User-specified Kelvin-hour budgets within model predictive control for energy-efficient buildings: Simulation and field demonstration

Jicheng Shi, Colin N. Jones

eess.SY ·submitted 2026-09-06 16:15 UTC · v1

Abstract

For energy-efficient building control, model predictive control (MPC) has been widely proposed to reduce energy use while maintaining prescribed indoor temperature bounds. In practice, MPC implementations may still produce temperature-bound violations because of model mismatch, weather-forecast errors, and softened constraints introduced to preserve feasibility. Existing soft- constrained MPC usually handles this trade-off through slack-weight tuning, so users cannot prescribe a violation-severity budget before operation. This paper develops a Kelvin-hour (Kh)-budget MPC that allows users to specify a running-average budget for temperature-bound violation severity. During operation, the controller uses the realized Kh budget surplus or overspend to update the temperature bounds, providing step-by-step budget feedback. We evaluate the method in two high-fidelity BOPTEST simulation cases and in an occupied residential deployment. In the first one-zone case, prescribed budgets produce clear running-average Kh violation responses across predictors and disturbance settings. At a prescribed budget of 0.005 Kh/step, the controller reduces energy use by 31.9% and Kh violation by 36.2% relative to the built-in default controller. In the second coupled two-zone case, separate zone budgets produce zone-level responses, with 18.9%-20.5% energy reduction and 9.4%-64.3% zone-level Kh violation reduction. In the occupied residential deployment, the running-average Kh violations remain close to or below their prescribed budgets under real sensing, actuation, weather, and occupancy conditions.

Closest papers

Nearest neighbours by meaning across the whole index.

Model-Free Control for Residential Heating: Deployment and Simulation of Nonlinear Data-Enabled Predictive Control

eess.SY math.OC ·2026-09-18 ·Sebastian Zieglmeier, Chris Verhoek, Jaap Eising, Mathias Hudoba de Badyn
similarity 0.68
Abstract · 19 pages, 8 figures, 7 tables

Residential heating accounts for a large share of building energy use, and predictive control strategies can reduce it by anticipating rather than reacting to the room temperature alone. The usual manner of implementing predictive control, model predictive control (MPC), requires an accurate model of each individual residential unit for heating control. Obtaining this model is time-consuming to obtain manually or even impossible, and such models do not transfer across a heterogeneous building stock. Data-enabled predictive control (DeePC) removes this modeling step by designing the controller directly using measured trajectories of the system. The foundations of DeePC, however, are built on the class of deterministic linear time-invariant systems, which is an unrealistic assumption for residential heating. This work applies three recently proposed nonlinear extensions of DeePC, collectively referred to as data-driven predictive control (DPC): Select-DPC, gain-scheduling DPC, and linear parameter-varying DPC. These are compared against standard DeePC and the hysteresis controller, the industry standard in residential heating. The comparison runs over a full heating season on a calibrated digital twin of an occupied research unit, the NEST research building in Switzerland, assessed by heating energy and comfort-band violation. Moreover, gain-scheduling DPC was deployed on the real residential apartment and validated the conclusions from the simulations. Each of the DPC controllers consumes significantly less energy than the hysteresis controller, amounting to roughly $11\%$ over the season, validating the use of DPC. The nonlinear methods further outperform linear DeePC in all assessed scenarios, and we analyze the relative costs and benefits of each nonlinear method.

0.40

Online Optimization for Controlling HVAC Systems

eess.SY math.OC ·2026-11-05 ·Tong Wu, Dominik Baumann, Angela Fontan, Nicola Bastianello
similarity 0.65
Abstract

Heating, ventilation, and air-conditioning (HVAC) systems account for a significant portion of buildings' energy consumption, motivating the design of energy- and cost-efficient control strategies. However, conventional strategies employ simple, reactive control, without incorporating a model. Therefore, in this paper we adopt an economic model predictive control framework and focus on designing online algorithms to solve the control input design problems with a limited computational budget. In particular, we propose two tailored online algorithms based on projected gradient descent, with a custom projection routine, and the projected primal-dual method. We discuss the pros and cons of both algorithm designs, focusing in particular on computational efficiency. We further compare them through numerical experiments simulating the control of an HVAC system over the course of a day. The results show that computationally efficient online solvers for HVAC systems control are indeed possible. Moreover, the performance closely matches that of a baseline algorithm with unlimited computational budget, in terms of reference temperature tracking and comfort temperature range enforcement.

