Stability of Droop-Controlled Low-Frequency Transmission Lines

Rafael Castillo-Sierra, Giri Venkataramanan, Dionisio Ramirez

eess.SY ·submitted 2026-09-01 17:38 UTC · v1
published

Abstract

Low-Frequency AC (LFAC) transmission systems employing power converters are being considered for a varity of applications. This work studies the small-signal stability of an LFAC transmission line controlled by the Droop Control Strategy. Eigenvalue Analysis is used to determine how the controller droop gains, operating frequency, transmission line parameters, and the operating point affect system stability. The results show that the overall system's dynamic is governed by the sum of the droop gains of the AC/AC converters. Analytical results that give insights on how the different system's parameters affect the critical stability point are presented. The results indicate that system stability is affected by the line's length, the line's R/X ratio, operating frequency and voltage.

Comment
6 pages, 3 figures, 2023 IEEE Energy Conversion Congress and Exposition (ECCE)
DOI
10.1109/ECCE53617.2023.10362032

Closest papers

Nearest neighbours by meaning across the whole index.

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.58
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Grid-Forming AC/DC Converters for Meshed DC Networks via Dual-Measurement Frequency Droop

eess.SY ·2026-10-26 ·Hisham Mahmood, Marcelo A. Elizondo
similarity 0.55
Abstract · 10 pages, 12 figures, 1 table

This paper proposes and analyzes a dual-measurement frequency-droop (DMFD) controller for meshed MVDC networks. Using only two local DC measurements, bus-voltage deviation and a filtered DC-port current or power deviation, the controller enables grid-forming operation at both AC and DC ports across the mesh. Although the DMFD regulates neither the DC voltage nor the DC current directly and acts only on the terminal frequency, it is shown that AC-side synchronization closes an effective DC droop at every synchronized terminal, so that the steady operating point of the mesh exists and is unique. Constant frequency deviations at a terminal and single-terminal islanding enter the same DC equations as equivalent current offsets, with the island frequency fixed by the island power balance, allowing node voltages and branch currents to be obtained from one linear system. The steady-state model yields design-use envelopes to map the droop ratios and the net DC-injection levels into bounds on DC-voltage deviation and terminal currents. A small-signal dynamic model is developed and used to generate eigenvalue loci and damping-ratio charts that guide controller-gain selection. Averaged EMT simulations on a four-terminal ring corroborate the analysis: in regimes where PLL-based grid-following control is known to lose damping, the DMFD controller maintains stable operation and follows the predicted steady-state characteristics.

0.29

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.53
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters

eess.SY ·2026-09-09 ·Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt +3 more
benchmark similarity 0.53
Abstract · Best Paper Award in the 2026 5th IEEE International Conference on Power Systems and Electrical Technology

This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.

0.20

Dynamic droop specifications for Grid-Forming Inverter-Based Resources

eess.SY ·2026-08-26 ·Jennifer T. Bui, Dominic Groß, Deepak Ramasubramanian
similarity 0.52
Abstract

The large-scale retirement of synchronous generators requires additional capabilities from inverter-based resources (IBRs) to ensure the stability and reliability of power grids. With the heterogeneous controls of IBRs, it is especially important to understand their behavior on the grid. This work proposes a simple data-enabled dynamic model to capture the small-signal dynamics of IBRs and formulate specifications for grid-forming (GFM) IBRs. The dynamic droop model is complementary to well-studied impedance models and extends the common definition of steady-state droop coefficients to dynamic droop coefficients that fully characterize the IBR small-signal response below the nominal line frequency (e.g., subsynchronous oscillations). We propose bounds on the gain and phase of the dynamic droop coefficients to encode minimum requirements for GFM IBRs to promote interoperability and minimize adverse interactions. The resulting specifications also provide some insights into the much-debated question of how to certify an IBR as GFM. Moreover, we also provide dynamic droop specifications for frequency control ancillary services that, e.g., clarify and generalize the notion of an IBR inertia response. Finally, common grid-following (GFL) and GFM controls as well as original equipment manufacturer (OEM) models are used to illustrate the results and showcase the use of dynamic droop coefficients as a tool to screen IBR dynamics for potential adverse interactions.

0.26

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.52
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Scalable Small-Signal Stability Assessment of Power Systems Based on Frequency-Domain Quadratic Constraints

eess.SY ·2026-09-28 ·Xiaoying Liu, Linbin Huang, Hangyu Chen, Huanhai Xin
similarity 0.52
Abstract

Small-signal stability analysis of power electronics-dominated power systems is becoming increasingly challenging due to the large-scale integration of heterogeneous grid-following (GFL) and grid-forming (GFM) converters. Classical centralized methods, such as eigenvalue analysis and the generalized Nyquist criterion, provide direct stability assessment tools but exhibit limited scalability as the system size increases. This motivates scalable analysis methods for stability assessment and device-level diagnosis, and calls for less conservative stability conditions. To this end, this paper proposes a scalable small-signal stability assessment method with quantitative stability indices for multi-converter systems based on frequency-domain quadratic constraints (FQCs). It is shown that several existing stability conditions, including geometric conditions based on the Davis-Wielandt (DW) shell, numerical range, $x$-$z$ graph, scaled relative graph (SRG), mixed gain-phase condition, and passivity condition, are special cases of the FQC-based stability condition. This FQC-based formulation also clarifies the requirements for decentralized verification of these existing stability conditions. To further reduce conservatism, a full-multiplier FQC-based stability condition is developed, based on which an optimization problem is formulated for scalable stability certification and device-level diagnosis using quantitative stability indices without relying on graphical inspection. Combined with the mixed gain-phase condition, this optimization problem forms a hierarchical screening-diagnosis procedure that improves efficiency. Case studies demonstrate that the proposed method is less conservative than existing criteria and can effectively identify problematic devices associated with potential instability risks.

0.40

Improved Droop Control in DC Microgrids via Voltage-Locked Loop Synchronization

eess.SY ·2026-09-18 ·Ognjen Stanojev, Jovan Krajacic, Enea Bianda, Orcun Karaca, Mario Schweizer
similarity 0.51
Abstract

DC microgrids are low- or medium-voltage networks designed to connect and manage DC-based sources and loads. A key challenge in operating DC microgrids is maintaining the DC voltage within certain predefined limits while ensuring its stability. Droop control, the most common method towards addressing this challenge, enables decentralized voltage control and power sharing, but suffers from poor transient performance, resulting in voltage dips and overshoots in applications with fast varying loads such as AI datacenters. This paper introduces an improved droop control method based on voltage-locked loop synchronization, which ensures DC voltage stabilization with significantly improved transient response and achieves the desired load sharing between the available source converters. The core design principle is reflected in the functional separation of the control scheme into a virtual DC machine (VDCM) that operates as a spinning wheel and a virtual current source connected in parallel. The transient response is provided by the VDCM to damp and stabilize DC bus voltage variations, while the slow droop response is provided by the virtual current source to ensure steady-state power balance. The performance of the proposed method is validated in an experimental microgrid setup.

0.18