A Control Philosophy for Multiplexed Power Converters in Active Distribution Systems

Matthew Deakin, Mahmood Jamali, Nail Tosun, Shafiq Odhano

eess.SY ·submitted 2026-09-06 14:12 UTC · v1
published

Abstract

Reconfigurable, multiplexed power electronic devices (M-PEDs) can provide more effective, flexible operation for applications in active distribution networks, enabling the mitigation of thermal constraints and voltage violations. To-date, operational approaches of these M-PEDs have not been described, a significant issue as a result of their relative complexity as compared to conventional PEDs. This work proposes a state machine-based control philosophy that can be used to manage the mutually exclusive selector- and current-control signals for M-PEDs. Two control approaches are described using this philosophy: an Off-Load approach, suitable for systems without time-critical network constraints; and a Hot-Swap approach, implemented when the impact of transients must be minimized. Simulations illustrate the evolution of the state machine for a back-to-back voltage source converter topology. It is concluded that the proposed state machine-based control philosophy enables M-PED operation whilst managing the additional complexity of this promising converter topology.

Comment
Accepted for presentation at ECCE 2026, Vancouver, Canada

Closest papers

Nearest neighbours by meaning across the whole index.

Multi-time-scale Control of Power Systems

eess.SY math.OC ·2026-10-26 ·Emiliano Dall'Anese, John W. Simpson-Porco, Florian Dorfler, Saverio Bolognani, Sairaj Dhople
survey similarity 0.58
Abstract · Submitted for publication

The power grid has been dominated by large synchronous generators and clearly separated control layers. Today, power-electronics energy conversion interfaces are rapidly being deployed calling for another look at system-level control hierarchies. This article examines how multi-time-scale modeling, feedback control, and feedback optimization can help reinterpret the traditional organically grown hierarchy of primary control, automatic generation control, and economic dispatch, and enable new approaches for control of contemporary power systems. Beginning with an overview of power system models and conventional operational practices, the article develops connections to modern control architectures that can coordinate heterogeneous resources, account for operational constraints, and exploit faster actuation without overlooking first-principles physics.

0.28

EMT Modeling and Coordinated Mode-Transition Ride-Through Control of Modern Data Centers

eess.SY ·2026-11-05 ·Junyuan Zheng, Salish Maharjan, Min Lwin, Soummya Roy, Zhaoyu Wang +3 more
similarity 0.58
Abstract

Large data centers are emerging as power-electronic loads whose response to grid voltage disturbances can affect bulk-system stability. This paper presents the composition and control characteristics of a proprietary electromagnetic transient (EMT) model of a modern data center comprising an uninterruptible power supply (UPS) with battery energy storage, induction-motor cooling loads, a computer room air handler (CRAH) driven by a variable-frequency drive (VFD), and an aggregated server load. A voltage-based state machine coordinates three aspects of the facility response: the UPS operating mode (eco, double conversion, or battery), the supply path of the CRAH, and a ramped reconnection of the grid-side UPS converter after the disturbance clears. A 100 MW facility is implemented in PSCAD/EMTDC and benchmarked against the PSSE PERC1 aggregate data center model under a symmetrical three-phase fault and low- and high-voltage ride-through (LVRT/HVRT) events. The two models agree closely in their voltage and active-power trajectories, while the EMT model also resolves the converter and motor-reacceleration transients that the phasor-domain model cannot.

0.50

Optimal Coordination of Heat Pump Demand Flexibility and Battery Energy Storage Considering the Operation of Distribution Networks

eess.SY ·2026-10-06 ·Gustavo L. Aschidamini, Guilherme S. Castiglio, Mariana Resener
similarity 0.55
Abstract