0.30

Comfort as a Constraint or as a Cost in Reinforcement Learning and Model Predictive Building Control

eess.SY cs.LG ·2026-11-16 ·Joram Liebeskind, Valentin Bhend, Varsha N. Behrunani, Alisa Rupenyan
similarity 0.63
Abstract

A building controller that keeps a zone within comfort bounds at minimum energy can treat the bounds as a soft constraint, by adding the weighted violation to its cost, or as a hard constraint. We analyze the effect of the hard and the soft formulation of the same problem and isolate the effect of the formulation from the effect of the algorithm. To this end, we measure the difference in energy use between the two formulations on the BOPTEST bestest_hydronic_heat_pump case, in model predictive control (MPC) and in reinforcement learning (RL). The soft formulations are a weighted MPC and weighted SAC and DDPG learners, each at twelve weights. The hard formulations are an MPC with an exact penalty and the Lagrangian learners SAC-Lagrangian and primal-dual DDPG. We find that the hard formulations use more energy than the soft formulations at the largest weight, but violate the comfort bounds less. For a large weight, the soft formulation approaches the behavior of the hard formulation. The frontiers of the energy-comfort trade-off of the three weighted controllers lie close to each other, and the weight selects an operating point on this frontier. Under the soft formulation, the three algorithms reach very similar operating points, although at somewhat different weights. For this HVAC problem, the formulation and the weight thus affect the energy use more than the choice of algorithm.

0.35

Model Predictive Control for Dynamic Hydraulic Balancing in Building Radiator Heating Systems: Modeling, Design, and Experimental Validation

eess.SY math.OC ·2026-09-08 ·Erfan Shakhesi, Maurice Heemels, Paula Chanfreut
similarity 0.62
Abstract

Hydronic radiator systems are among the most widely used heating systems in buildings. In the literature, radiator heat outputs are often assumed to be independent of one another and arbitrarily adjustable in time when designing controllers. However, in practice, radiators are supplied by one or multiple common heat sources and are hydraulically coupled through the water circulation system. Maintaining occupant comfort in multi-zone buildings therefore requires not only an appropriate supply temperature but also proper hydraulic balancing to distribute the available water flow according to the heating demand of each zone. To this end, we develop a grey-box thermal model that captures the hydraulic interactions among radiators and the effects of radiator valves, circulation pumps, and heat sources. In a real building, we show that accounting for hydraulic interactions reduces the root mean square error (RMSE) between the measured and modeled zone temperatures by approximately 11% compared with a model that neglects these interactions. Additionally, we integrate the developed model into a model predictive control (MPC) framework for dynamic hydraulic balancing that jointly optimizes valve openings and the supply temperature to maintain thermal comfort in each zone while reducing energy consumption. Through both real-world experiments and numerical case studies, we demonstrate that, compared with existing MPC formulations that neglect hydraulic interactions or do not control radiator valves, the proposed MPC reduces comfort-range violations by at least 27% while requiring a similar or even lower cumulative supply temperature.

0.39

Economic Model Predictive Control with Policy-Guided Terminal Ingredients

eess.SY ·2026-09-02 ·Salim Msaad, Robert D. McAllister
similarity 0.62
Abstract

Conventional designs for model predictive control typically rely on terminal costs and constraints derived from a steady state to guarantee closed-loop stability and performance. However, this dependence on a steady-state assumption limits the applicability of this control method to systems in which such a fixed operating point is either not available or not desirable. This work introduces a novel framework, termed policy-guided MPC, to address this limitation. Our approach constructs terminal costs and constraints using a known sub-optimal control policy. Specifically, the terminal region is defined around a center determined by a rollout of the policy, and a penalty on deviation from this center is used to define the terminal cost. This method obviates the need for a steady state or reference trajectory. Closed-loop performance guarantees are established relative to the guiding policy, for both finite and infinite horizon problems. The effectiveness of the proposed framework is demonstrated through numerical simulations on an energy management example.

