PLL-Less Synchronization of Grid-Following Converters Using a Voltage-Driven Frenet Frame

Jinhui Chen, Huadong Sun, Shiyun Xu, Bing Zhao, Peng Han, Federico Milano

eess.SY ·submitted 2026-11-13 08:25 UTC · v1
benchmark

Abstract

In grid-following converters, the synchronization path can transmit voltage disturbances to the current loop under weak or unbalanced grid conditions. This paper develops a Frenet-frame controller that derives its axes from the integral curve of the measured voltage at the point of common coupling. The tangential current governs active power, while the normal and binormal currents govern the transverse components of non-active power. Feedforward terms derived from the output filter model compensate curvature and torsion coupling, yielding identical nominal current dynamics across the axes. The controller operates without a phase-locked loop or sequence extraction. A reduced transverse model accounts for the finite bandwidth of geometric rate reconstruction and predicts a reduction in low-frequency coupling from voltage disturbances to current. Controller hardware-in-the-loop tests using real-time simulation of a three-phase four-wire converter show the shortest settling time after an active power reference step and the smallest peak power deviations during balanced voltage disturbances among the tested controllers. Under single-phase voltage unbalance, the method reduces peak binormal current and maximum phase-current total harmonic distortion relative to both benchmarks. It also settles to the commanded power in a weak-grid connection test where the phase-locked loop benchmark exhibits sustained oscillations.

Closest papers

Nearest neighbours by meaning across the whole index.

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.63
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.61
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.57
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

An Energy-Based Framework for Transient Stability of Grid-Forming Converter Networks With Current Limiting

eess.SY ·2026-09-29 ·Wei Zhou, Yunjie Gu
similarity 0.57
Abstract · 10 pages, 6 figures

Existing analyses for the transient stability of grid-forming (GFM) converters under current limiting mainly address single-converter systems, while network-level transient stability analysis remains challenging. This paper develops a network energy construction that incorporates current limiting while retaining a provable dissipation property. This structure enables Lyapunov-based analysis consistent with classical direct method for synchronous-machine based systems, without switching between mode-dependent energy functions. A two-GFM example using a reactive circular current limiter and impedance insertion illustrates the proposed framework. Electromagnetic transient simulations support the theoretical results.

0.25

Grid-Forming AC/DC Converters for Meshed DC Networks via Dual-Measurement Frequency Droop

eess.SY ·2026-10-26 ·Hisham Mahmood, Marcelo A. Elizondo
similarity 0.56
Abstract · 10 pages, 12 figures, 1 table

This paper proposes and analyzes a dual-measurement frequency-droop (DMFD) controller for meshed MVDC networks. Using only two local DC measurements, bus-voltage deviation and a filtered DC-port current or power deviation, the controller enables grid-forming operation at both AC and DC ports across the mesh. Although the DMFD regulates neither the DC voltage nor the DC current directly and acts only on the terminal frequency, it is shown that AC-side synchronization closes an effective DC droop at every synchronized terminal, so that the steady operating point of the mesh exists and is unique. Constant frequency deviations at a terminal and single-terminal islanding enter the same DC equations as equivalent current offsets, with the island frequency fixed by the island power balance, allowing node voltages and branch currents to be obtained from one linear system. The steady-state model yields design-use envelopes to map the droop ratios and the net DC-injection levels into bounds on DC-voltage deviation and terminal currents. A small-signal dynamic model is developed and used to generate eigenvalue loci and damping-ratio charts that guide controller-gain selection. Averaged EMT simulations on a four-terminal ring corroborate the analysis: in regimes where PLL-based grid-following control is known to lose damping, the DMFD controller maintains stable operation and follows the predicted steady-state characteristics.

0.29

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.56
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.56
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Internal-Model-Control-Based Virtual Admittance Emulation for Enhanced Grid-Forming Performance

eess.SY ·2026-09-18 ·Ruzica Cvetanovic, Lazar Stojanovic, Paolo Sbabo, Paolo Mattavelli, Massimo Bongiorno
similarity 0.55
Abstract

The large-scale integration of renewable energy into electrical power systems places a growing reliance on grid-forming converters (GFMs) to overcome critical stability and control hurdles. By emulating a slowly varying voltage source behind a tunable resistive?inductive impedance, GFMs enable precise setpoint tracking and vital grid support. In this regard, virtual admittance (VA)-based inner-loop control provides exceptional flexibility in shaping the converter's small-signal immittance at connection terminals, allowing for advanced GFM functionalities. This article addresses a novel internal-model-control-based VA approach, which inherently accounts for the effects of the inner current-control loop and the voltage feedforward. Unlike the state-of-the-art VA control, the proposed VA control ensures that, at frequencies outside the influence of outer loops, the converter's terminal admittance closely matches the target admittance, which is shown to be relevant for stability. It is revealed how, with the state-of-the art VA control, a small-signal instability in the harmonic range may arise if a low-pass filter with a high cut-off frequency is used for the voltage feedforward. However, the proposed VA control ensures stable operation regardless of this cut-off frequency. The methodology is experimentally validated using a laboratory prototype that features three-phase voltage-source converters.

0.21