Dynamic Operational Reserve Margin Assessment from Risk-Constrained Unit Commitment States

Pratishtha Shukla, Shaked Regev, Evan J. R. Brody, Charles Foltz, Teja Kuruganti

eess.SY stat.AP ·submitted 2026-09-02 18:38 UTC · v1

Abstract

We propose Dynamic Reserve Margin (DRM) as a time-varying operational adequacy metric derived from risk-constrained unit commitment (RCUC) states. DRM quantifies reserve adequacy using the additional generation capacity that committed generators can provide within a 5-minute response window relative to uncertainty and contingency reserve requirements. We introduce a complementary Reserve Risk Envelope (RRE) metric to quantify operational reserve headroom in directly interpretable MW terms. A low-margin duration metric is further developed to quantify the persistence of reserve stress over an operating horizon. We use an IEEE 14-bus example to illustrate these concepts, followed by large-scale RCUC case studies under multiple operating scenarios. Results demonstrate that reserve requirements and ramp-accessible reserve capability can vary substantially across operating conditions, and that commitment decisions adapt to maintain reserve adequacy under changing system conditions. The proposed DRM and RRE metrics provide an interpretable operational characterization of reserve adequacy, reveal reserve accessibility and stress persistence that are not captured by conventional reserve margin metrics.

Closest papers

Nearest neighbours by meaning across the whole index.

Adaptive Calibration of Day-Ahead Flexibility Reserve Requirements Under Distribution Shift

eess.SY ·2026-10-12 ·Napoleon Costilla-Enriquez, Yang Weng, Miguel A. Ortega-Vazquez
theory similarity 0.63
Abstract

The increasing integration of variable renewable generation introduces weather-driven variability and uncertainty into power-system operations. System operators manage the resulting deviations between day-ahead forecasts and real-time net load by scheduling upward and downward flexibility reserves. These requirements have traditionally been set using simple deterministic rules. Newer data-driven methods tailor reserves to forecasts and operating conditions. However, their reliability may deteriorate when conditions depart from the historical data. We address this limitation with a sequential framework that updates day-ahead reserve requirements as operating outcomes become available. Within this framework, Adaptive Conformal Inference targets the frequency of insufficient reserve, whereas Rolling Risk Control targets expected uncovered deviation, the mean residual beyond the scheduled reserve. We prove finite-horizon bounds on realized miscoverage and capped uncovered-deviation loss. We test the framework on real ERCOT data in a chronological deployment simulation that respects operational timing: outcomes from one day first affect the reserve schedule two days later. Training and validation use 2022--2023 data; the uninterrupted test covers 2024--2025. Coverage calibration achieves approximately 90% coverage, with upward and downward miscoverage near 5%. Risk calibration brings expected uncovered deviations close to their budgets while using 5.3% less reserve than the uncalibrated requirements. The framework thus produces adaptive reserve requirements that provably control the selected reliability metrics over finite horizons without assuming stationarity or exchangeability.

0.22

State-of-Charge Targets for Storage Participation in Two-Settlement Markets: Reliability, Price, and Compensation Impacts

eess.SY ·2026-11-13 ·Yichen Li, Alexandre Moreira, Ruiwei Jiang, Miguel Heleno, Julie Mulvaney-Kemp
hot direction similarity 0.59
Abstract

As energy storage assumes a larger role in electricity systems, market operation must coordinate its use across time to support reliability during periods of system stress. Minimum state-of-charge (SOC) targets provide a means of preserving energy for these periods, but their design shapes reliability, operating efficiency, and storage compensation. This paper evaluates alternative SOC target designs in a California-based day-ahead and real-time electricity market model. The comparison examines targets based on day-ahead schedules or rolling centralized dispatch, enforced at the individual-resource or system level, across seasons, stress conditions, and participant information settings. The results show that retaining more energy does not necessarily reduce load shedding: targets that restrict discharge can limit storage support during shortages. Under critical summer conditions, individual targets derived from rolling centralized dispatch reduce weekly load shedding by approximately 83--84\% relative to operation without targets. Lower RT clearing costs and average prices can coexist with higher storage compensation, reflecting the role of day-ahead positions and real-time deviations in determining settlement outcomes. These findings highlight the importance of coordinating energy retention with timely discharge and network deliverability when designing SOC requirements for storage participation in electricity markets.