Electrifying space heating with heat pumps (HP) and backup electric-resistance heaters (ERH) is incentivized to support decarbonization but increases voltage and thermal issues in distribution networks. Direct load control (DLC) of smart thermostats (ST) provide grid support, yet, to the best of our knowledge, existing methods do not co-optimize this flexibility with grid-scale battery energy storage systems (BESS) and voltage-regulation devices, and do not use ERH for preheating, limiting peak demand reduction and undervoltage mitigation. We propose a mixed-integer linear programming (MILP)-based model predictive control (MPC) framework that coordinates ST setpoints for preheating and setback, grid-scale BESS, on-load tap changers, switched capacitor banks, and step voltage regulators. The framework is evaluated on 23-node and 733-node distribution networks, including a real-data-based feeder, across multiple realized days. On the 23-node feeder with 50% HP penetration and 50% DLC participation, the proposed framework reduces the feeder peak by 23.1%, and by 27.1% with the co-optimized BESS. Rolling-horizon setpoint optimization contributes 6.5 percentage points beyond a day-ahead ST schedule (16.6%), and dispatching the ERH for preheating adds 2.7 percentage points beyond backup-only operation (20.4%). On the 733-node feeder, where thermal congestion is the binding constraint, the framework reduces overloaded branches by 94% and overloaded transformers by 47%. These results demonstrate the potential of coordinated demand flexibility and voltage regulation to accommodate heating electrification.

0.12

Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control

eess.SY ·2026-11-14 ·Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah +2 more
hot direction similarity 0.54
Abstract · 5 pages, 7 figures

The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.

0.22

Equivalent Modeling of Load-Side Systems With Distributed Renewable Generation Considering Fault Responses and Nodal Voltage Coherence

eess.SY ·2026-09-21 ·Yuqi Cao, Chen Shen, Shaowei Huang, Ying Chen, Hongyi Zhu
similarity 0.54
Abstract · Submitted to IEEE Transactions on Power Systems

Operating conditions and fault severity change both the initial states and control modes of active distribution networks. Direct capacity aggregation can therefore lose the power responses required for transmission-system dynamic analysis. This paper develops a procedure for generating low-order physical electromagnetic transient equivalents from a small set of representative operating conditions. Device power, ride-through states, load mechanical states, and local sequence voltages are combined with electrical distance to form response families. Response reconstruction and terminal simulation errors determine the retained architecture, after which bounded sensitivity calculations determine effective dynamic coefficients. The architecture and coefficients are then fixed. For a new operating condition, capacity and power balances, voltage-dependent load relations, and an initialization correction generate the model parameters from static inputs and power-flow results. A representative severe fault establishes a template for each fault type, which is reused across fault depths. Aggregation and switching-time bounds explain the roles of voltage coherence and state separation. Comparisons with direct aggregation show improved terminal responses across operating conditions and several fault types, with the largest gains under severe unbalanced faults. The method provides a reusable physical equivalent for operating-condition studies and fault-depth screening.

0.17

Fixed-Time Voltage Regulation in Distribution Networks with Impedance Awareness

eess.SY ·2026-10-01 ·Nilanjan Roy Chowdhury, Venkatesh Sarangan
similarity 0.54
Abstract · 8 pages, 6 figures

This letter introduces an optimization-based fixed time control algorithm for solving the voltage regulation problem of a radial and balanced power distribution network. The proposed algorithm requires no prior knowledge of the exact network impedance (resistance and reactance), yet guarantees voltage convergence to the predefined safe limit within a fixed time-window. We embrace results from Fixed-time stability (FxTs) and Control Lyapunov function (CLF) to analyze the stability and robustness of the underlying algorithm and then synthesize it leveraging the Quadratic Programming (QP) approach. We first analytically provide sufficient conditions on the control gains and the design parameters, that can ensure voltage regulation in fixed-time. Thereafter we transform the existing voltage regulation problem into an equivalent QP-based optimization framework and translate the aforesaid conditions to find feasible solutions for voltage stability. We empirically verify the efficacy of our proposed algorithm on the IEEE-33 bus distribution network and compare its performance against other existing robust control methods.

0.29

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.53
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Quantifying the Unintentional Islanding Risk: A Comparative Study on Active Distribution Network

eess.SY ·2026-09-10 ·Harshit Nayak, Edoardo Daccò, Jose Luis Rueda Torres, Davide Falabretti
similarity 0.53
Abstract

The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.

0.28