CS Paper Radar

Online Identification Can Replace a Floor-Plan Prior on Unseen Buildings

Elias T. -H. Shieh, Chun Fu

eess.SY cs.LG ·submitted 2026-11-25 02:23 UTC · v1
publishedbenchmark

Abstract

The Smart Buildings Challenge asks for one HVAC control policy that runs office buildings and weather it has never seen, from the building's metadata and sensor streams alone. Our controller sees no data from the target building before it runs and is not tuned per building; its few global constants were set on development scenarios. Each zone has a first-order grey-box model that starts from coefficients computed from the floor plan and is updated online by recursive least squares, and a planner and a closed-form mapping turn the models into plant commands. On two sets of buildings and weather that we generated, a validation set and a stress set with real-year weather, it scores 0.145 and 0.159 times the starter kit's PID baseline, and 0.095 times on a holdout built after all versions were fixed and scored once. It improves on every building, also against our two implementations of ASHRAE Guideline 36: per set it scores 0.60 to 0.71 times a basic version and 0.83 to 0.96 times one partly tuned on the public leaderboard, which wins one of 54 scenarios; with a 5 °C frost target for empty zones on both, the margin over the tuned version shrinks to 1.4% on the stress set, where one of six buildings is 0.2% worse. In an ablation on a reduced-order model, removing both the floor-plan prior and online identification costs 28%, 20% and 42% on the validation, stress and holdout sets, far more than the two effects combined: either source of building-specific information recovers most of what is lost without both. On one office floor in a second simulator, BOPTEST, this does not carry over: with identification on, the two priors give similar results, but the floor-plan prior alone, with constants fitted on the competition's simulator, is the least stable arm. These simulation results motivate testing floor-plan-initialised adaptive control in buildings that have drawings but no operating data.

Comment
Smart Buildings Competition Track, NeurIPS 2026. First place, Round One paper prize. 8 pages main text, 21 pages in total, 8 figures, 5 tables

Closest papers

Nearest neighbours by meaning across the whole index.

The Smart Buildings Challenge: Learning Foundation Models for Real-World Optimization at Scale

cs.AI ·2026-10-13 ·Judah Goldfeder, Ayush Rai, Philippe M. Wyder, Na Li, Victoria Dean +9 more
similarity 0.67
Abstract · This is for a Neurips 2026 competition

Buildings cause nearly 40\% of carbon emissions in the US. Of total building emissions, HVAC systems are responsible for approximately 40-60\% and account for 15\% of global energy consumption. Despite advances in artificial intelligence, most buildings still operate as inefficiently as they did decades ago. Building optimization, perhaps more so than any other optimization problem, has enormous potential for Machine Learning (ML) driven impact on climate change, in both the short and long term. One of the biggest obstacles for building optimization is the lack of policy transfer. Most building control systems, whether simulation or learning based, don't generalize: they only work well for the building they were developed for, but not for other buildings. To solve this problem, we propose a challenge for the development of building foundation models that easily adapt to new buildings with minimal configuration and thereby enable building optimization to scale across the globe. Participants will build control policies on a set of simulated buildings, and have their policies evaluated on an unseen set of buildings. The buildings vary in size, layout, weather, material properties, and HVAC system. Successful outcomes from this initiative promise a massive leap forward in global sustainability efforts and demonstrate the great potential of ML to combat climate change.

0.33

Ground-Truth-Aware Stress Testing of a Closed-Loop Smart-Building Digital Twin Under Sensor Drift and Missing Data

cs.CE ·2026-08-14 ·Lyes Saad Saoud
similarity 0.63
Abstract

Digital twins are increasingly used for smart-building monitoring and control, yet many evaluations focus on state estimation or fault detection rather than whether sensing errors materially affect closed-loop outcomes. This paper introduces a ground-truth-aware simulation framework that separates the latent physical state from a corrupted sensing layer and compares practical sensor-driven policies with an oracle controller. The synthetic twin includes 20 zones simulated at 15-minute intervals over 30 days and models occupancy-driven CO2, ventilation-energy trade-offs, sensor drift, measurement noise, and missing observations. Policy comparisons use a one-step information delay and common random numbers for paired Monte Carlo evaluation. Under nominal sensing, the raw-sensor controller disagreed with the oracle on 2.59% of decision steps, while aggregate CO2, energy, and comfort outcomes remained nearly unchanged. At 8x nominal drift, decision mismatch increased to 7.00%, but outcome gaps remained small. Across a 4x4 drift-missingness grid, none of 48 sensor-driven policy-condition combinations crossed the predeclared material-divergence thresholds. A three-sample rolling median increased nominal mismatch from 2.59% to 6.31% without meaningful outcome improvement, and Ground-Truth Regret rankings varied with utility weights. The results show that sensor error, decision disagreement, and outcome degradation are related but distinct. Because the study is fully synthetic and uncalibrated, its contribution is methodological rather than a claim of real-building performance.

