Safety Screening for Voltage Control in Active Distribution Grids via Distributionally Robust Conformal Screening

Sarra Bouchkati, Petros Ellinas, Adriana Geisler, Steffen Kortmann, Johanna Vorwerk, Spyros Chatzivasiliadis, Andreas Ulbig

eess.SY cs.AIcs.LG ·submitted 2026-08-31 14:43 UTC · v1

Abstract

Deploying a new control policy for voltage control in active distribution grids requires evidence that physical limits will be satisfied before the policy is tested on the physical grid. This assessment is difficult for two reasons. First, simulations cannot capture every disturbance, modeling error, and device interaction present in the real grid. Second, historical measurements reflect operation under existing control policies, whereas a new policy may drive the grid into different operating conditions. To address these challenges, we propose Distributionally Robust Conformal Safety Screening (DR-CSS), a policy-agnostic framework for pre-deployment, scenario-by-scenario screening of a new control policy using historical data and a nominal simulator. For each new scenario, the simulator predicts a future voltage trajectory for the whole grid; DR-CSS then constructs a conformal safety interval around this prediction using historical simulation-to-reality errors. The interval is further enlarged to account for closed-loop changes induced by the deployment of the new policy and its interactions with the remaining controllers. To the best of our knowledge, DR-CSS is the first framework in power systems to combine historical data from an existing control policy with an imperfect simulator for pre-deployment safety screening of a new policy. Experiments on the IEEE 33-bus and IEEE 141-bus systems evaluate the deployment of learning-based voltage control policies and show that DR-CSS identifies all unsafe test scenarios. To reduce unnecessary warnings on safe scenarios, we adapt the safety intervals to different operating conditions and gradually introduce new policies with recalibration after each stage. These extensions increase the informational value of the safety screening and support safer deployment decisions in active distribution grids.

Comment
Sarra Bouchkati, Petros Ellinas, and Adriana Geisler contributed equally to this work

Closest papers

Nearest neighbours by meaning across the whole index.

Adaptive Calibration of Day-Ahead Flexibility Reserve Requirements Under Distribution Shift

eess.SY ·2026-10-12 ·Napoleon Costilla-Enriquez, Yang Weng, Miguel A. Ortega-Vazquez
theory similarity 0.62
Abstract

The increasing integration of variable renewable generation introduces weather-driven variability and uncertainty into power-system operations. System operators manage the resulting deviations between day-ahead forecasts and real-time net load by scheduling upward and downward flexibility reserves. These requirements have traditionally been set using simple deterministic rules. Newer data-driven methods tailor reserves to forecasts and operating conditions. However, their reliability may deteriorate when conditions depart from the historical data. We address this limitation with a sequential framework that updates day-ahead reserve requirements as operating outcomes become available. Within this framework, Adaptive Conformal Inference targets the frequency of insufficient reserve, whereas Rolling Risk Control targets expected uncovered deviation, the mean residual beyond the scheduled reserve. We prove finite-horizon bounds on realized miscoverage and capped uncovered-deviation loss. We test the framework on real ERCOT data in a chronological deployment simulation that respects operational timing: outcomes from one day first affect the reserve schedule two days later. Training and validation use 2022--2023 data; the uninterrupted test covers 2024--2025. Coverage calibration achieves approximately 90% coverage, with upward and downward miscoverage near 5%. Risk calibration brings expected uncovered deviations close to their budgets while using 5.3% less reserve than the uncalibrated requirements. The framework thus produces adaptive reserve requirements that provably control the selected reliability metrics over finite horizons without assuming stationarity or exchangeability.

0.22

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.59
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.57
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Optimal Measurement Selection for Certifiable Voltage Monitoring in Power Distribution Systems

eess.SY ·2026-09-23 ·Peng Zhang, Line Roald, Manish K. Singh
similarity 0.57
Abstract · 10 pages, 4 figures, submitted to HICSS'60

Maintaining consumer-end voltages within mandated limits is a central task in operating power distribution systems. Rising penetration of distributed generation, electric vehicles, and flexible loads complicates this task, while a scarcity of real-time measurements leaves distribution networks largely unobservable. Operators commonly monitor a few bellwether meters, which indicate operational health but certify nothing about the unmeasured buses. This work asks how to select measurements that are reported in real time and can certify network-wide voltage-limit compliance. We first illustrate the geometry of the measurement values that certify voltage safety at unmeasured nodes. Building on this geometry, we formulate a bilevel optimization that selects measurements to maximize certification capability, introducing a novel safety-violation metric with favorable monotonicity properties. We derive a strong-duality-based single-level reformulation and two scenario-reduction schemes with quantifiable suboptimality. Numerical tests on the SCE 56-bus system corroborate the superior certification capability and computational efficiency of the proposed approach.

