Towards Efficient Edge AI for Power Flow in Renewable-Rich Grids with Volt/VAR Control

Shahariya R. R. Puthanpurayil, Vlad A. Sanduleac, Remus Teodorescu

eess.SY ·submitted 2026-11-11 08:26 UTC · v1
code/data

Abstract

AI models of the power grid must capture how wind and solar plants support the voltage, adjusting their reactive power to the local voltage along a grid-code Q(V) characteristic. This research examines whether grid foundation models, fast neural network models for power-flow analysis, can represent this behaviour. We introduce the Q(V) bus, a new bus type for the open-source GridFM GraphKit, whose physics decoder evaluates the reactive injection from the plant characteristic at the predicted voltage in every correction step. Training data comprise 7882 hourly operating points of a modified IEEE 118-bus system, matched to Energinet DK1/DK2 measurements and solved with pandapower. Compared with a physics-informed baseline that represents the parks as negative load, the Q(V) bus lowers the voltage-magnitude RMSE 2.3-fold, reduces the power-balance mismatch at the parks from 25 to 0.66 MVA, and raises the F1 score for voltage-band violations from 0.40 to 0.76. An ablation over five configurations shows that the Q(V) bus type provides the accuracy and the physics loss provides the power balance. For edge monitoring, we distil the trained $2.0\times10^{7}$-parameter model into students of $6\times10^{5}$ and $1.3\times10^{6}$ parameters; a flat-start initialisation prevents their collapse into an incorrect low-voltage state in which the characteristic saturates. With output distillation, the 12-step student reaches 1.4 times the teacher's error and, for edge inference on an NVIDIA Jetson Orin Nano (15 W), solves an hourly scenario in 12.2 ms, within the 20 ms synchrophasor interval.

Closest papers

Nearest neighbours by meaning across the whole index.

Droop-Aware Foundation Model Power Flow

cs.ET ·2026-09-20 ·Khezr Sanjani, Peng Zhang
similarity 0.68
Abstract

This paper develops a droop-aware extension of the GridFM power systems foundation model, embedding droop gains and frequency/voltage deadband parameters as per-bus node features to enable control-aware AC power-flow analysis. Existing power-flow datasets encode only static electrical features, conflating operating points from qualitatively different control regimes; this work resolves that gap by exposing droop and deadband parameters as structured node features, with deadband discontinuities handled through a smooth tanh approximation that preserves solver differentiability. A transformer-based graph neural network is pre-trained on masked reconstruction and fine-tuned on the resulting control-aware datasets. The framework is validated against PSCAD electromagnetic-transient simulations on a two-bus system (0.11% maximum steady-state error) and cross-validated against an independent PyPower droop solver on the IEEE 24-bus RTS. On the 24-bus system the surrogate attains R2 = 0.9996 for active generation and 0.0015 p.u. voltage-magnitude RMSE; scalability is confirmed on the IEEE 300-bus system (0.0036 p.u. RMSE, R2 = 0.9841 for voltage magnitude across 299,700 predictions). A three-mode control study further shows that the deadband widens the control-error distribution while leaving total droop compensation unchanged, establishing deadband width as an actionable node-level design feature.

0.29

Physics-Aware Distillation of a Grid Foundation Model for Real-Time Edge Inference

cs.LG ·2026-10-15 ·Vlad Alexandru Sănduleac, Shahariya Rasheed Rayamarakkarveettil Puthanpurayil, Noman Khan, Remus Teodorescu
benchmark similarity 0.68
Abstract

Grid foundation models (GridFMs) are graph transformers pretrained on a masked power-flow objective, and evaluate power flow orders of magnitude faster than an iterative solver. Their size, however, targets data-centre inference, whereas low-inertia operation increasingly asks for inference at the edge, next to the measurement, at batch size one and within a single synchrophasor (PMU) reporting frame. We distil a 20.1M-parameter, 12-layer GridFM teacher into a 0.62M-parameter, 6-layer student, a $32.5\times$ parameter reduction at half the message-passing depth, using an objective that combines the masked power-flow loss with output, physics-residual, latent-state and attention transfer. The physics-residual term, which matches the teacher's power-residual profile, has not previously been applied to typed power-grid graphs. We evaluate on a renewable variant of the IEEE 118-bus benchmark grid in which 26 of the conventional (synchronous) generators are replaced by inverter-based renewables with battery flexibility and standardised reactive-power limits (IEEE 1547), giving $97\,529$ physically valid (AC-OPF-feasible) operating scenarios, and we ablate all eight combinations of the transfer terms, reporting accuracy against ground truth and fidelity to the teacher separately. Distillation lowers student error on all four predicted quantities, by up to $48\%$ on active-power dispatch, and every distilled student is more accurate than its teacher on reactive-power dispatch. The gain is largely carried by the output matching term. The physics-residual term, in the layer-aggregated form used here, is consistently harmful, which we attribute to the spatial averaging it applies to a bus-level residual field. The resulting student is $32.5\times$ smaller in parameter count and has half the message-passing depth, making it a candidate for subsequent edge-device benchmarking.