0.04

Where Can a Decision Model Diagnose HVAC Faults? Reasoning Demand, Physical Representation, and Robustness Under Shift

cs.AI ·2026-10-07 ·Wooyoung Jung
similarity 0.60
Abstract · 58 pages, 4 figures, 12 tables. Submitted to Energy and Buildings

Artificial intelligence supports building operations in several forms, each with its own barrier. Expert rules must be tuned for every system, supervised models need labeled data that buildings rarely record, and language models return free text that requires human-in-the-loop checking, since their stated confidence is unreliable. A newer kind of pretrained model, here called a decision model, returns a probability for every allowed answer, so one model could serve many decisions without training. This study answers three open questions for fault diagnosis in heating, ventilation, and air-conditioning systems: which decisions such a model can make, what input it needs, and whether its probabilities hold when conditions change. On 128 fault days from four public datasets of real equipment, faults are graded by the reasoning their diagnosis demands, with data given raw, as physical features, or with Brick topology. The decision model Jev, open language models, and a supervised model face nine tests that change season, control configuration, or building. Given physical features, Jev and the larger open model diagnosed faults whose evidence one feature carries, but not faults that need operating context. Under shift they kept their accuracy and calibration, while the supervised model lost 0.33 macro-F1 yet led or tied within a building. Their probabilities still needed correction, and detection was weak. The study maps which faults a decision model can diagnose and from what input, and supports a division of work in which code computes the physics and the model ranks candidate faults for an operator.

0.64

Large Language Models for HVAC Operations in Building Energy Systems: A Critical Review of Methods, Applications, and Deployment Readiness

cs.AI cs.CLeess.SY ·2026-09-04 ·Alexander Neubauer, Tianzhen Hong, Han Li, Mengbo Yu, Amin Darbandi +2 more
survey similarity 0.60
Abstract · 38 pages, 9 figures, 16 tables. Submitted to Energy and Buildings

Building automation systems generate rich sensor data yet remain insight-poor because heterogeneous point naming, missing metadata, and fragmented documentation obstruct their operational use. This systematic review analyses and codes 66 peer-reviewed studies on large language models (LLMs) for HVAC operations published between 2023 and March 2026. Each study is classified across five application families and three LLM method families and assessed for evidence realism, deployment readiness, and the responsibility boundary between the LLM and physical HVAC decisions. The corpus is concentrated in building energy modelling (BEM, 32 of 66 papers), while load forecasting remains too sparse for subfield-level conclusions. Only four studies reach pilot-level evidence, and none reports sustained operational deployment. No study was classified as ready-now for industry adoption; three were near-term and 63 research-only. Nevertheless, several bounded, human-in-the-loop uses merit near-term trials, including point-name normalisation, document-grounded operator support, BEM workflow assistance, and advisory interfaces around physics-based controllers. Conventional machine learning (ML), model predictive control (MPC), reinforcement learning (RL) and ontology-based tools remain more adopted for high-frequency control, short-horizon numerical forecasting, and well-posed ontology mapping, while autonomous agentic operation and unvalidated occupant proxies remain research-stage. Current evidence therefore supports LLMs primarily as semantic and workflow layers rather than autonomous HVAC controllers. Future work should prioritise field-validated benchmarks, orchestration evaluation under operational constraints, and LLM-MPC/RL architectures with bounded latency and verifiable safety properties.

0.64

How ready is the United States commercial building stock for artificial intelligence? A national estimate from energy codes and survey data

cs.CY ·2026-11-15 ·Wooyoung Jung
similarity 0.59
Abstract · 48 pages, 9 figures, 17 tables. HUBS Lab Paper No. 2026-011. Code and data: doi:10.5281/zenodo.23966090

Buildings serve as platforms for artificial intelligence (AI) through the data they generate, but the building stock's readiness as an AI platform has not been assessed. A recent framework measures a building's AI readiness as the share of 76 answer levels, across 31 types of operators' questions, that its recorded data could reach, and has so far been applied only to individual buildings. This study applies it to the 2018 U.S. commercial building stock. It combines 6,436 records of the Commercial Buildings Energy Consumption Survey with ASHRAE 90.1's data requirements, state code adoption, advanced-meter statistics and 45 buildings' knowledge graphs, imputing each building's code edition and data recording. Weighted by floor area, the stock could answer on average 0.145 (95% interval 0.127-0.163) of these answer levels. For 92.0% of floor area its data answer less than half of the questions about current status, and most floor area stays below that mark under every tested assumption about compliance, description and the reference buildings. More than half of what installed equipment could answer is lost in recording, mostly because conventional thermostats store nothing and meters lack interval readings. Readiness rises with size, from 0.073 in buildings of at most 5,000 ft$^2$ to 0.173 at 25,000 ft$^2$ or more. Only 1.6% of floor area was built under a code edition requiring recording, introduced in 90.1-2013 for large buildings. The study gives the first national baseline of commercial-building AI readiness and a public-data method that can be reapplied to each new survey to track the stock.

