One number per hour is not enough: directional carbon intensity of data-center ramps on the PJM fleet

Xiaoying Shi, Jinyue Yan

eess.SY ·submitted 2026-11-09 08:33 UTC · v1
unusual

Abstract

A data-center campus can change its load by hundreds of megawatts within an hour, yet every carbon signal in use gives one value per hour for a load change, whatever its size or direction. We compute the directional carbon intensity, the emission caused or avoided per megawatt-hour of a finite upward or downward ramp, for every hour of 2025 on the PJM Interconnection's fossil fleet, and compare it with the locational marginal emission rate (LME) and the regional average. The LME misstates a 1 GW ramp by more than 10% in 60% to 83% of hours in eleven months. Upward and downward ramps differ in a quarter to three quarters of hours but agree on their monthly mean. Location-based reporting assigns 47% to 59% of a ramp's emission to other consumers. A campus should schedule on the signal for its ramp's size and direction and report the emission it causes.

Comment
15 pages main text, 6 pages supplemental information. Code and derived results: https://doi.org/10.5281/zenodo.24074188

Closest papers

Nearest neighbours by meaning across the whole index.

Investigating the Impact of CI-Source Sensitivity in Carbon-Aware Resource Management Systems

cs.DC ·2026-11-16 ·Gonçalo Ferreira, Jaime Iglesias Blanco, María Castrillo, Álvaro López García, Li Wu +1 more
similarity 0.55
Abstract · 9 pages, 6 figures, 6 tables

The sustainable growth of data centres increasingly depends on Resource-Management Systems (RMSs) that aim to reduce carbon emissions of computing workloads without degrading performance. This need is intensified by the rise of Artificial Intelligence (AI) workloads, which demand exponentially growing amounts of compute and energy across geographically distributed infrastructure. Recent carbon-aware RMSs exploit temporal and spatial variation in grid Carbon Intensity (CI) to shift workloads towards lower-carbon periods or locations. In practice, CI estimates and forecasts can be inaccurate and uncertain, and CI providers' methods differ substantially. Such discrepancies may have a significant impact on RMS placement decision-making, raising concerns about the fragility of existing solutions. Thus, in this work, we ask how discrepancies between plausible CI estimates propagate into resource-management decisions and operational outcomes. To answer this question, we harmonise and characterise CI traces from Wattnet and ElectricityMaps across five Central European zones. We then propose our evaluation framework: External CI Signal Characterisation And Perturbation Evaluation (ESCAPE), which assesses provider switching and controlled CI perturbations in a reproduced placement setting. We implement our framework using CarbonEdge as a use case, and measure changes in placement decisions and operational outcomes, such as carbon proxy, energy use, and latency. Our results show that switching CI-source changes the dominant placement site in 43.50% cases, and alters reported operational outcomes. These changes occur despite high rank correlation and structured disagreement between CI-sources. This observed sensitivity to CI-source choice motivates robustness-aware carbon-aware placement, in which CI uncertainty should be explicitly accounted for in resource-allocation decisions.

0.33

GreenPassport: Request-Level Carbon Accounting for Cross-Border AI Inference

cs.CY eess.SY ·2026-09-06 ·Rui Lu
similarity 0.54
Abstract

AI inference often crosses regional boundaries as prompts travel to remote data centers and generated tokens return to users. Regional averages cannot represent the resulting differences in serving hardware, electricity, and network delivery. Request-level accounting needs a common boundary for the service, serving site, route, local comparator, uncertainty, and data provenance. GreenPassport Carbon Accounting (GPCA) associates these inputs with each request. It estimates serving and route carbon, then selects a reporting level from the available documentation. Our public-data implementation covers data-center instances, accelerators, model families, electricity mixes, routes, and cloud-region carbon intensity. Against six accounting baselines and four energy-prediction baselines, GPCA reduced median absolute percentage error by 56.3% and median absolute error by 15.5% relative to EcoLogits under the aligned accelerator-energy boundary. It produced zero rule overstatement in the deterministic conformance tests. In the buyer case, the clean-electricity CN-West scenario produced 0.0148 gCO2e per request, 88% below the local service at 0.1220 gCO2e per request.

