CS Paper Radar

AC-Aware Steady-State Security Region Characterization via Exclusion Refinement

Zhirou Wang, Zhengshuo Li, Shuo Yang

eess.SY ·submitted 2026-10-12 02:25 UTC · v1

Abstract

As active power dispatch becomes increasingly coupled with reactive power support and voltage security in modern power systems, AC security regions (AC-SRs) under exact steady-state AC power flow (AC-PF) constraints provide valuable insights into admissible operating boundaries and security margins for security assessment. However, the nonconvexity of exact AC-PF constraints makes it difficult to achieve both accuracy and computational efficiency in AC-SR characterization. To this end, this paper proposes an AC-aware iterative exclusion refinement (AC-ITER) approach that refines a given convex-relaxed AC-SR toward the exact AC-SR by progressively constructing and removing convexlocal exclusion subregions around numerically identified insecure points. Boundary-point searches and dual-based local exclusion cuts provide a tractable approximation of relaxation-induced insecure portions. A statistical certification method based on uniform sampling is developed to support high-confidence assessment of residual-region security and guide termination, while an AC-PF security similarity-based acceleration (AC-SSA) approach is introduced to further accelerate the sampling-based search for insecure operating points. Numerical studies on academic test systems and real-world systems demonstrate the characterization accuracy of AC-ITER and the computational efficiency gained through AC-SSA.

Closest papers

Nearest neighbours by meaning across the whole index.

Severity-Aware Minimum Security Sets for Accelerated Preventive SCOPF Using Machine Learning

eess.SY ·2026-10-14 ·Mohammad Iman Alizadeh, Saeed Zeynali, Salah Ghamizi, Sylvain Kubler
similarity 0.60
Abstract

This paper proposes a severity-aware machine learning framework for reducing the computational burden of preventive AC security-constrained optimal power flow (PSCOPF). The central idea is to identify a compact minimum security set (MSS) containing only the non-dominated contingencies and associated post-contingency constraints that materially influence the preventive operating point while satisfying a prescribed severity tolerance. An offline procedure combines AC security assessment, severity-based ranking, non-dominated screening, and iterative reduced PSCOPF. After each reduced PSCOPF solution, exhaustive security assessment over all credible contingencies identifies additional contingency--constraint pairs whose residual severity exceeds the specified threshold. Severity is characterized using the normalized number, accumulated magnitude, maximum magnitude, and average magnitude of post-contingency violations. The resulting operating-point-dependent MSSs are used as labels for a supervised multi-label learning model that predicts the security elements required to construct the reduced PSCOPF directly from the pre-contingency state. The proposed framework therefore focuses the optimization on the contingencies and constraints that affect preventive control decisions, reducing problem size and computation time while explicitly controlling residual post-contingency severity. Results on the IEEE 60-bus and 118-bus systems, the latter having an approximately seven-times-larger PSCOPF formulation, demonstrate substantial computational reductions with limited impact on the preventive operating solution.

0.22

Hierarchical Agglomerative Clustering for Efficient Annual Voltage Security Assessment in Very-High RES Penetrated Power Systems

eess.SY ·2026-08-28 ·Rock Agon, Robin Preece, Jovica V. Milanovic
similarity 0.59
Abstract · In preparation for submission to IEEE

Voltage security assessment in power systems with high renewable energy source (RES) penetration requires analyzing many operating conditions to capture variability and uncertainty, but simulating a full year of operating points is computationally costly - motivating the selection of representative operating points (ROPs). Most existing methods cluster demand and generation profiles, but similarity in these profiles does not guarantee similarity in voltage behavior, since reactive power limits, voltage-control actions, and nonlinear network interactions shape voltage response in ways that cannot be inferred from power profile patterns. This paper proposes an unsupervised learning framework that selects ROPs based on the system's actual voltage response: each operating point is represented by system-wide voltage-risk indices from AC power-flow solutions, Principal Component Analysis reduces dimensionality, and Hierarchical Agglomerative Clustering with Ward linkage identifies representative voltage regimes. A comprehensive set of evaluation criteria then measures how well the selected ROPs reproduce the full year's voltage-security characteristics under normal and contingency conditions. On the IEEE Voltage Test System under very high RES penetration, the framework reduces the annual operating point set by 99.66 percent while reproducing full-year voltage behavior with 98.3 percent reconstruction accuracy in steady state and 93.4 percent in post-contingency response, outperforming existing injection-space clustering and heuristic sampling.

