shuffle execution and an average reshuffle blind window of 2.6% of the 3-s decision cycle.

0.29

Adversarial Robustness Is Not Zero-Day Generalization: A Controlled Evaluation of Flow-Based Intrusion Detectors on Corrected CIC-IDS2017

cs.CR cs.LG ·2026-10-31 ·Abdulhamid Zaro
code/data similarity 0.64
Abstract · 10 pages, 10 tables. Code and per-seed results: https://github.com/abdulhamid-zaro/robustness-vs-zeroday-nids

Synthetic variants of known attacks, including feature-space adversarial perturbations, are sometimes used as stand-ins for unseen ("zero-day") attacks when evaluating machine-learning network intrusion detection systems (NIDS). We test whether this proxy holds. On the corrected CIC-IDS2017 release we train Random Forest, XGBoost, a 1D-CNN and an FT-Transformer and compare, at a fixed 1% false-positive rate over five seeds, detection under constrained perturbations of known attacks (gradient-based and black-box attacks on 42 attacker-controllable features) with leave-one-attack-family-out (LOAO) detection, where an entire family is absent from training. Detection under the strongest perturbation we tested, with budgets of at most 0.2, stays between 90.9% and 99.7%, yet mean detection of held-out families falls to 76.2% (RF), 40.2% (XGBoost), 25.8% (1D-CNN) and 22.8% (FT-Transformer). Robustness exceeds LOAO detection for every model (gaps of 24 to 72 percentage points, 23 to 66 when robustness is also averaged over families; Holm-adjusted p $\le$ 0.00096), and the two measures agree at most on a coarse ranking of the models. An exact mixed-integer evasion search confirms the tree ensembles' scores. Benign-only anomaly detectors and a simple multi-class open-set baseline do not close the gap. A temporal split on 5 seeds (3 of the 4 models) leaves the gap in place. On CSE-CIC-IDS2018 the gap recurs for every model (16 to 68 points). On these benchmarks and under this threat model, a robustness score should not be read as a zero-day score, and the two should be reported separately. Code and per-seed results are publicly available.

0.40

EnergyEminence: Source-Aware Environmental Calibration and Evaluation in a Physics-Grounded Grid Digital Twin

cs.LG eess.IV ·2026-09-28 ·Huy Trinh, Michael Mai, Yu Nong
similarity 0.63
Abstract

Power-grid digital twins must combine data-driven prediction with physically meaningful state evolution while preserving the provenance of environmental observations. This paper presents an early-stage EnergyEminence testbed that couples an IEEE 118-bus-style graph-temporal predictor, nonlinear AC cascade simulation, and operator-dashboard-like temporal replay. In addition, we introduce a shared bounded calibration that converts wildfire-detection confidence and spatial extent into source-comparable wildfire interpretable and explainable evidence. We then evaluate it with visually diverse fire and hard-negative videos. Sixteen synthetic environmental videos are curated to generate 160 source-tracked grid scenarios, and a source-video-disjoint test yields 10 true positives, 8 false positives, 22 true negatives, and no false negatives. The errors occur in stressed, non-cascading scenarios conditioned on an unseen growing-fire source. Our diagnostic then reveals environmental shortcut learning that is obscured by scenario-level random splitting. The paper therefore contributes a data-centric and inspectable evaluation workflow for multimodal grid-resilience models, together with evidence supporting separation of environmental alerting from electrical cascade inference