0.24

Green500: Adventure in Qualifying a Cluster

cs.DC ·2026-11-06 ·Nicolas Richart, Xavier Ouvrard, Julia Paolini, Manuel Cubero-Castan, Gilles Fourestey
similarity 0.53
Abstract · submitted to EESP Workshop 2026

Energy effciency has become a key metric for evaluating High Performance Computing (HPC) systems, as reflected by the Green500 ranking. However, energy effciency alone does not capture the full environmental impact of an HPC cluster. Using the Kuma cluster at EPFL, we report on two Green500 measurement campaigns at Level 2 and Level 3, and extend this analysis to a full carbon footprint assessment using the MITSI life-cycle based methodology. GPU power capping experiments show that energy effciency peaks at 450 W, achieving an 11% performance loss offset by a 20% reduction in energy consumption. When embodied emissions are accounted for, the optimal power cap for carbon effciency shifts to 500 W under Switzerland's low-carbon electrical grid, revealing a tension between minimizing usage and embodied contributions. We discuss the challenges of generalizing this approach into a broader carbon-based HPC ranking, and argue that moving beyond energy effciency is both necessary and feasible.

0.20

Massachusetts' 2026 Clean Peak Standard Recalibration: Adaptation and Storage Tradeoffs

eess.SY ·2026-09-29 ·Yuhan Dai, Boyu Yao
published similarity 0.51
Abstract · Accepted for IEEE GESS 2026

Massachusetts recalibrated its Clean Peak Standard (CPS) in 2026 by lowering the minimum standards and expanding the Near-Term Resource Multiplier for qualifying storage. This paper evaluates the change using a three-zone, hourly capacity expansion model for 2026--2030. Both scenarios achieve full CPS compliance, but the post-May scenario reduces new battery additions by 53.1% and modeled system cost by 3.7%. CPS-eligible discharge declines by 30.4%, while Clean Peak Energy Certificate production declines by only 9.5%. Fossil generation during CPS hours increases by 11.7%, whereas modeled emissions remain nearly unchanged because the Regional Greenhouse Gas Initiative cap binds. The recalibration therefore lowers the modeled storage capacity requirement while weakening physical clean-peak performance.

0.36

Exploiting the Benefits of V2B Application on Peak Shaving of Data Center Loads

eess.SY ·2026-08-31 ·Arya Joshi, Hamed Haggi, Chinmay Morankar
similarity 0.48
Abstract · Digest submission version for IEEE IAS Annual Meeting 2026

The accelerated growth in data center projects has introduced a demand-driven bottleneck throughout power grids and contributed to a substantial increase in carbon emissions. These concerns are fueling discussions on methods to use existing energy assets to drive operational efficiency. To this end, this paper explores the benefits of Vehicle-to-Building (V2B) applications to support peak shaving of data center cooling loads. Initially, a literature review was conducted considering V2B constraints and optimization methods including SoC limitations, EV participation, tariffs, and building loads. This analysis was then used to develop a conceptual case study of a 10 MW data center in Loudoun County, VA by simulating a temperature-dependent load profile and adjusting the V2B participation of 40 commercial and passenger EVs. Simulation results indicate that, depending on seasonal variations in cooling load demands, strategic deployment of V2B assets between 12-5pm can offset gross cooling loads by 13-36%.

