CS Paper Radar

Checking DER Commands Against Grid Context Catches Credentialed Attacks Static Checks Miss

Benjamin Blakely

cs.CR ·submitted 2026-11-09 16:58 UTC · v1

Abstract

Authorization of distributed energy resource (DER) commands judges a command by who sent it and whether its value has been seen before. An attacker holding a legitimate credential who writes ordinary values passes both tests. We add a check that judges each DER write against the grid's operating context: the bus voltages around the target, the hour, the day- ahead price, system load, and irradiance, compared with what operators wrote under similar conditions in the feeder's own benign history. We evaluate it live on the IEEE 123-bus and 8500-node feeders, driven by a measured 2024 year of price, load, and irradiance, against nine attack scenarios. A lookup trained on the same history catches none of the writes of the four scenarios that send values already familiar on the targeted device; the context check refuses 91.7% of insider-abuse writes and 64.4% of DER-aggregation writes while denying 1.28% of benign writes. In an offline test that replays recorded moments with curtailment setpoints drawn from the benign range, issued at a positive price, it refuses 47.3% and 50.5% on the two feeders, against 18.5% and 16.0% for the same check without context; live, the few setpoints tested were mostly shallow and were mostly allowed. The context check complements the lookup.

Closest papers

Nearest neighbours by meaning across the whole index.

Agreement Is Not Assurance: Evidence-Independent Safety Gates for Agentic AI in DER-Rich Distribution Grids

eess.SY ·2026-11-11 ·Qianxue Xia
similarity 0.67
Abstract · 10 pages, 3 figures, 4 tables

Physics-based safety gates for large language model (LLM) agents can approve unsafe actions when the agent and gate rely on the same corrupted measurements or network records. We formulate this shared-evidence failure for voltage-constrained distributed energy resource (DER) export decisions and analyze how nearly critical DER telemetry can bias state estimation while evading residual-based bad-data detection. We propose evidence-independent verification (EIV), which combines advanced metering infrastructure (AMI) voltage readings, measurement selection based on predicted voltage rise, and bounded physical probes. An IEEE 123-bus hidden-truth testbed evaluates 1,654 near-limit requests under telemetry attacks and record errors. For telemetry attacks targeting the nominal gate, an AC-twin gate with bad-data detection approved 95% of unsafe requests, compared with 3.1% for EIV; EIV rejected 22% of safe clean requests. At matched false-rejection settings, direct AMI checks outperformed incorporating the same readings into state estimation. Gate-targeted attacks exposed a vulnerability in telemetry-based response prediction. Command-based prediction removed that route, but targeted attacks on fresh validation cases still produced a 20% unsafe-approval rate under the tested attack pool. LLM agents frequently sought independent evidence voluntarily, but injected instructions and phase-label errors caused unsafe decisions. When offered the EIV checker as a tool, they used it in 93-100% of episodes; mandatory use did not reduce observed violations, which primarily reflected checker errors. These results distinguish enforcement of verification from reliability of the verifier itself.

0.27

TwinGridShield: Consequence-Aware Runtime Authorization for LLM Grid-Agent Actions

cs.AI cs.CR ·2026-08-15 ·Md Fazley Rafy
published similarity 0.65
Abstract · 6 pages, 3 figures, 4 tables and accepted in North American Power Symposium 2026

Large language model (LLM)-assisted energy-management tools can translate natural-language context into structured grid commands, but syntactic validity does not imply physical admissibility. This paper presents TwinGridShield, a model-independent runtime authorization layer that evaluates each proposed action in a deterministic network twin before release. The prototype checks connectivity, branch-flow, generator, and load-shedding invariants and records each decision in a hash-chained log. A controlled IEEE 14-bus study evaluates single-step switching, redispatch, and load-shedding actions using DC power flow and experimentally assigned branch ratings. In the matched-model experiment, a stochastic proposal source configured to select an unsafe action with probability p=0.84 produced 421 unsafe proposals in 500 attacked-condition trials, a realized rate of 84.2%. This value characterizes the configured surrogate and is not an empirical measurement of LLM prompt-injection susceptibility. TwinGridShield produced 0 unsafe releases in those 500 trials. Because action labeling and authorization used the same DC model, system state, branch ratings, and encoded constraints, this result verifies conformance of the implementation to its encoded authorization predicate rather than safety under model error. The principal robustness evaluation therefore introduces model mismatch. Unsafe acceptance reached 5.63% under bounded +20% and -20% per-bus load-measurement error and 30.09% when actual branch ratings were 20% below modeled ratings.

