CS Paper Radar

Data4Cyber: Labeled Cyber-Physical Datasets for Distribution-Grid Management Systems Under Representative OT Attacks

Ömer Sen, Lennart Bader, Marawan Emara, Martin Serror, Benedikt Schwalm, Junichi Tsurumi, Tatsumi Oba, Tomohiro Izawa, Yoshihiro Ujiie

cs.CR ·submitted 2026-11-10 11:29 UTC · v1
published

Abstract

Cyberattacks against power systems increasingly exploit industrial communication and control dependencies arising from distributed energy resources (DER), remote management, and market-based incentives. Progress on intrusion detection is constrained by a lack of public datasets that align operational technology (OT) network telemetry with physical measurements and control context. Data4Cyber is a labeled cyber-physical dataset recorded in a laboratory distribution management system (DMS) for self-consumption optimization with photovoltaic generation, battery storage, controllable loads, and substation metering. It captures synchronized process measurements, controller context, price incentives, and packet captures (Modbus/TCP and MQTT) across one benign baseline and six attack scenarios spanning protocol-semantic Modbus manipulation, man-in-the-middle (MitM) false-data injection, and MQTT price manipulation. Its fixed 1 s time base, phase-resolved labels, and state-oriented representation support temporally blocked stateful-detector evaluation. Baseline results show that high recall alone is insufficient: several detectors achieve sensitivity through alarm saturation. Context-driven attacks require process-aware interpretation rather than single-channel thresholding.

Closest papers

Nearest neighbours by meaning across the whole index.

Economic Impact Assessment of Denial-of-Service and Time-Delay Attacks on Advanced Metering Infrastructure

eess.SY cs.CR ·2026-08-10 ·Lais Oliveira Krohl, Saurav Basnet, Ioannis Zografopoulos
similarity 0.64
Abstract · IEEE North American Power Symposium (NAPS) 2026, 6 pages

Advanced Metering Infrastructure (AMI) plays an important role in modern power systems by providing near real-time consumption data for operational planning and load estimation. Despite this, AMI communication networks are vulnerable to certain cyberattack types, such as denial-of-service (DoS) and time delay attacks (TDAs), which may compromise data availability. This paper evaluates the impact of these attack types on AMI communication using a Mininet-based simulation environment that implements a communication model inspired by the Distributed Network Protocol 3 (DNP3) for communication among smart meters, data concentrators, and utility systems. Different cyberattack scenarios are analyzed, including communication delay, packet loss, combined degradation rate (D_rate), and concentrator failure, to evaluate their effects on network performance and data availability. The results indicate increased latency, higher communication unavailability rates, and reduced data reliability under attack conditions. In addition, the study correlates how communication degradation can result in potential uncertainties in energy demand estimation and provides estimates of the associated financial impacts on energy procurement, using electricity pricing data from the Independent System Operator-New England (ISO-NE). The experimental results reveal that a 500 ms delay increased the average RTT (Round-trip time) from 0.22 ms to 69.5 ms, while a 50% packet loss scenario resulted in 87 timeout events and a 5.31% communication degradation rate. Under a regional-scale deployment of 10,000 smart meters, this degradation could cause an estimated economic impact of $1,009/day under normal market conditions and up to $5,097/day during high-price events.

0.07

Stealthy, High-Impact False Data Injection Attacks in Smart Grid Using Physics-Constrained GAN with Limited System Knowledge

cs.LG eess.SY ·2026-11-11 ·Md. Mainul Islam, Hasan Kurban, Abdulrahman Takiddin, Muhammad Ismail, Rachad Atat +1 more
hot direction similarity 0.64
Abstract · 11 pages

False data injection (FDI) attacks can distort power system state estimation while retaining plausible measurement patterns. Existing FDI methods trade stealth for impact or vice versa. They often assume access to internal grids, all-bus sensing, or defender models. In this paper, we propose a detector-agnostic physics-constrained generative adversarial network (PCGAN) that learns decoupled power-flow sensitivities from historical measurements of deployed sensors. The learned active-power-angle and reactive-power-voltage-magnitude relationships guide perturbations restricted to compromised channels, while adversarial training promotes realistic spatiotemporal patterns. We implement PCGAN and seven existing FDI attacks on the IEEE 300-bus system using one year of observed hourly demand from PJM Interconnection, a regional transmission organization in the United States, and synthetic bus-level load profiles. We compare their performance across 10%, 30%, 60%, and 100% compromised sensors. Attack stealth is assessed against ten machine-learning (ML) detectors and conventional bad-data detection (BDD) methods, while physical impact is quantified through nonlinear alternating-current weighted least-squares state estimation. PCGAN achieves 84.28% mean ML evasion and 22.31% mean spatial load misperception across the four scenarios. Its mean stealth-impact trade-off score reaches 18.69%, compared with 5.61% for the strongest competing attack. PCGAN also achieves 83.45% chi-square BDD evasion and 86.02% largest-normalized-residual BDD evasion. These results demonstrate a favorable stealth-impact balance under varying sensor-access levels and provide challenging attack cases for evaluating FDI detectors.