0.25

Duration-Aware Ramp Adequacy Screening

eess.SY ·2026-09-30 ·Qian Zhang, Aidan Looney, Chao Tian, Xu Andy Sun, Le Xie
benchmark similarity 0.59
Abstract

Ramp products are widely used in regional electricity markets to procure intertemporal flexibility in anticipation of net demand changes. However, the design of such ramp products often lacks a clear specification of ramping duration, potentially leading to infeasible dispatch solutions. This paper develops a duration-aware ramp adequacy screening method that evaluates whether the currently committed and dispatched fleet can meet the anticipated net-demand ramp requirement across different durations. A negative ramp adequacy margin identifies an insufficient-duration set in which the fleet lacks adequate ramp capability. Evaluating this margin across duration supports product-duration selection, while tracking it over time provides a metric for assessing ramp adequacy under different products and dispatch policies. We further formulate rolling-window ramp-reserve procurement with horizon-dependent forecast uncertainty and show that a product can affect ramp capability beyond its designated duration through changes in dispatch positioning. Building on this framework, we develop a forecast-free ramp-reserve scarcity dispatch policy that prioritizes resources according to their remaining ramp-up durations and, in the transmission-unconstrained setting, achieves the same minimum operational security loss as a perfect-foresight benchmark. Studies on a 10-generator system and a 2751-bus synthetic Texas grid demonstrate the value of the proposed framework for early detection of ramp scarcity, product design and evaluation, and screening-guided emergency dispatch.

0.20

Assessing Data Center Hosting Capacity Considering Electromagnetic Transient Dynamics

eess.SY ·2026-11-11 ·Fan Jiang, Xingpeng Li
hot direction similarity 0.57
Abstract

Hosting capacity is commonly assessed with steady-state optimization, which leaves the dynamic response of the data center and the grid at the resulting operating point untested. This paper assesses candidate data center capacities by coupling a unit commitment (UC) model with electromagnetic transient (EMT) simulation. During the capacity search, the UC model determines the economic dispatch for each tested data center capacity, and the resulting operating points are tested for settling with the generators committed online by the UC model and after a selected synchronous generator outage. Three nested capacities are obtained: the optimization-based steady-state capacity, the dynamic pre-outage capacity, and the post-outage dynamic capacity, each bounded by the previous one. On a test system with a detailed data center model, both dynamic capacities fall well below the optimization capacity, and the ranking of connection locations changes with the assessment stage and with the outage. In the most severe outage case at each candidate bus, the capacity is about 30% below the steady-state capacity. Thus, the dynamic response of the data center and the grid should be part of the hosting capacity assessment, and the comparison of connection locations should be made on the post-outage dynamic capacity.

0.34

Readiness-Constrained Pre-Islanding Dispatch for Military Microgrids

eess.SY math.OC ·2026-10-29 ·Aidan Looney, Annie Weathers, Nicholas Judson
similarity 0.56
Abstract · 32 pages, 5 figures, 3 tables, submitted to Military Operations Research

Military installation energy readiness depends on having sufficient resources to sustain mission-critical loads throughout a prolonged utility outage. This paper develops a method to help operators manage energy resources during normal grid-connected operation while preserving islanded readiness. A robust viability kernel identifies combinations of battery energy, fuel, and load-shifting capability sufficient to sustain critical load under uncertain demand and photovoltaic generation. A probability bound translates stochastic generator start failures and recovery into a deterministic generator count selected to meet a specified availability requirement at islanding. Case studies for a fourteen-day islanding requirement at 0.999 islanding-entry availability show that advance warning of an outage can be used to prepare resources to meet a higher readiness requirement before islanding begins. The case studies further demonstrate that economic-only operation and the evaluated fixed battery reserve policy can fail to sustain critical load for the required duration, whereas enforcing the resource-dependent requirement preserves readiness at a modest increase in modeled grid-connected operating cost. These results demonstrate how active resource management can preserve long-duration energy readiness. The framework also helps commanders understand how readiness changes with operating conditions, even when the available resources remain the same.