0.22

Data4Cyber: Labeled Cyber-Physical Datasets for Distribution-Grid Management Systems Under Representative OT Attacks

cs.CR ·2026-11-10 ·Ömer Sen, Lennart Bader, Marawan Emara, Martin Serror, Benedikt Schwalm +4 more
published similarity 0.64
Abstract

Cyberattacks against power systems increasingly exploit industrial communication and control dependencies arising from distributed energy resources (DER), remote management, and market-based incentives. Progress on intrusion detection is constrained by a lack of public datasets that align operational technology (OT) network telemetry with physical measurements and control context. Data4Cyber is a labeled cyber-physical dataset recorded in a laboratory distribution management system (DMS) for self-consumption optimization with photovoltaic generation, battery storage, controllable loads, and substation metering. It captures synchronized process measurements, controller context, price incentives, and packet captures (Modbus/TCP and MQTT) across one benign baseline and six attack scenarios spanning protocol-semantic Modbus manipulation, man-in-the-middle (MitM) false-data injection, and MQTT price manipulation. Its fixed 1 s time base, phase-resolved labels, and state-oriented representation support temporally blocked stateful-detector evaluation. Baseline results show that high recall alone is insufficient: several detectors achieve sensitivity through alarm saturation. Context-driven attacks require process-aware interpretation rather than single-channel thresholding.

0.63

Attack-Resiliency Analytics for Wide-Area Control Systems in Smart Grids

eess.SY ·2026-09-29 ·Mohammad Zakaria Haider, Prabin Mali, Nur Imtiazul Haque, Muhammad Nadeem, Sumit Paudyal +1 more
similarity 0.62
Abstract

Wide-area monitoring, protection, and control (WAMPAC) systems damp inter-area oscillations in large interconnected grids, but their reliance on synchronized PMU measurements carried over wide-area networks exposes them to false data injection (FDI) attacks. This paper presents an attack-resiliency analytics framework that formally models the coupled dynamics of the wide-area damping loop, automatic generation control, and the governor and excitation systems, and formulates the optimal stealthy FDI attack as a mixed-integer linear program (MILP). The anomaly detection model (ADM) enters as a replaceable constraint set: either a static bad-data detection (BDD) rule or a boundary learned from benign operation calibrated to a common false-positive rate. On the IEEE 39 and 118 bus systems, with reference dynamics validated on an OPAL-RT hardware-in-the-loop testbed, the optimal attack with wide-area access attains 3.3 and 8.1 times the benign objective and reaches a 0.5Hz frequency excursion more than twice as fast as an attack confined to automatic generation control. Learned boundaries reduce the attack objective by 15.5 55.0% and prevent over-frequency relay trips in all configurations, with feasible stealthy attacks remaining in every case, and residual risk tracks the width of the learned boundary rather than the detector family.

0.31

Grid Trouble in Paradise: Uncovering Vulnerable Distributed Energy Resources and Their Grid-Level Risks

cs.CR eess.SY ·2026-09-07 ·Anna Raymaker, Samuel Talkington, Zeezoo Ryu, Richard Asiamah, Emad Abukhousa +6 more
top venue similarity 0.62
Abstract · 20 pages, 10 Figures, To appear in the Proceedings of the 2026 ACM SIGSAC Conference on Computer and Communications Security (CCS '26)

Grid-connected solar distributed energy resources (DERs), such as solar inverters and monitoring platforms, have been deployed at unprecedented scale over the past few years, with global solar capacity more than doubling since 2022. To support monitoring and control, many of these systems are Internet-connected and configured by installers or end users, yet the real-world scale of their Internet exposure and the implications for power grid operation remain poorly understood. In this paper, we present an Internet-scale evaluation of exposed and vulnerable solar DER infrastructure, and assess the risk that compromised DERs can pose to energy grids. We develop a method for accurately identifying solar DERs from Internet scanning data, and discover a diverse population of over 66,000 Internet-exposed solar DERs. We detect that at least 10,000 of these DERs may have known CVEs, such as unauthenticated monitoring and control endpoints. To assess the risk that these vulnerable DERs pose to a power grid, we use an electric grid network for Oahu, Hawaii, established and used by the power system research community, and conduct a power system analysis. Our evaluation shows that by compromising exposed DERs, attackers can cause voltage and line flow violations across multiple locations in the Oahu network, resulting in a range of consequences from degraded power quality to damaged power system components to power outages. Ultimately, our work brings to light the emerging threat of grid-connected DERs, and provides directions for improving energy security.