0.30

Quantifying the Cost of Restoring AC Feasibility for Approximate Optimal Power Flow Solutions

eess.SY math.OC ·2026-11-11 ·Sanjay Johnson, Sungho Shin
theory similarity 0.59
Abstract · 5 pages, 4 figures, submitted to 2027 IEEE Power & Energy Society General Meeting

Power system operations rely on approximate solutions of the AC optimal power flow problem, most notably the DC optimal power flow used in security-constrained unit commitment and economic dispatch, while convex relaxations, machine learning surrogates, and other approximations are studied extensively in the academic literature. Because these approximations neglect or relax parts of the AC power flow equations, their solutions must be adjusted before dispatch; for example, the DC optimal power flow, which neglects transmission losses, reactive power, and voltage magnitude variations, is known to produce solutions that are always infeasible. The cost of this adjustment is not adequately understood. This paper proposes a method that quantifies, for any approximate solution, the minimum cost of the adjustments that restore AC feasibility, which is a lower bound on the cost of the heuristic adjustments used in practice. We apply it to the DC optimal power flow, the second-order cone and quadratic convex relaxations, and the AC optimal power flow solved to a loose relative tolerance of $10^{-4}$ instead of $10^{-8}$. Relative to the AC optimal power flow solution obtained from a local nonlinear optimization solver, and even with the minimum adjustment, the DC optimal power flow requires adjusting, on average, generators that account for 15.6% of total generation capacity and incurs a 1.10% cost increase; the convex relaxations require more adjustment (17.2% and 16.9%) but smaller cost increases (0.68% and 0.78%); and the loose-tolerance AC optimal power flow requires 6.1% and incurs 0.42%. These results indicate significant value in operating markets directly on the AC optimal power flow, which avoids the distortion of the dispatch and prices caused by heuristic feasibility restoration.

0.35

Certified Safety Radii in Forecast-Error Space for Wasserstein Distributionally Robust Small Signal Stability-Constrained AC Optimal Power Flow via Lifted Spectrahedral Containment

cs.LG ·2026-08-31 ·Ziqi Zhang, Xi Chen
similarity 0.58
Abstract

Directly robustifying small-signal stability in AC optimal power flow is challenging since the stability boundary in the original uncertainty space is implicit, highly nonconvex, and changes with the operating decision. This paper exploits an alternative geometry. For a fixed model-specific stability certificate admitting suitable physical lifts, the small-signal stability requirement becomes an affine positive semidefinite constraint in the lifted variables, thereby defining a convex certified safe region. Instead of approximating the nonlinear instability boundary itself, we optimize a sample-wise safe radius in the original uncertainty space and certify, in the lifted space, that the entire power-flow image of the corresponding uncertainty ball is contained in the convex stability region. To this end, a componentwise Perron certificate guarantees existence, uniqueness, and Jacobian regularity of the target AC power-flow branch throughout each ball. An adjoint elimination then provides an exact affine-quadratic representation of the stability-relevant quantities, while rigorous matrix remainder bounds convert their nonlinear variation into finite robust PSD constraints. The resulting radii are certified lower bounds on the distances from empirical samples to failure and can therefore be coupled directly to the distance-based reformulation of a Wasserstein distributionally robust chance constraint, without directly approximating the instability boundary. Numerical studies demonstrate the effectiveness of the proposed framework.

0.26

Scalable Voltage-Stability Dataset Generation Via Boundary-Proximity Indicators Clustering

eess.SY ·2026-08-28 ·Rock Agon, Robin Preece, Jovica V. Milanović
similarity 0.57
Abstract · Submitted to MedPower Conference 2026

This paper proposes a scalable framework for voltage-stability dataset generation. Voltage-stability-constrained planning increasingly relies on machine-learning surrogates but training them requires large datasets labelled by continuation power flow (CPF) results, which is computationally costly. To address this, this paper proposes a framework that uses hierarchical clustering on boundary-proximity indicators to reduce the number of required CPF evaluations. The proposed approach combines (i) uniform sampling of feasible operating space using Hit-and-Run Markov Chain Monte Carlo, (ii) structured stress directions via maximin Latin hypercube sampling (LHS), (iii) sensitivity-guided perturbations to target weak buses, and (iv) clustering-based representative CPF labelling that reconstructs the voltage stability margins of unlabelled operating points from representative cluster medoids. Results on the IEEE 39-bus system show that the proposed framework significantly reduces CPF evaluations by 95.45% while preserving high accuracy and boundary fidelity for both regression and classification tasks. The reduced surrogates remain structurally consistent with their full-CPF dataset counterparts, demonstrating the suitability and scalability of the proposed approach for operation and planning optimization.

