Grid-Forming AC/DC Converters for Meshed DC Networks via Dual-Measurement Frequency Droop

Hisham Mahmood, Marcelo A. Elizondo

eess.SY ·submitted 2026-10-26 16:32 UTC · v1

Abstract

This paper proposes and analyzes a dual-measurement frequency-droop (DMFD) controller for meshed MVDC networks. Using only two local DC measurements, bus-voltage deviation and a filtered DC-port current or power deviation, the controller enables grid-forming operation at both AC and DC ports across the mesh. Although the DMFD regulates neither the DC voltage nor the DC current directly and acts only on the terminal frequency, it is shown that AC-side synchronization closes an effective DC droop at every synchronized terminal, so that the steady operating point of the mesh exists and is unique. Constant frequency deviations at a terminal and single-terminal islanding enter the same DC equations as equivalent current offsets, with the island frequency fixed by the island power balance, allowing node voltages and branch currents to be obtained from one linear system. The steady-state model yields design-use envelopes to map the droop ratios and the net DC-injection levels into bounds on DC-voltage deviation and terminal currents. A small-signal dynamic model is developed and used to generate eigenvalue loci and damping-ratio charts that guide controller-gain selection. Averaged EMT simulations on a four-terminal ring corroborate the analysis: in regimes where PLL-based grid-following control is known to lose damping, the DMFD controller maintains stable operation and follows the predicted steady-state characteristics.

Comment
10 pages, 12 figures, 1 table

Closest papers

Nearest neighbours by meaning across the whole index.

Improved Droop Control in DC Microgrids via Voltage-Locked Loop Synchronization

eess.SY ·2026-09-18 ·Ognjen Stanojev, Jovan Krajacic, Enea Bianda, Orcun Karaca, Mario Schweizer
similarity 0.63
Abstract

DC microgrids are low- or medium-voltage networks designed to connect and manage DC-based sources and loads. A key challenge in operating DC microgrids is maintaining the DC voltage within certain predefined limits while ensuring its stability. Droop control, the most common method towards addressing this challenge, enables decentralized voltage control and power sharing, but suffers from poor transient performance, resulting in voltage dips and overshoots in applications with fast varying loads such as AI datacenters. This paper introduces an improved droop control method based on voltage-locked loop synchronization, which ensures DC voltage stabilization with significantly improved transient response and achieves the desired load sharing between the available source converters. The core design principle is reflected in the functional separation of the control scheme into a virtual DC machine (VDCM) that operates as a spinning wheel and a virtual current source connected in parallel. The transient response is provided by the VDCM to damp and stabilize DC bus voltage variations, while the slow droop response is provided by the virtual current source to ensure steady-state power balance. The performance of the proposed method is validated in an experimental microgrid setup.

0.18

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.61
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

PLL-Less Synchronization of Grid-Following Converters Using a Voltage-Driven Frenet Frame

eess.SY ·2026-11-13 ·Jinhui Chen, Huadong Sun, Shiyun Xu, Bing Zhao, Peng Han +1 more
benchmark similarity 0.56
Abstract

In grid-following converters, the synchronization path can transmit voltage disturbances to the current loop under weak or unbalanced grid conditions. This paper develops a Frenet-frame controller that derives its axes from the integral curve of the measured voltage at the point of common coupling. The tangential current governs active power, while the normal and binormal currents govern the transverse components of non-active power. Feedforward terms derived from the output filter model compensate curvature and torsion coupling, yielding identical nominal current dynamics across the axes. The controller operates without a phase-locked loop or sequence extraction. A reduced transverse model accounts for the finite bandwidth of geometric rate reconstruction and predicts a reduction in low-frequency coupling from voltage disturbances to current. Controller hardware-in-the-loop tests using real-time simulation of a three-phase four-wire converter show the shortest settling time after an active power reference step and the smallest peak power deviations during balanced voltage disturbances among the tested controllers. Under single-phase voltage unbalance, the method reduces peak binormal current and maximum phase-current total harmonic distortion relative to both benchmarks. It also settles to the commanded power in a weak-grid connection test where the phase-locked loop benchmark exhibits sustained oscillations.

0.38

Stability Enhancement of Cascaded DC Systems via Source Output-Impedance Reshaping Using Model-Free Control

eess.SY ·2026-10-23 ·Wanrong Li, Shuhan Hu, Hengping Xiong, Runnan Wang, Huawei Yuan +2 more
published similarity 0.56
Abstract · Accepted at the 2026 CPSS & IEEE International Symposium on Energy Storage and Conversion (ISESC)

Cascaded DC systems may become unstable through source-load impedance interactions even when their constituent converters are locally stable. This paper proposes a source-side model-free control (MFC) method that reuses bus-voltage feedback to reshape the source output impedance while preserving nominal reference-to-output dynamics. The controller uses only nominal source-loop information and requires neither a load-converter model nor load-side measurements. A current-controlled buck source supplying a regulated buck-resistor load that exhibits constant-power load (CPL) behaviour at low frequencies is used as the case study. Impedance analysis predicts that the proposed MFC increases the maximum stable load power by approximately 50%, thereby improving the stability margin of the cascaded system. Switched-model simulations confirm preservation of the nominal reference-to-output response and show that the MFC-controlled system remains stable at load levels for which the baseline system becomes unstable.

0.40

Stability of Droop-Controlled Low-Frequency Transmission Lines

eess.SY ·2026-09-01 ·Rafael Castillo-Sierra, Giri Venkataramanan, Dionisio Ramirez
published similarity 0.55
Abstract · 6 pages, 3 figures, 2023 IEEE Energy Conversion Congress and Exposition (ECCE)

Low-Frequency AC (LFAC) transmission systems employing power converters are being considered for a varity of applications. This work studies the small-signal stability of an LFAC transmission line controlled by the Droop Control Strategy. Eigenvalue Analysis is used to determine how the controller droop gains, operating frequency, transmission line parameters, and the operating point affect system stability. The results show that the overall system's dynamic is governed by the sum of the droop gains of the AC/AC converters. Analytical results that give insights on how the different system's parameters affect the critical stability point are presented. The results indicate that system stability is affected by the line's length, the line's R/X ratio, operating frequency and voltage.

0.57

Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC Systems

eess.SY ·2026-11-05 ·Francisco J. Cifuentes Garcia, Thomas Roose, Luis Müller, Jef Beerten
code/data similarity 0.55
Abstract · Under review (10 pages). For the associated packages visit http://github.com/Electa-Git/PowerImpedance.jl and http://github.com/Electa-Git/Z…

The integration of offshore wind farms (OWFs) and the interconnection of different transmission networks are key drivers for multi-terminal DC (MTDC) systems. Bipolar high-voltage direct current (HVDC) employing dedicated metallic return (DMR) are attractive due to their increased availability, which co-exist with monopolar and rigid bipole configurations. While existing works focus on symmetric operation and particular configurations, we present a unified framework for MTDC stability analysis valid for both symmetric and asymmetric conditions. The formulation uses the minimum number of variables without loss of information, and combines the analytical network representation with black-box converter models, thereby enabling sensitivity studies. In addition, a closed-form expression guiding the stability improvement is presented, which requires minimal data exchange between involved parties. The framework is demonstrated on several case studies of increasing complexity, which highlight the importance of considering intra-station converter couplings and possible uncertainty of network parameters.

0.44

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.55
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.54
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32