0.44

Adversarially-Informed Node Criticality Identification in Power Grid Measurements

eess.SY math.OC ·2026-08-27 ·Koto Omiloli, Olugbenga Moses Anubi
similarity 0.61
Abstract

Power grid state estimation relies on sensor measurements that are increasingly vulnerable to adversarial corruption in cyberphysical environments, potentially leading to significant deviations in system observations. This motivates the need to identify critical measurement nodes whose compromise results in the most severe system-level impact. However, existing node criticality methods primarily rely on structural or steady-state analyses and do not explicitly account for adversarial effects on system behavior. To address this gap, this paper proposes an adversarially informed framework for identifying critical measurement nodes in linearized power systems. Within this framework, a structured attack generation mechanism is developed to construct stealthy and effective false data injection attacks (FDIAs) against an H-infinity resilient state estimator. Node criticality is then evaluated using coalition-based marginal contributions of compromised sensor subsets, estimated via permutation sampling over a prescribed set of admissible nodes, with the resulting importance scores mapped to the corresponding physical buses. Simulation results on the IEEE 14-bus system show that adversarially identified nodes induce larger deviations in frequency, voltage angle, and net power compared to randomly selected nodes, demonstrating the effectiveness of the proposed framework.

0.23

Robustness of Local Energy Markets to Cyberattacks: Case Study of False Data Injection

cs.CR ·2026-09-29 ·Mehran Moradi, Reza Zamani, Phil Aupke, Andreas Theocharis, Andreas Kassler
similarity 0.59
Abstract

Market clearing in community-based local energy markets relies on power demand and PV forecasts, making it vulnerable to coordinated false data injection (FDI) attacks. This paper proposes a bilevel optimization framework to identify worst-case bus-level FDI against interconnected multi-community electricity markets within a distribution network. The upper level attacker maximizes physical impact, measured by cumulative voltage deviation, while accounting for detectability. The lower level re-clears the interconnected multi-community markets subject to operational and network constraints. The bilevel model is reformulated as a single-level mixed-integer program through Karush-Kuhn-Tucker conditions and solved using the epsilon constraint method to characterize the trade-off between physical impact and detectability. Case studies on the IEEE 33-bus system with three communities show that even bounded, system-level zero-sum attacks can reshape local trading, reduce voltage security margins, and produce asymmetric community-level market outcomes. The results further show that vulnerability depends strongly on the spatiotemporal placement of falsified data rather than on uniform spreading across buses and time periods.

0.26

Resource-constrained Remote Attestation of Smart Meters Using Merkle Trees in a Trusted Execution Environment

cs.CR cs.AR ·2026-10-12 ·Amirhossein Shakiba, Hamid Reza Ghaeini, Sadegh Dorri Nogoorani
similarity 0.57
Abstract · 21 pages

Smart meters are pivotal to the functioning of smart grids, as they measure and transmit energy consumption data that includes sensitive information about household energy usage patterns. While this data offers significant financial benefits, it can also reveal detailed insights into residents' daily routines, making the security of smart meters a critical concern. This paper introduces a novel remote attestation method for smart meters that ensures the integrity and privacy of data exchanged between smart meters and central servers while detecting unauthorized tampering. Our approach structures the communication data into a Merkle Tree-a hash data structure that facilitates efficient data integrity and authenticity verification. All operations involved in constructing the Merkle root and hashing critical data are executed in the secure environment of a Trusted Execution Environment (TEE) using OP-TEE, thereby maintaining the integrity and security of the smart meter's data. Comparing our experimental results with the related works highlights the superiority of our method in terms of resource efficiency, security robustness, and the feasibility of implementation on smart meters and resource-constrained devices, thereby enhancing the overall security and reliability of smart grid systems.

0.27