0.18

One Agent per Zone: Decentralised Active Inference under Partial Observability for Multi-Zone HVAC Control on Edge Hardware

cs.MA cs.AI ·2026-10-14 ·Panagiotis Kasnesis, Lazaros Toumanidis, Christos Chatzigeorgiou, Amalia Contiero Syropoulou, Miguel De Prado
published similarity 0.58
Abstract · 9 pages, 3 figures, accepted in European Conference on EDGE AI Technologies and Applications, EEAI 2026, Malta

Multi-zone HVAC control is a shared-resource problem: zones on a floor share one fan and cooling coil, so each zone's demand affects its neighbours and the building's peak power. One controller per zone scales well and isolates faults, but each controller then observes only its own zone, not the shared air loop. In this work, we present a decentralised controller that assigns each zone an independent active-inference agent, which plans by minimising expected free energy and learns its zone dynamics online. The agents exchange no messages, so none depends on peers or a coordinator; each accounts for the unobserved coupling through a latent disturbance and a congestion signal derived from the metered power of the other floors. Fifteen agents are evaluated in EnergyPlus on a Sinergym office building against three rule-based controllers and three MADDPG fleets, one given the same floor meters. On five noisy weather years unseen during training, the fleet attains the lowest mean building peak (88.3 kW, 3 to 17 % below the baselines) and staggers the floor peaks better than any baseline, with a coincidence factor (building peak over the sum of the floor peaks) of 0.929 versus 0.936 to 0.994. Compared with a reactive rule at similar comfort (0.912 versus 0.916), it lowers the sum of monthly peaks, on which demand charges are billed, by 33 kW (4 %) in every year, at the cost of about 10 % more energy. It costs 9% less per year than the proactive rule (at lower comfort) and 1% less than the MADDPG fleet given the same floor meters, in every test year. The whole fleet runs on a single low-cost Raspberry Pi 5, closing the observation-to-action loop over MQTT in 442 ms at p95, far below the 15-minute control step.

0.32

User-specified Kelvin-hour budgets within model predictive control for energy-efficient buildings: Simulation and field demonstration

eess.SY ·2026-09-06 ·Jicheng Shi, Colin N. Jones
similarity 0.58
Abstract

For energy-efficient building control, model predictive control (MPC) has been widely proposed to reduce energy use while maintaining prescribed indoor temperature bounds. In practice, MPC implementations may still produce temperature-bound violations because of model mismatch, weather-forecast errors, and softened constraints introduced to preserve feasibility. Existing soft- constrained MPC usually handles this trade-off through slack-weight tuning, so users cannot prescribe a violation-severity budget before operation. This paper develops a Kelvin-hour (Kh)-budget MPC that allows users to specify a running-average budget for temperature-bound violation severity. During operation, the controller uses the realized Kh budget surplus or overspend to update the temperature bounds, providing step-by-step budget feedback. We evaluate the method in two high-fidelity BOPTEST simulation cases and in an occupied residential deployment. In the first one-zone case, prescribed budgets produce clear running-average Kh violation responses across predictors and disturbance settings. At a prescribed budget of 0.005 Kh/step, the controller reduces energy use by 31.9% and Kh violation by 36.2% relative to the built-in default controller. In the second coupled two-zone case, separate zone budgets produce zone-level responses, with 18.9%-20.5% energy reduction and 9.4%-64.3% zone-level Kh violation reduction. In the occupied residential deployment, the running-average Kh violations remain close to or below their prescribed budgets under real sensing, actuation, weather, and occupancy conditions.

0.46

Which Buildings Are Artificial Intelligence-Ready? A Measurement-Based Assessment Framework for AI Question Answering and Actuation

cs.AI ·2026-10-06 ·Wooyoung Jung
similarity 0.56
Abstract · 47 pages, 11 figures, 23 tables. Code, results and data supplement: https://doi.org/10.5281/zenodo.23197610

Agentic artificial intelligence (AI) systems are becoming the interface to buildings, answering questions and controlling operations, but a building's readiness for them has not been systematically assessed. This study proposes a framework to quantify it. First, a building's knowledge graph sets two ceilings. The answerable-readiness ceiling is the share of operational questions its data could answer, and the actuation-readiness ceiling is the share of control actions it exposes. Second, a reference AI agent's accuracy on a fixed set of these questions shows how much of the ceilings is realized. On a simulated office, the agent realizes 0.62 of a 0.64 answerable ceiling, so missing data, not the AI, limit readiness, except in naming a fault's cause. Across 37 public real-building graphs, the median answerable ceiling is 0.16, and in 15 of 45, unlinked sensors lower it. The framework turns "is this building AI-ready?" into an auditable, ranked retrofit question.

0.53