0.22

Adjacent Heat Transfer Effects Can Bias Savings Estimates When Controlling Only Part of a Multi-Zone Building

eess.SY ·2026-11-12 ·Arash J. Khabbazi, Kevin J. Kircher
publishedtheory similarity 0.61
Abstract · 10 pages. Accepted at the 2027 ASHRAE Winter Conference

Field demonstrations of advanced heating, ventilation, and air-conditioning control often operate a few thermal zones within a larger building and report savings for those zones alone. A recent theorem showed that this practice overestimates whole-building savings, because heat drawn from the neighboring zones is paid for by their equipment and is not counted. The error grows with the thermal conductance between the controlled and uncontrolled zones, with how much colder the controlled zones run over the test, and with the price of the heat their neighbors supply. For one controlled zone with one neighbor, a single thermal price, and slowly changing prices, the relative error reduces to the ratio of two conductances, a screening number that can be evaluated from the two conductances before a demonstration begins. This paper tests how far that reduction can be taken. A two-story house with one thermal zone per floor is simulated over a 90-day heating season in West Lafayette, Indiana, with receding-horizon model predictive control on the first floor and setpoint control on the second, under four combinations of electricity tariff (time-of-use or flat) and heating plant (heat pump or electric resistance). The exact correction from the theorem recovers the true savings in every case, and the full theorem, evaluated from the controlled zone's temperatures, the prices, and the building parameters, reproduces the measured relative error in every case. The conductance ratio bounds that error from above in all four cases, tightly under a flat tariff, within 3%, and loosely under a time-of-use tariff, where most of the controller's savings come from shifting load through the thermal mass rather than from lowering the temperature.

0.30

Building Seasonal Highways for Residential Energy Hubs: Sizing, planning and operating thermal energy storage

eess.SY math.OC ·2026-10-01 ·Dario Slaifstein, Mohammad Khosravi, Gautham Ram Chandra Mouli, Laura Ramirez-Elizondo, Pavol Bauer
similarity 0.61
Abstract

The operation of residential energy hubs with multiple energy carriers (electricity, heat, mobility) poses a significant challenge due to the energy storage differences in time-constants, round-trip efficiencies and self-discharge rates. Usually, thermal storage exhibits flexibility in yearly planning optimizations or long-term scenarios. However, as optimization horizons shrink (1-48hs) so does their supplied value due to the lower round-trip efficiencies. To avoid this early depletion during operation this paper proposes a data-driven highway to steer the short-term daily control towards long-term optimality. The proposed methodology also presents how to optimally size the thermal storage and avoid yearly simulations and how all of this is related to nonlinearities in the daily operation. The presented framework links seasonal and daily optimizations through dynamic terminal sets and value functions. The seasonally-aware nonlinear economic model predictive controller achieves the most balanced performance, with the second best mean grid cost of all MPCs at -\texteuro 209. It also achieves better battery degradation control than its linear counterparts (between 26-34%) and the best thermal comfort of the nonlinear benchmarks. Nevertheless, the data-driven seasonal highway restrains the ability to control battery degradation and slightly increases computational time.

0.14

CityLearn v3: A Configurable Simulation and Evaluation Framework for Realistic Control Studies of Renewable Energy Communities

cs.MA cs.AI ·2026-09-18 ·Tiago Fonseca, Luis Lino Ferreira, Armando Sousa, Ava Mohammadi, Zoltan Nagy
similarity 0.61
Abstract · 34 pages, 14 figures

Renewable energy communities (RECs) coordinate buildings, photovoltaic generation, batteries, electric vehicles and flexible loads. Controller studies often simplify changing participation, equipment availability, service deadlines and data quality, so lower cost or peak demand can conceal missed services or infeasible power requests. This paper presents CityLearn v3, a configurable simulation and evaluation framework for REC control studies under these conditions. It represents changing members and assets, flexible-load deadlines, demand-response requests, local energy sharing, and data or equipment failures within one simulation environment. Building and phase power limits constrain controllable requests, while a declared timestep preserves consistent power-to-energy accounting. The framework records controller inputs and distinguishes requested actions from those applied to the simulated equipment. Reference controllers, service- and constraint-aware performance indicators, and trajectory exports support comparisons within and across communities. Software checks and application examples examine service delivery, electrical constraints, settlement and changing scenarios; a synthetic high-frequency trace replay illustrates how aggregation can conceal short peaks without changing annual energy. Together, these records allow aggregate performance to be interpreted alongside service failures, action reductions and participant-level outcomes.

0.22