0.17

Beyond Scalar Flexibility: From Eligible AI Workloads to Dependable Load Relief

eess.SY cs.DC ·2026-09-04 ·Meiyi Li
similarity 0.48
Abstract · 20 pages, 18 figures, 5 tables. Code and derived data: https://doi.org/10.5281/zenodo.22308423

Grid studies often represent data-center flexibility as a fixed percentage of load, although no public production trace has shown how much eligible load persists across event durations or co-moves across clusters. We reconstruct 4,439 hourly power observations from a 185-day trace of 155,410 GPUs and derive a workload-semantic flexibility envelope. The fleet's time-averaged Monte Carlo median facility demand is 55.8 MW, while immediate eligible curtailment averages 3.55 MW after retaining allocated-GPU idle power: 12.1% of workload power and 6.35% of median facility power. Under full realization of that eligibility, 95%-available relief falls from 2.51 MW for one hour to 2.32 MW for four hours and 1.95 MW for 24 hours; a common realizable fraction q scales every value exactly by q. A mean-calibrated scalar overstates these quantities by 17%, 25%, and 47%, while a scalar tail-calibrated at four hours understates the one-hour product by 6% and overstates the 24-hour product by 17%; the share that reproduces the surface varies by a factor of 1.6 across durations and reliability levels. Aggregating 13 clusters raises four-hour firmness from 0.38 to 0.66, but cross-cluster covariance limits the gain. The production scheduler exposes almost no additional delay-based capacity: newly deferrable arrivals average 0.008 MW and have zero 95%-available capacity. These results replace an assumed flexibility percentage with duration, reliability, portfolio, and realizability terms that can be written into interconnection and demand-response contracts.

0.43

Beyond Energy: When Sustainability Dimensions Reshape LLM Serving Decisions

cs.CY cs.DCcs.LGcs.PF ·2026-09-28 ·Tianyao Shi, Xipeng Shen, Yi Ding
similarity 0.45
Abstract · 41 pages, 30 figures, 13 tables

Large language model (LLM) serving has environmental impacts across energy consumption, carbon emission, water consumption, and biodiversity loss. Yet these dimensions are largely evaluated in isolation, leaving it unclear when and how they lead to different optimization decisions. We present PRISM, a unified framework for characterizing and optimizing LLM serving across energy, carbon, water, and biodiversity impacts. Our analysis reveals a fundamental distinction: computing configurations determine energy consumption, whereas where and when LLM serving is deployed determine its carbon, water, and biodiversity impacts. Under a fixed deployment choice and operational-only accounting, all dimensions preserve the same energy-based configuration ranking. Deployment rankings can diverge across dimensions, while embodied impacts can break configuration invariance when they exceed a lifecycle crossover boundary. PRISM identifies these conditions, quantifies cross-dimensional regrets, and balances the four dimensions. In regional-routing experiments, PRISM reduces median worst-case regret by 50.2% relative to the strongest baseline.

0.18

InFactPlanner: Planning Sustainable Geo-Distributed LLM Data Centers

cs.DC cs.AI ·2026-08-13 ·Nicoletta Tsiopani, Moysis Symeonides, George Pallis, Marios D. Dikaiakos
published similarity 0.45
Abstract · Author copy of paper published at 34th International Symposium on the Modeling, Analysis, and Simulation of Computer and Telecommunication S…

The rapid growth of LLM inference is shifting sustainability concerns from one-time training to continuous serving, where infrastructure decisions shape energy use, carbon emissions, water consumption, and service quality. Yet operators often need to compare deployment alternatives before large-scale infrastructure is built, making direct measurement costly, slow, and sometimes infeasible. We present InFactPlanner, a trace-driven decision-support framework for what-if analysis of sustainable AI data center deployment for LLM inference across single and geo-distributed sites. InFactPlanner combines query traces, hardware-model profiles, candidate site configurations, PUE/WUE parameters, renewable generation models, and time-varying grid carbon intensity to estimate power, energy, carbon emissions, water use, latency, and server utilization. The framework abstracts low-level serving effects into configurable hardware-model profiles, enabling rapid comparison of site selection, capacity placement, hardware, model, renewable integration, and routing choices. We validate the energy accounting pipeline by reproducing reference LLM inference energy estimates with less than 10% deviation, evaluate scalability across multiple data centers and server counts, and demonstrate scenario-driven decision analyses for hardware selection, renewable placement, geographic deployment, and carbon-aware routing. Our results show that sustainability-optimal choices can differ from latency-optimal ones, and that the carbon value of deployment depends strongly on the local grid mix.

0.54