Data-Driven Generator Transient Prediction for Digital Twin Decision Support

Emad Sadeghi, Emerson Miller, Kerry Sado, Adel Nasiri

eess.SY eess.SP ·submitted 2026-09-04 17:02 UTC · v1

Abstract

This paper develops a calibrated transient forecasting surrogate model for generator digital twin (DT) decision support that evaluates planned active- and reactive power load commands before they are applied. The proposed event-conditioned Hankel Dynamic Mode Decomposition with Control (Hankel-DMDc) model combines delay-coordinate lifting, command-event memory features, and an event-weighted Hankel basis so that sparse load-transition dynamics influence the reduced representation and fitted dynamics. This design targets intervals where voltage/frequency deviations and recovery behavior determine whether a candidate load command keeps the system within acceptable limits. To provide operator-facing confidence information, a split-conformal calibration layer is applied to the frozen surrogate model to form event-conditioned joint prediction bands for voltage and frequency. The experimental results show event-window root-mean-square errors of 1.058 V and 0.155 Hz. For a nominal 90% target, the bands attain 90.17% pointwise joint voltage-frequency coverage, with mean band widths of 3.55 V and 0.566 Hz. A 50-s open-loop rollout is computed in 181 ms on a single CPU core, approximately 280 times faster than real time, with forecast accuracy evaluated over horizons up to 5 s. These results demonstrate a computationally efficient advisory framework for generator DTs that combines transient prediction with calibrated uncertainty.

Comment
In submission for possible publication in IEEE Transactions on Power Systems

Closest papers

Nearest neighbours by meaning across the whole index.

Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data Center

eess.SY ·2026-11-19 ·Jesus D. Vasquez-Plaza, Sunil Subedi, Jin Dong, Joao Pereira Pinto
similarity 0.54
Abstract · Submitted to IEEE PES General Meeting 2027

Data centers supplied through centralized uninterruptible power supplies (UPSs) are converter-dominated loads whose grid response reflects IT demand, power-conversion controls, energy storage, cooling, and site-support dynamics. This paper develops and electrically realizes a causal multi-output surrogate for a nominal 1-MW, 0.48-kV simulated data center. Four physics-informed terminal features-normalized IT demand, positive-sequence voltage deviation, voltage-unbalance ratio, and frequency deviation-are used to predict active and reactive power at both the point of common coupling (PCC) and UPS output. Six causal surrogate families are evaluated using separate training, validation, and held-out trajectories. A ridge-regularized low-order nonlinear autoregressive model with exogenous inputs (NARX) achieves the lowest validation and test errors, with mean four-output errors of 0.1959\% and 0.1441\% on a 1-MVA base, respectively. The selected surrogate is then coupled to a three-phase electrical interface in MATLAB/Simulink, where predicted PCC active power controls a variable resistive load and predicted reactive power is realized through controlled current sources synchronized to the PCC voltage. Across two 41-s AI workload profiles, including an additional pipeline parallelism trajectory, the electrical realization tracks the NARX commands with active- and reactive-power RMSEs of 0.604 kW and 0.353 kVAR for Evaluation Profile A and 1.539 kW and 0.442 kVAR for Evaluation Profile B, respectively. The results demonstrate a compact terminal surrogate that can reproduce both predicted power trajectories and their corresponding three-phase electrical behavior under measured PCC excitation.

0.17

A Hybrid Systems Approach to Parameterizing the PERC1 Model for Data Centers Using Synchrophasor Measurements

eess.SY ·2026-11-16 ·Bukunmi Gabriel Odunlami, Marcos Netto
similarity 0.53
Abstract

The Power Electronic Reconnecting and Ceasing (PERC1) load model represents the timed ceasing and reconnection of large power-electronic loads, including data centers. Voltage thresholds and timers govern its response, with a ramp on reconnection, making it a hybrid dynamical system. This paper formulates PERC1 as a hybrid automaton and uses that structure to identify its parameters from synchrophasor records of grid disturbances. We propose a four-stage identification procedure: mode-sequence identification, estimation of logic parameters from event-time constraints, and joint Gauss-Newton refinement using hybrid trajectory sensitivities and saltation matrices. The resulting salted Fisher information is then used to analyze parameter identifiability. Two structural results are established. The detection and actuation delays are identifiable only through their sum unless a second dip interrupts the reconnection ramp, and a single disturbance leaves one unidentifiable direction in each threshold-delay pair, which two disturbances with different voltage slopes resolve. A case study using synthetic 60 frames/s synchrophasor records demonstrates recovery of the ceasing and reconnection dynamics and identifies poorly observable parameters.

