CS Paper Radar

Embedding Single-Phase Grid-Forming Inverters in Three-Phase Unbalanced Power Flow

Kamini Shahare, Fei Feng, Peng Zhang

cs.ET ·submitted 2026-09-02 20:37 UTC · v1

Abstract

This letter introduces Grid-Forming Three-Phase Power Flow (GFM-3PF), an augmented Newton power flow framework for modeling single-phase grid-forming inverters (GFMs) in three-phase unbalanced networks. The contributions of this work are threefold: 1) developing a two-stage solution strategy based on positive-sequence initialization followed by three-phase phase-domain lifting for robust large-scale computation; 2) incorporating phase-domain unbalanced network modeling with controlled mutual coupling together with phase-dependent, frequency-sensitive load representation; and 3) embedding a single-phase GFM bus model directly into the three-phase unbalanced Newton power flow equations through a common droop-governed frequency state. GFM-3PF is validated on 3-bus, 33-bus, and 118-bus test systems, demonstrating its accuracy, robustness, and scalability.

Closest papers

Nearest neighbours by meaning across the whole index.

QSVT-Based Three-Phase Unbalanced Power Flow

cs.ET ·2026-09-02 ·Kamini Shahare, Peng Zhang
benchmarkunusual similarity 0.69
Abstract

This letter introduces QSVT-3PF, a quantum singular value transformation (QSVT) based solver for three-phase unbalanced power flow with embedded single-phase grid-forming inverter (GFM) operation. The contributions are threefold: 1) reformulating the Newton correction as a QSVT-compatible inverse problem using a normalized block-encoded phase-domain Jacobian; 2) introducing a regularized singular-value filter to improve robustness under ill-conditioned and stressed operating conditions; and 3) validating the proposed solver on an IEEE 5-bus system and the IEEE 123-node test feeder with single-phase GFM integration. Test results show that QSVT-3PF matches the classical Newton benchmark in residual convergence, voltage profile, and final operating point, demonstrating the feasibility of QSVT-3 for large, unbalanced distribution systems.

0.34

Blackbox Small-Signal Modeling of Grid-Connected Inverters in Asymmetrical Power Grids

eess.SY ·2026-09-01 ·Airan Frances, Dionisio Ramirez, Javier Uceda
top venuehighly cited similarity 0.61
Abstract · 11 pages, 14 figures, IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 10, OCTOBER 2023

Power electronic converters are envisaged to be key enablers of modern electric power distribution systems. Grid-connected three-phase inverters are widely used in Smart Grids and microgrids, but also in standard grids. They provide controllability and dynamic decoupling capabilities, which are fundamental in the integration of renewable sources and storage systems and in specialized applications such as FACTS. Nevertheless, power electronics-based systems can exhibit dynamic interactions, which may lead to power quality issues. Although the electrical model of each element of these systems is important for their system-level analysis, they are rarely available. Blackbox modeling strategies are useful for obtaining behavioral models of commercial electronic converters. Most blackbox modeling strategies are focused on dc-dc electronic converters; however, some works have extended these concepts to three-phase converters by means of the dq framework, under the assumption of symmetrical and balanced conditions. This work proposes a new structure in the sequence domain to represent the dynamic behavior of grid-connected commercial converters in asymmetrical conditions. Experimental tests have been performed on a three-phase inverter to identify its blackbox model and its performance has been validated during an asymmetric voltage sag.

0.82

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.61
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers

eess.SY ·2026-11-02 ·Muhammad Hamza Ali, Amritanshu Pandey
similarity 0.56
Abstract

This document presents dynamic models of a transmission network and average models of power-electronic devices and loads in the synchronous $dq$ frame. We model the network in the positive sequence and its synchronous generators with the classical swing equation and a first-order turbine governor. The power-electronic models cover grid-following inverters and AI data centers. Each inverter has a phase-locked loop, a power controller, and a current controller. Each data center connects to the grid through two step-down transformers. Its low-voltage bus feeds an IT load, an induction-motor cooling load, and a constant-impedance load. A double-conversion uninterruptible power supply (UPS) serves the IT load. We model its rectifier, grid-forming output inverter, battery, and bidirectional DC-DC converter. A measured GPU power trace drives the IT demand. We replace every non-smooth operation with a smooth surrogate. This keeps the discretized model continuously differentiable for the nonlinear solver. We also show how we initialize each model at its power-flow operating point.

0.25

A unified power-grid representation for reuse across network structures and computational tasks

eess.SY ·2026-09-07 ·Yanhao Huang, Changqing Liu, Zichang Wang, Qianhong Wu
similarity 0.56
Abstract

Data-driven power-system models are typically developed for specific grids and computational tasks, but their performance can deteriorate markedly or even fail when network structures or analytical objectives change. This paper develops a unified grid representation that separates physical-grid description from downstream computation. A self-supervised encoder represents each grid as a variable number of fixed-dimensional node, branch and global vectors under a common latent description. Although pretrained only on systems with at most 270 buses, the frozen encoder transfers without adaptation to a 70,000-bus network, more than 250 times larger in bus count, while preserving 0.7919 bus-correspondence accuracy. The same representation supports four independently trained downstream tasks: power-flow calculation, reactive-power adjustment, operating-condition generation and transient-stability assessment. On the previously unseen 70,000-bus grid, power-flow calculation achieves mean errors of 0.108$^{\circ}$ in phase angle and 3.8$\times$10\textsuperscript{-6} p.u. in voltage magnitude. Reactive-power adjustment achieved a 75\% PSASP-verified correction rate on the previously unseen 70,000-bus grid, while operating-condition generation delivered at least one PSASP-verified feasible state for 82.2\% of requests on previously unseen 400--1,000-bus grid families. For transient-stability assessment, the frozen encoder achieves accuracy within 0.8 percentage points of full encoder adaptation under matched training conditions. These results demonstrate that a unified power-grid representation can be learned once and reused unchanged across structurally different power systems and heterogeneous computational tasks.

0.47

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.56
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.56
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.28

Unifying Power Flow and Electromagnetic Transient Modeling

eess.SY ·2026-09-08 ·Tina Gao, Aayushya Agarwala, Timothy McNamara, Lawrence Pileggi
similarity 0.55
Abstract

Grid tools are separated by timescales: steady-state analysis is performed by power flow (PF), whereas the fastest dynamics are captured by electromagnetic transient (EMT) simulation. Although operating at varying timescales, different tools should produce consistent results when analyzing the same grid conditions. However, the PF steady-state solution does not match the time-to-infinity EMT response. This mismatch exists because simplified device models in PF are inconsistent with the "ground truth" EMT models derived from first principles. As inverter-based resources (IBRs) and data centers strip away inertia and operating reserves, approximations used in PF risk grid security by missing violations. To address this, we introduce a steady-state framework that uses full-physics EMT models for high-fidelity steady-state grid analysis. The challenge lies in systematically formulating algebraic frequency-domain representations of dynamic power devices that are naturally described in state-space form. Our tool, SALT (Steady-state After Last Transients), constructs steady-state representations that exactly capture grid device physics when embedded into transmission networks. The approach exploits the structural properties of power device models and the single-harmonic, balanced nature of the transmission system. Results demonstrate SALT achieves EMT steady-state accuracy while delivering a 1x10^6 times speedup. We demonstrate that SALT can capture security threats in contingency scenarios without exception --- whereas PF-based analyses reported 75% fewer rated line violations, 18% fewer Q-limit violations, and 7% fewer voltage violations.

0.20