0.32

Feasibility-Aware Learning for Network-Constrained Unit Commitment

eess.SY ·2026-11-08 ·Hien Thanh Doan, Yeji Lim, Hongseok Kim
similarity 0.56
Abstract

Learning-based approaches to network-constrained unit commitment (NCUC) usually still rely on an optimization solver to repair or complete their predictions, which limits the speedup they can deliver. This paper proposes FALCON-UC, a feasibility-aware graph learning framework that predicts commitment and dispatch jointly and produces final schedules without solving a mixed-integer program at inference time. It combines an LSTM--GraphSAGE predictor over a fully connected generator graph, a differentiable correction that embeds commitment-dependent dispatch bounds, power balance, and PTDF-based branch flows in training, and deterministic commitment, dispatch, and ramp-coupled reserve repairs at inference. On the 2383-bus system, FALCON-UC achieves $99.09\%$ commitment accuracy and a $0.4350\%$ mean absolute cost gap with all evaluated constraints within tolerance at $0.0562$ s per instance, a $2.27\times10^{3}$ speedup over the solver. MTLR R-SCUC-FL is slightly more accurate but still needs an optimization solver to complete each schedule, which takes $262.2$ s per instance, $4.67\times10^{3}$ times the FALCON-UC runtime. A label-only baseline without repair violates the balance and branch limits on every 2383-bus test instance, and FALCON-UC also meets all evaluated constraint tolerances on a 1354-bus system.

0.26

Impact of Wind-Solar-Battery Growth on Electricity Prices: Reserve Scarcity and Transmission Congestion

eess.SY ·2026-11-14 ·Haoxiang Wan, Ivan Castillo, Xingpeng Li
similarity 0.56
Abstract · 7 pages, 3 figures, 2 tables. Submitted to IEEE GECA 2027

This paper asks whether sequential wind, solar, and battery storage additions that eliminate unserved energy also remove modeled reserve scarcity and transmission congestion. Thirty-one cumulative portfolio states are evaluated on a modified IEEE 24-bus system for a constructed stressed day using a 24-hour day-ahead unit commitment model with network constraints, co-optimized energy and upward reserve, chronological battery storage, and an approximation of the Electric Reliability Council of Texas operating reserve demand curve. The thermal baseline has 106 MWh of unserved energy, whereas 450 MW of wind is sufficient to serve all demand. However, with 1,500 MW of wind, the hourly modeled reserve scarcity price still reaches \$5,000/MWh because wind output declines after the system peak. Adding 1,800 MW of solar reduces the load weighted daily average modeled reserve scarcity price from \$1,136.2/MWh to \$101.2/MWh and confines modeled reserve scarcity to three evening hours. Adding 250 MW/1,000 MWh of battery storage further lowers the average to \$4.3/MWh and reduces wind curtailment from 631 MWh to 306 MWh. Transmission congestion nevertheless remains: all residual wind curtailment occurs at bus 21, wind capture prices at buses 21 and 23 differ by \$31.8/MWh, and identical battery storage plants yield normalized net energy market revenues of \$201/(MW$\cdot$day) and \$121/(MW$\cdot$day) at buses 19 and 21, respectively. These results show that unserved energy, modeled reserve scarcity, and locational congestion effects measure distinct operating conditions and should be evaluated separately but interpreted together.

0.35

ePACT: Energy-Performance-Aware Commitment Tracking for LLM Serving

cs.DC ·2026-10-01 ·You Peng, Youhe Jiang, Chen Wang, Binhang Yuan
similarity 0.55
Abstract

Reducing LLM serving energy does not by itself guarantee lower deployment cost when electricity procurement exposes operators to unfavorable deviations from preset commitments. We study hourly commitments with positive, potentially asymmetric costs for overuse and underuse, and formulate energy-Performance-Aware Commitment Tracking: minimize deviation costs subject to request-level service requirements. We implement ePACT, a two-level controller that adjusts serving capacity and GPU clocks as requests arrive. A global planner updates interval energy targets from measured consumption and the remaining hourly commitment. A local decision maker predicts candidate configurations' energy and completion times, checks predicted deadline misses, and selects among admitted configurations by asymmetric target-deviation cost, with a service-first fallback. Coarse-to-fine action search runs asynchronously with serving. We evaluate ePACT through single-hour comparisons, controller ablations, and full-day trace simulations for H20 and H200 GPU pools. In the 24-hour simulations, ePACT reduces the asymmetric deviation cost by $73.8\%$ and $75.7\%$ relative to vLLM while retaining near-vLLM SLO attainment. Mean absolute hourly deviations are $2.16\%$ and $2.31\%$, respectively.

0.17