0.21

Checking DER Commands Against Grid Context Catches Credentialed Attacks Static Checks Miss

cs.CR ·2026-11-09 ·Benjamin Blakely
similarity 0.64
Abstract

Authorization of distributed energy resource (DER) commands judges a command by who sent it and whether its value has been seen before. An attacker holding a legitimate credential who writes ordinary values passes both tests. We add a check that judges each DER write against the grid's operating context: the bus voltages around the target, the hour, the day- ahead price, system load, and irradiance, compared with what operators wrote under similar conditions in the feeder's own benign history. We evaluate it live on the IEEE 123-bus and 8500-node feeders, driven by a measured 2024 year of price, load, and irradiance, against nine attack scenarios. A lookup trained on the same history catches none of the writes of the four scenarios that send values already familiar on the targeted device; the context check refuses 91.7% of insider-abuse writes and 64.4% of DER-aggregation writes while denying 1.28% of benign writes. In an offline test that replays recorded moments with curtailment setpoints drawn from the benign range, issued at a positive price, it refuses 47.3% and 50.5% on the two feeders, against 18.5% and 16.0% for the same check without context; live, the few setpoints tested were mostly shallow and were mostly allowed. The context check complements the lookup.

0.40

Adversarially-Informed Node Criticality Identification in Power Grid Measurements

eess.SY math.OC ·2026-08-27 ·Koto Omiloli, Olugbenga Moses Anubi
similarity 0.64
Abstract

Power grid state estimation relies on sensor measurements that are increasingly vulnerable to adversarial corruption in cyberphysical environments, potentially leading to significant deviations in system observations. This motivates the need to identify critical measurement nodes whose compromise results in the most severe system-level impact. However, existing node criticality methods primarily rely on structural or steady-state analyses and do not explicitly account for adversarial effects on system behavior. To address this gap, this paper proposes an adversarially informed framework for identifying critical measurement nodes in linearized power systems. Within this framework, a structured attack generation mechanism is developed to construct stealthy and effective false data injection attacks (FDIAs) against an H-infinity resilient state estimator. Node criticality is then evaluated using coalition-based marginal contributions of compromised sensor subsets, estimated via permutation sampling over a prescribed set of admissible nodes, with the resulting importance scores mapped to the corresponding physical buses. Simulation results on the IEEE 14-bus system show that adversarially identified nodes induce larger deviations in frequency, voltage angle, and net power compared to randomly selected nodes, demonstrating the effectiveness of the proposed framework.

0.23

Agreement Is Not Assurance: Evidence-Independent Safety Gates for Agentic AI in DER-Rich Distribution Grids

eess.SY ·2026-11-11 ·Qianxue Xia
similarity 0.63
Abstract · 10 pages, 3 figures, 4 tables

Physics-based safety gates for large language model (LLM) agents can approve unsafe actions when the agent and gate rely on the same corrupted measurements or network records. We formulate this shared-evidence failure for voltage-constrained distributed energy resource (DER) export decisions and analyze how nearly critical DER telemetry can bias state estimation while evading residual-based bad-data detection. We propose evidence-independent verification (EIV), which combines advanced metering infrastructure (AMI) voltage readings, measurement selection based on predicted voltage rise, and bounded physical probes. An IEEE 123-bus hidden-truth testbed evaluates 1,654 near-limit requests under telemetry attacks and record errors. For telemetry attacks targeting the nominal gate, an AC-twin gate with bad-data detection approved 95% of unsafe requests, compared with 3.1% for EIV; EIV rejected 22% of safe clean requests. At matched false-rejection settings, direct AMI checks outperformed incorporating the same readings into state estimation. Gate-targeted attacks exposed a vulnerability in telemetry-based response prediction. Command-based prediction removed that route, but targeted attacks on fresh validation cases still produced a 20% unsafe-approval rate under the tested attack pool. LLM agents frequently sought independent evidence voluntarily, but injected instructions and phase-label errors caused unsafe decisions. When offered the EIV checker as a tool, they used it in 93-100% of episodes; mandatory use did not reduce observed violations, which primarily reflected checker errors. These results distinguish enforcement of verification from reliability of the verifier itself.