0.40

Toward Out-of-Distribution Generalization in Neural AC Power Flow

cs.LG cs.AI ·2026-11-18 ·Ojas Sanghi, Anvita Bhagavathula, Alvaro Carbonero, Priya L. Donti
published similarity 0.67
Abstract · 11 pages, 5 figures. Accepted as an oral presentation at the NeurIPS 2026 Workshop on AI Foundations for Power Grids: From Models to Deploym…

Growing uncertainty in power system operations from renewables integration, extreme weather, and data center loads challenges the reliability of traditional power flow solvers at scale. Machine learning-based proxies are a potentially promising alternative, but the prohibitive cost of generating training data for large grids makes out-of-distribution generalization a key capability for deployment; currently, models trained on small grids lack that capability. In this work, we systematically evaluate how physics-informed losses, multi-grid training, and perturbation-based data augmentation improve the zero-shot transfer of three graph neural network-based power flow models from smaller systems to a larger, unseen 500-bus system. We find that (1) physics-informed losses improve transfer relative to purely supervised objectives; (2) multi-grid training on smaller systems matches the best single grid but does not close the gap to target-grid training; (3) perturbation-based augmentation on edge attributes improves transfer by up to 54.6%; and (4) random line/generator dropout does not consistently improve performance.

0.40

A unified power-grid representation for reuse across network structures and computational tasks

eess.SY ·2026-09-07 ·Yanhao Huang, Changqing Liu, Zichang Wang, Qianhong Wu
similarity 0.66
Abstract

Data-driven power-system models are typically developed for specific grids and computational tasks, but their performance can deteriorate markedly or even fail when network structures or analytical objectives change. This paper develops a unified grid representation that separates physical-grid description from downstream computation. A self-supervised encoder represents each grid as a variable number of fixed-dimensional node, branch and global vectors under a common latent description. Although pretrained only on systems with at most 270 buses, the frozen encoder transfers without adaptation to a 70,000-bus network, more than 250 times larger in bus count, while preserving 0.7919 bus-correspondence accuracy. The same representation supports four independently trained downstream tasks: power-flow calculation, reactive-power adjustment, operating-condition generation and transient-stability assessment. On the previously unseen 70,000-bus grid, power-flow calculation achieves mean errors of 0.108$^{\circ}$ in phase angle and 3.8$\times$10\textsuperscript{-6} p.u. in voltage magnitude. Reactive-power adjustment achieved a 75\% PSASP-verified correction rate on the previously unseen 70,000-bus grid, while operating-condition generation delivered at least one PSASP-verified feasible state for 82.2\% of requests on previously unseen 400--1,000-bus grid families. For transient-stability assessment, the frozen encoder achieves accuracy within 0.8 percentage points of full encoder adaptation under matched training conditions. These results demonstrate that a unified power-grid representation can be learned once and reused unchanged across structurally different power systems and heterogeneous computational tasks.

0.47

Learning by Examples: Power Grid Steady State Analysis with a Tabular Foundation Model

cs.LG ·2026-10-14 ·Olayiwola Arowolo, Oluwadara Adedeji, Peter Palensky, Jochen L. Cremer
similarity 0.64
Abstract · 12 pages, 8 figures, under review

Foundation models have shown strong generalization across scientific domains, but their use in power systems remains largely task-specific. We investigate whether a pretrained tabular foundation model (TFM), TabPFN, can serve as a general-purpose neural solver for power grid steady-state analysis. We evaluate the TFM on three tasks: power flow (PF) prediction, N-k contingency screening (NCS), and voltage stability margin (VSM) prediction. We performed experiments on 118- and 2000-bus systems, comparing the TFM against task-specific neural baselines. Without retraining or fine-tuning, the TFM matches or outperforms the best task-specific model in several settings across the three tasks. For 118-bus PF prediction, a variant of the TFM achieves errors of $1\times 10^{-3}$ pu for voltage magnitudes and $0.30^\circ$ for voltage angles, outperforming all baselines. On unseen N-1 contingency and close-to-infeasible PF cases, the TFM is competitive with the DCPF approximation. For millions of unseen N-2 contingencies, the TFM achieves AUCs of 0.92 and 0.95 for branch and voltage violation screening, respectively. The TFM also attains accurate VSM prediction performance for the 2000-bus system with limited labelled data. The TFM attains strong results across the tested tasks despite pretraining without any power-system-specific dataset and requiring no fine-tuning step. These results offer a glimpse into the potential of pretrained TFMs as a neural solver for a range of power grid analysis tasks.