0.25

Optimal Measurement Selection for Certifiable Voltage Monitoring in Power Distribution Systems

eess.SY ·2026-09-23 ·Peng Zhang, Line Roald, Manish K. Singh
similarity 0.57
Abstract · 10 pages, 4 figures, submitted to HICSS'60

Maintaining consumer-end voltages within mandated limits is a central task in operating power distribution systems. Rising penetration of distributed generation, electric vehicles, and flexible loads complicates this task, while a scarcity of real-time measurements leaves distribution networks largely unobservable. Operators commonly monitor a few bellwether meters, which indicate operational health but certify nothing about the unmeasured buses. This work asks how to select measurements that are reported in real time and can certify network-wide voltage-limit compliance. We first illustrate the geometry of the measurement values that certify voltage safety at unmeasured nodes. Building on this geometry, we formulate a bilevel optimization that selects measurements to maximize certification capability, introducing a novel safety-violation metric with favorable monotonicity properties. We derive a strong-duality-based single-level reformulation and two scenario-reduction schemes with quantifiable suboptimality. Numerical tests on the SCE 56-bus system corroborate the superior certification capability and computational efficiency of the proposed approach.

0.27

Zero-Sum Power Factor Games

eess.SY math.OC ·2026-08-20 ·Cameron Khanpour, Samuel Talkington, Mathieu Dahan, Daniel K. Molzahn
similarity 0.57
Abstract

Variable active power injections arising from device behavior or compromised dispatch complicate voltage regulation in electric power networks with distributed energy resources (DERs). An operator can limit the resulting voltage deviations by remotely selecting DER reactive power parameters before observing the active power injections. IEEE Standard 1547-2018 specifies constant power factor as one such control mode, coupling each device's reactive power to its realized active power. Using a linear voltage model, we formulate the operator's decision as a robust minimax problem in which the operator minimizes the largest feasible aggregate voltage deviation. We solve this problem by expressing the power factor decisions through continuous reactive to active power ratios and exactly decomposing the payoff according to the signs of the voltage deviations. When every feasible voltage residual remains on its initial side of nominal, the resulting ratios cancel each injection's contribution and yield a closed form minimax strategy. We identify realistic DER ratings for which this strategy applies and quantify the regulation capacity lost under restricted power factor ranges. Numerical tests check the cancellation computation, solve the complete minimax problem directly at a representative DER rating, and compare the linear voltage predictions with nonlinear AC power flow.

0.23

Explicit Convex Inner Approximation of TSO-DSO Flexibility Regions via Exact Second-order Cone Relaxation in Radial Networks

eess.SY ·2026-10-20 ·Wenyu Liu, Mario Paolone
benchmark similarity 0.56
Abstract · 10 pages, 4 figures

Accurate representations of the flexibility in distribution grids via tractable algorithms are essential for TSO-DSO coordination. However, flexibility region (FR) estimation based on nonlinear optimal power flow (OPF) generally lacks feasibility guarantees, while conventional convex relaxations may suffer from inexactness. This paper proposes a framework for constructing explicit inner approximations of active-reactive power FRs in radial networks based on the augmented relaxed OPF (AR-OPF). First, less-conservative sufficient conditions for the AR-OPF exactness are derived and extended to generalized objectives. Furthermore, an interior-feasibility analysis is established, guaranteeing that the entire region enclosed by the traced boundary is AC feasible under the proposed sufficient conditions. Building on these theoretical results, two adaptive algorithms are developed to construct explicit inner approximations and numerically convex representations of FRs. Numerical evaluations on different benchmark networks demonstrate consistently small relaxation residuals and high flexibility area retention in most cases, showing that the proposed methods provide a grounded approach to construct operationally admissible FRs for TSO-DSO coordination.

0.35