0.27

Equivalent Modeling of Load-Side Systems With Distributed Renewable Generation Considering Fault Responses and Nodal Voltage Coherence

eess.SY ·2026-09-21 ·Yuqi Cao, Chen Shen, Shaowei Huang, Ying Chen, Hongyi Zhu
similarity 0.53
Abstract · Submitted to IEEE Transactions on Power Systems

Operating conditions and fault severity change both the initial states and control modes of active distribution networks. Direct capacity aggregation can therefore lose the power responses required for transmission-system dynamic analysis. This paper develops a procedure for generating low-order physical electromagnetic transient equivalents from a small set of representative operating conditions. Device power, ride-through states, load mechanical states, and local sequence voltages are combined with electrical distance to form response families. Response reconstruction and terminal simulation errors determine the retained architecture, after which bounded sensitivity calculations determine effective dynamic coefficients. The architecture and coefficients are then fixed. For a new operating condition, capacity and power balances, voltage-dependent load relations, and an initialization correction generate the model parameters from static inputs and power-flow results. A representative severe fault establishes a template for each fault type, which is reused across fault depths. Aggregation and switching-time bounds explain the roles of voltage coherence and state separation. Comparisons with direct aggregation show improved terminal responses across operating conditions and several fault types, with the largest gains under severe unbalanced faults. The method provides a reusable physical equivalent for operating-condition studies and fault-depth screening.

0.17

Safety Screening for Voltage Control in Active Distribution Grids via Distributionally Robust Conformal Screening

eess.SY cs.AIcs.LG ·2026-08-31 ·Sarra Bouchkati, Petros Ellinas, Adriana Geisler, Steffen Kortmann, Johanna Vorwerk +2 more
similarity 0.52
Abstract · Sarra Bouchkati, Petros Ellinas, and Adriana Geisler contributed equally to this work

Deploying a new control policy for voltage control in active distribution grids requires evidence that physical limits will be satisfied before the policy is tested on the physical grid. This assessment is difficult for two reasons. First, simulations cannot capture every disturbance, modeling error, and device interaction present in the real grid. Second, historical measurements reflect operation under existing control policies, whereas a new policy may drive the grid into different operating conditions. To address these challenges, we propose Distributionally Robust Conformal Safety Screening (DR-CSS), a policy-agnostic framework for pre-deployment, scenario-by-scenario screening of a new control policy using historical data and a nominal simulator. For each new scenario, the simulator predicts a future voltage trajectory for the whole grid; DR-CSS then constructs a conformal safety interval around this prediction using historical simulation-to-reality errors. The interval is further enlarged to account for closed-loop changes induced by the deployment of the new policy and its interactions with the remaining controllers. To the best of our knowledge, DR-CSS is the first framework in power systems to combine historical data from an existing control policy with an imperfect simulator for pre-deployment safety screening of a new policy. Experiments on the IEEE 33-bus and IEEE 141-bus systems evaluate the deployment of learning-based voltage control policies and show that DR-CSS identifies all unsafe test scenarios. To reduce unnecessary warnings on safe scenarios, we adapt the safety intervals to different operating conditions and gradually introduce new policies with recalibration after each stage. These extensions increase the informational value of the safety screening and support safer deployment decisions in active distribution grids.

0.21

A Unified Mamba--MoE Surrogate for Closed-Loop Simulation and Measurement-Window Forecasting of Inverter Transients

cs.LG eess.SY ·2026-08-15 ·Haoguang Wang, Huy Hoang Le, Akhila Kandivalasa, Christian Moya, Marcos Netto +1 more
similarity 0.52
Abstract

This paper proposes a Mamba surrogate model with mixture-of-experts (MoE) routing to represent the transient dynamics of inverter-based resources. A Mamba surrogate model is a predictive machine learning model built on the Mamba architecture. MoE routing uses a router network to assign data-dependent weights to specialized subnetworks (experts). The resulting Mamba--MoE surrogate can perform two tasks: (i) closed-loop simulation and (ii) measurement-window forecasting of inverter transients. A single Mamba backbone with task conditioning and expert routing serves both tasks, replacing two separate specialists. Task-matched objectives fit each prediction form, and an adaptive conformal layer provides prediction intervals for both tasks. For the considered grid-following inverter, the unified surrogate model remains in the same low-error regime as a Mamba specialist pair while using 13% fewer parameters. The prediction intervals achieve 94--96% empirical mean marginal coverage across the two tasks. For transient dynamics---that is, beyond the vicinity of an equilibrium point---our surrogate model with MoE routing yields lower errors across all outputs in both tasks compared to a shared Mamba backbone without expert routing. A controller hardware-in-the-loop simulation validates our results and shows that adapting only the shared output head with limited measured data reduces held-out forecasting error.