0.15

Benchmarking Graph Neural Networks for AC Power Flow: The Role of Inductive Biases and Physical Constraints

cs.LG cs.AI ·2026-10-28 ·Federico Clerici, Ferran Bohigas-Daranas, Hamid Latif-Martínez, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt +1 more
benchmark similarity 0.64
Abstract

Fast and accurate models for AC power flow (ACPF) are increasingly important as modern electrical grids require more frequent system analyses. Graph neural networks (GNNs) naturally exploit electrical grid topology, yet the effects of architectural design choices on predictive performance remain poorly understood given differences in graph representations and evaluation settings across studies. We present a unified benchmark of representative GNN architectures for ACPF prediction under a common experimental framework. All models use identical preprocessing and training procedures and comparable parameter budgets, isolating the impact of message-passing mechanisms and inductive biases. We also analyze errors by distance from the slack bus and systematically ablate key design components. We evaluate predictive accuracy and physical consistency on the IEEE 14-bus and IEEE 118-bus systems. Results indicate that anisotropic message-passing architectures offer the most favorable trade-off between predictive accuracy and physical consistency under the studied parameter and topology constraints. Explicit edge features encoding line impedances and global context aggregation are particularly important for representing electrical interactions and system-wide dependencies, especially for voltage-angle predictions on the topologically bottlenecked IEEE-118 grid. Under a budget with approximately fixed parameters, two or three message-passing layers generally provide the best balance between depth and representation width, while additional depth offers no consistent improvement. Ablations also show that standard residual and root connections are not necessarily beneficial in shallow models, and that aggregation operators involve trade-offs between statistical accuracy and physical consistency. These results provide practical guidelines for designing graph-based power system models.

0.17

Physics-Informed but Not Physics-Consistent: Error Geometry and Subspace Projection for Neural AC Power Flow

cs.LG cs.AI ·2026-10-05 ·Changhun Kim, Timon Conrad, Redwanul Karim, Karan Pahlajani, Julian Oelhaf +5 more
code/data similarity 0.63
Abstract · ICASSP 2027 submitted; 3 figures, 3 tables. Code: https://github.com/Kimchangheon/neural-acpf-error-geometry

Recent neural power-flow solvers, including emerging foundation models, achieve accurate voltage predictions, yet such accuracy does not necessarily imply physically consistent solutions. Even small complex voltage errors can yield large AC power-balance residuals. We study this accuracy-consistency gap across PIGNN-GC, GridSFM, gridfm-graphkit, and LUMINA on realistic 2224-bus Great Britain network (GBnetwork) scenarios, with cross-grid evaluation of GridSFM over 31 systems. Using a singular value decomposition (SVD) basis fitted to training AC power-flow solutions, we find that neural prediction errors contain substantial components outside the dominant solution subspace. To address this mismatch, calibrated solution-subspace projection (CSP) suppresses off-subspace prediction components after train-only bias calibration, reducing Mean PB by 67.0%, 37.8%, 40.5%, and 68.9% for PIGNN-GC, GridSFM, gridfm-graphkit, and LUMINA, respectively, relative to calibrated predictions, while improving voltage-magnitude accuracy in all four models. These results identify output-error geometry as an important factor in physics-consistent neural AC power flow. Code: https://github.com/Kimchangheon/neural-acpf-error-geometry

0.34

GENCO - A Unified Neural Solver Embedded in a Development Framework for Steady-State Grid Analysis

cs.AI ·2026-08-10 ·Alban Puech, Matteo Mazzonelli, Tamara R. Govindasamy, Mangaliso Mngomezulu, Héctor Maeso-García +17 more
code/datahighly cited similarity 0.63
Abstract

Foundation models are transforming business workflows and boosting productivity, yet they remain largely absent from engineering domains such as power system analysis, where strict physical consistency must be enforced. We present GENCO (GEometric Neural Corrective Optimizer), a unified neural solver for steady-state transmission grid analysis that handles power flow (PF), optimal power flow (OPF), and state estimation (SE) within a single architecture and shared grid representation. To support advances in neural power system solvers, we introduce the open-source GridFM Development Framework, which standardizes synthetic data generation and training in a low-code environment. We also release large-scale datasets with millions of PF and OPF scenarios across diverse grid topologies to support reproducible benchmarking. We evaluate GENCO on the PFDelta and OPFData benchmarks against state-of-the-art neural solvers and classical solvers, including Newton-Raphson and IPOPT, as well as on real-world Hydro-Québec SCADA data. For large-scale PF, GENCO recovers the full AC operating state, including voltage magnitudes and reactive power that DC-PF cannot provide, while matching DC-PF-level active power-balance residuals. It achieves up to 30x speedups over Newton-Raphson at only 2x the runtime of DC-PF. For OPF, it achieves up to 85x speedups over IPOPT while improving feasibility, optimality, and runtime over DC-OPF. For SE, GENCO is more robust than classical weighted least squares to noisy measurements and grid parameter errors, and always returns a high-quality estimate even when weighted least squares fails to converge. Together, the unified architecture and development framework provide a new approach to large-scale steady-state grid analysis, lowering the barrier to entry for power system engineers and marking a step toward Grid Foundation Models.

0.60