0.27

Critical Weather Scenario Screening Using Weather-to-Voltage (W2V) Predictive Modeling

eess.SY ·2026-08-24 ·Sol Lim, Min-Seung Ko, Hao Zhu
published similarity 0.57
Abstract · 6 pages, 2 figures. Accepted to IEEE SmartGridComm 2026

This paper proposes a critical weather scenario screening framework for identifying weather conditions that can trigger high-voltage (HV) events in the power grid. Unlike conventional weather-aware contingency analysis limited to component-level outage risk, our framework screens weather scenarios as potential drivers of grid-level voltage violations. Given a non-critical weather scenario, we seek the perturbation over the high-dimensional weather space to maximize a pre-defined voltage criticality score, by using a differentiable weather-to-voltage (W2V) predictive model to facilitate the gradient update over a compact latent space. Specifically, a non-negativity constraint is used for achieving physically-consistent perturbations, with another L1-norm based constraint for bounded perturbation. The latter could promote sparse and interpretable perturbations, and this uniform budget also yields a sensitivity-aware vulnerability ranking across different weather scenarios. Numerical experiments on a 6717-bus synthetic Texas system have effectively demonstrated the potential of weather uncertainty in triggering HV events, and this potential cannot be represented by the voltage analysis of individual weather scenarios. Interestingly, the most vulnerable scenarios are characterized by wind-dominated perturbation patterns concentrated in high wind-capacity regions, coinciding with observations from actual power flow data and experiences in real system operations.

0.40

AIDC Microgrid Vulnerability Assessment Under Computing-Power Coordinated Attacks

eess.SY ·2026-08-11 ·Ze Yu, Hongwei Zhen, Chao Shen, Mingyang Sun
similarity 0.56
Abstract

The rapid growth of large language model (LLM) services is expanding AI data centers (AIDCs), increasing electricity demand and associated carbon emissions. Renewable energy integration can mitigate these impacts but also strengthens the coupling between AIDC loads and inverter-interfaced generation, creating cross-domain cyber-physical vulnerabilities. Specifically, adversarial AI requests alter AIDC power demand, whereas inverter control tampering modifies source-side dynamics, and their combined impact on system stability varies with generation forecast and demand response uncertainties. To this end, we propose an uncertainty-aware AIDC microgrid vulnerability assessment framework under computing-power coordinated attacks. First, the framework maps adversarial AI requests to AIDC power variations and represents uncertainties in attack-induced demand responses and photovoltaic (PV) forecasts through confidence-weighted realizations. Then, impedance based stability analysis combines these realizations with bounded inverter parameter tampering to construct attack reachable domains and identify critical attack time windows. Furthermore, a separate criterion identifies fixed coordinated attack vectors that retain destabilizing capability throughout each selected window. Case studies demonstrate that, unlike either attack component applied alone, coordinated attacks within identified critical windows induce sustained inverter frequency oscillations with peak absolute deviations exceeding 20% of nominal frequency, whereas the evaluated out-of-window response remains bounded. The proposed method further identifies critical attack windows and the associated coordinated attack vectors.

0.04

AC-Aware Steady-State Security Region Characterization via Exclusion Refinement

eess.SY ·2026-10-12 ·Zhirou Wang, Zhengshuo Li, Shuo Yang
similarity 0.56
Abstract

As active power dispatch becomes increasingly coupled with reactive power support and voltage security in modern power systems, AC security regions (AC-SRs) under exact steady-state AC power flow (AC-PF) constraints provide valuable insights into admissible operating boundaries and security margins for security assessment. However, the nonconvexity of exact AC-PF constraints makes it difficult to achieve both accuracy and computational efficiency in AC-SR characterization. To this end, this paper proposes an AC-aware iterative exclusion refinement (AC-ITER) approach that refines a given convex-relaxed AC-SR toward the exact AC-SR by progressively constructing and removing convexlocal exclusion subregions around numerically identified insecure points. Boundary-point searches and dual-based local exclusion cuts provide a tractable approximation of relaxation-induced insecure portions. A statistical certification method based on uniform sampling is developed to support high-confidence assessment of residual-region security and guide termination, while an AC-PF security similarity-based acceleration (AC-SSA) approach is introduced to further accelerate the sampling-based search for insecure operating points. Numerical studies on academic test systems and real-world systems demonstrate the characterization accuracy of AC-ITER and the computational efficiency gained through AC-SSA.

0.27

Safety-Critical Control under Uncertainty via Adaptive Conformal Quantile Prediction Intervals

cs.RO ·2026-09-20 ·Hao Zhou, Yanze Zhang, Yiwei Lyu, Wenhao Luo
published similarity 0.56
Abstract · 8 pages, accepted to CDC 2026

Safety-critical control under uncertainty requires uncertainty representations that are both statistically valid (for certifiable performance) and compatible with enforceable safety constraints. However, existing methods often assume particular distributions of uncertainty for provable safety guarantees or establish symmetric and input-agnostic prediction intervals for robust safety, which can lead to misaligned or overly conservative safety constraints in control synthesis. In this paper, we introduce a novel safe control framework with adaptive uncertainty quantification that constructs calibrated and state-dependent prediction intervals to enable high-probability safety guarantees, while improving constrained control performance. The framework leverages adaptive conformal prediction (ACP) and extends it with conformal quantile regression (CQR) to capture distribution-free, asymmetric uncertainty intervals with certifiable probabilistic coverage, and integrates the resulting uncertainty sets into a probabilistic control barrier function formulation to enforce robust safety with reduced conservativeness. This yields uncertainty-aware safe control constraints that can be incorporated within a model predictive control(MPC) framework to provide provably safe behaviors with high probability. Simulation and theoretical results are provided to demonstrate the effectiveness of our approach.

0.28