0.34

X-OPM: Explainable Automatic Digital On-Chip Power Modeling for Enhanced Robustness

cs.AR cs.AIcs.LG ·2026-10-06 ·Jingbo Jiang, Xizi Chen, Jian Peng, Wei Zhang
similarity 0.52
Abstract

Proactive power management systems reduce processor dynamic power through runtime power prediction and power-aware scheduling. Accurate, stable and low-overhead digital on-chip power meters (OPMs) are crucial for improving the prediction quality. Recent studies have explored various modeling methods, including using linear models, decision trees, and multi-layer perceptrons (MLPs) to construct OPMs. However, most current approaches train models end-to-end without analyzing the physical interpretability of features, affecting their ability to generalize to unseen workloads. Grounded in the design principles of synchronous digital VLSI circuits, X-OPM introduces a robust feature engineering framework that uses tree-based models to capture feature interactions and linear models for prediction. It also incorporates a human-in-the-loop workflow to balance model accuracy against modeling effort. Evaluated on a commercial C906 vector processor, X-OPM consistently achieves $R^2 > 0.93$ across all workloads with sampling window size set below $8$ cycles. In contrast, state-of-the-art methods including APOLLO, COBIT, and standard MLPs fail to generalize across all test cases. Layout with commercial EDA tools shows that X-OPM incurs an area overhead below $0.1\%$, which is on par with lightweight tree-based and linear models, and significantly smaller than MLP-based models.

0.20

Frequency-Calibrated Decision-Focused Learning for BESS Dispatch Under Renewable Uncertainty

eess.SY ·2026-10-30 ·Zihan Meng, Chenxi Hu, Xin Cui, Francis Yunhe Hou
hot direction similarity 0.51
Abstract

Battery energy storage system (BESS) flexibility depends on state of charge and intertemporal operating constraints. Renewable forecast errors of similar magnitudes can lead to different BESS dispatch results. An error may alter early charging or discharging decisions and reduce the flexibility available for subsequent regulation, while another may have little effect on the resulting schedule. To account for these unequal consequences, this paper proposes Frequency-Calibrated Decision-Focused Learning (FC-DFL), which trains renewable predictors using the realized operating costs of their induced BESS schedules. Gaussian smoothing and solver-based zeroth-order estimation provide training feedback without requiring differentiating through the non-differentiable mixed-integer BESS dispatch problem. The same decision feedback is further combined with prediction sensitivity to develop a decision-oriented XAI method that identifies the input features and forecast periods most consequential to BESS operation. Case studies using German wind and solar data show that FC-DFL reduces the integrated absolute frequency-deviation metric by 6.05% and decision regret by 23.92% relative to accuracy-based predict-then-optimize method. The XAI analysis further demonstrates that the identified high-impact forecast periods produce 2.84 times larger average absolute changes in realized operating cost than low-impact periods. These findings highlight the importance of incorporating downstream decision-making outcomes into renewable forecasting and demonstrate the value of FC-DFL in improving BESS regulation and providing operationally meaningful forecast explanations.

0.24

A simulation based dataset of faults and events for machine learning in power systems

eess.SY ·2026-08-20 ·Georg Kordowich, Jonathan Loebel, Julian Oelhaf, Andreas Maier, Siming Bayer +2 more
similarity 0.51
Abstract

The integration of inverter-based renewable energy sources into electric grids challenges conventional power system protection. Machine learning-based solutions can address these challenges by utilizing available data in modern smart grids. However, the lack of open datasets prevents reproducibility and fair comparisons between different approaches and their results, which hinders further progress. Therefore, this paper presents EvEMTBench, a synthetic dataset of faults and events generated using electromagnetic transient simulations. The physical plausibility of the power system simulation is ensured by validating the simulation parameters against established literature and providing comprehensive documentation of the simulation procedure. The dataset is designed for training, fine-tuning, and benchmarking machine learning models by providing synchronized point-on-wave voltage and current measurements at 9600 Hz across a diverse set of topologies and voltage levels. The inclusion of a wide range of fault and operating events allows the utilization of EvEMTBench for different tasks like incipient fault detection, fault localization, or event detection.

0.50