0.27

Grid Trouble in Paradise: Uncovering Vulnerable Distributed Energy Resources and Their Grid-Level Risks

cs.CR eess.SY ·2026-09-07 ·Anna Raymaker, Samuel Talkington, Zeezoo Ryu, Richard Asiamah, Emad Abukhousa +6 more
top venue similarity 0.61
Abstract · 20 pages, 10 Figures, To appear in the Proceedings of the 2026 ACM SIGSAC Conference on Computer and Communications Security (CCS '26)

Grid-connected solar distributed energy resources (DERs), such as solar inverters and monitoring platforms, have been deployed at unprecedented scale over the past few years, with global solar capacity more than doubling since 2022. To support monitoring and control, many of these systems are Internet-connected and configured by installers or end users, yet the real-world scale of their Internet exposure and the implications for power grid operation remain poorly understood. In this paper, we present an Internet-scale evaluation of exposed and vulnerable solar DER infrastructure, and assess the risk that compromised DERs can pose to energy grids. We develop a method for accurately identifying solar DERs from Internet scanning data, and discover a diverse population of over 66,000 Internet-exposed solar DERs. We detect that at least 10,000 of these DERs may have known CVEs, such as unauthenticated monitoring and control endpoints. To assess the risk that these vulnerable DERs pose to a power grid, we use an electric grid network for Oahu, Hawaii, established and used by the power system research community, and conduct a power system analysis. Our evaluation shows that by compromising exposed DERs, attackers can cause voltage and line flow violations across multiple locations in the Oahu network, resulting in a range of consequences from degraded power quality to damaged power system components to power outages. Ultimately, our work brings to light the emerging threat of grid-connected DERs, and provides directions for improving energy security.

0.46

Detect, Repair and Audit: A Hierarchical Multi-Agent Defense Against Adversarial Attacks in Energy Forecasting

cs.CR ·2026-11-02 ·Zewei Shi, Ruoxi Sun, Minhui Xue, Feng Liu, Hua Ma +2 more
similarity 0.61
Abstract

Accurate electricity-demand forecasting is essential for the modern energy infrastructure. Recently, Times-Series Large Language Models (TS-LLMs) have emerged as a promising approach to forecasting more accurate demand from historical consumption data in zero- and few-shot settings, helping energy operators effectively plan supply and allocate energy resources. However, these models are vulnerable to compromised sensor inputs that can distort forecasts and lead to erroneous market orders or unnecessary load shedding. Existing defenses focus primarily on end-device forecasting, overlooking the distinct data-drift, latency, and audit requirements across energy infrastructure. To address this gap, we extract from major energy standards and regulatory frameworks a three-layer conceptual model that captures the security postures for each layer. Guided by this model, we develop a Multi-Agent Reinforcement Learning (MARL) detector coupled with signal repair at local control centers, designed to mitigate distributional data drift through complementary feature-based detection and clean-reference-calibrated repair while meeting latency budgets. We further deploy an evidence-grounded LLM auditing agent with human-in-the-loop validation for audit-critical Virtual Power Plants (VPPs). In our evaluation, the best MARL configuration achieves an F1 score above 0.91 across all dataset-attack pairs, while signal repair reduces adversarial-to-clean input Relative Squared Error (RSE) by up to 83%. The few-shot auditor detects 77.78% of attacks in the Sherlock dataset. On the evaluated hardware, detection and repair require 7.95 ms on average, with a worst-observed latency of 14.50 ms, remaining within the local-center latency budget informed by IEEE 1646.

0.31

FedGuard-DC: Privacy-Preserving Federated Load Forecasting and Cyber-Attack Detection for Data-Center Loads in Transmission Systems

cs.CR ·2026-08-19 ·Md Kibria Saroare, Md Rubel Ahmed
published similarity 0.61
Abstract · Accepted on North American Power Symposium (NAPS) 2026

The rapid growth of large data-center (DC) loads is creating new challenges for power-system visibility, privacy, and cyber-physical security. System operators need accurate short-term information about these fast-varying loads, while DC operators may avoid sharing raw megawatt measurements because they can reveal sensitive workload and utilization patterns. This paper presents FedGuard-DC, a federated learning (FL) framework for privacy-preserving DC load forecasting and local false-data-injection attack (FDIA) detection. Each DC trains a dual-head model on its own measurements, where a shared encoder supports both a forecasting head and a reconstruction head. A calibrated anomaly score combines forecast residual and reconstruction error to detect corrupted measurements locally. Raw measurements and absolute MW demand remain at each DC, while only model updates, normalized forecast outputs, and scalar attack flags are shared with the global controller. Optional differential privacy and robust trimmed-mean aggregation are included to evaluate privacy-utility behavior and poisoned-client resilience. The framework is validated using phasor-domain simulation data from four large DC loads rated between 150 and 350 MW integrated into the IEEE 39-bus New England system. Results show a 0.5 s-ahead normalized forecast RMSE of 0.023-0.038 pu, compared with 0.32-0.34 pu for persistence. FedGuard-DC detects FDIA with ROC-AUC of 0.979, F1 = 0.930, and precision of 0.988, while robust aggregation reduces the poisoned-client RMSE impact from 0.042 to 0.035 pu.

0.25