Congestion Structure and Exceedance Bounds for Locational Marginal Emissions

Cameron Khanpour, Samuel Talkington, Daniel K. Molzahn

eess.SY ·submitted 2026-09-15 02:04 UTC · v1

Abstract

Locational marginal emissions (LMEs) give the sensitivity of total operating carbon emissions to nodal power demand. We show that this vector with $n$ entries has a much smaller intrinsic dimension under DC optimal power flow. Within a fixed active constraint set, the LME vector lies in the span of the uniform vector and the power transfer distribution factor rows of the binding lines. Its rank $r$ is therefore at most one more than the number of binding/congested lines. This structure makes $r$ independent scalar observations necessary and sufficient for exact recovery. Across ten systems with nonzero operating emissions, from 14 to 1,354 buses, $r$ ranges from 2 to 15. For instance, on a 300 bus system, 24 dispatch simulations recover all 300 LMEs. We also derive an emissions exceedance bound under uncertain demand. The bound separates variation while the nominal active set remains unchanged, the probability of an active set change, and estimation error. Numerical results show that its usable forecast error range depends on local active set geometry.

Closest papers

Nearest neighbours by meaning across the whole index.

Time to AC-t: When AC-transmission changes capacity expansion planning

eess.SY math.OCphysics.soc-ph ·2026-11-02 ·Lara Booth, Shiva Madadkhani, Ruaridh Macdonald, Priya L. Donti
code/data similarity 0.57
Abstract · 35 pages, 5 figures, 3 tables; plus 16 pages of supplemental information (8 figures, 6 tables). Submitted to Joule

Capacity expansion models often dramatically simplify the physics of how power flows through a transmission network in order to preserve computational tractability. However, with the rapid growth of electrification, large loads, renewables, and storage, increased realism in planning future grids is imperative. We extend the open-source capacity expansion model GenX with AC optimal power flow physics, and analyze generation, storage, and transmission investment decisions for 20-zone, hourly models of Germany and Texas. We compare our results against those using two common approximations, the transport model and DC optimal power flow. We find that total costs and emissions largely agree across all formulations. However, we find substantial differences in outputs related to transmission, generation siting, storage, and reactive-power support between the approximate formulations and the true AC physics formulation. We identify where AC physics changes planning decisions and discuss how to potentially capture these effects without the full computational cost.

0.23

Congestion Price Uncertainty From Interconnection Queue by Monte Carlo Sampling

eess.SY ·2026-10-14 ·William A. Wheeler, Samuel Chevalier, Amritanshu Pandey
similarity 0.56
Abstract · 8 pages, 9 figures

The generation interconnection queue adds discrete uncertainty to power grid congestion price estimates on the project planning timescale. The conventional approach to this uncertainty is to make an informed guess of the single or few most likely configurations of generators that interconnect. In this paper, we show that Monte Carlo sampling is a more effective alternative. Given an estimate of the joint probability distribution of generator interconnections, a small number of samples yields good estimates of the congestion distribution. Crucially, this problem is not about rare events, but rather about the expected congestion over the worst times of the year, which makes congestion a common outcome over the distribution of interconnection events. We give empirical results on a 2000-bus network, averaging price outcomes from security-constrained DCOPF over eight different loading scenarios. For each line and contingency of the network, we estimate the full distribution as well as mean price and probability of exceeding a price threshold. Single-point estimates are unreliable and can be misleading about whether a line is likely to be congested. Combining the top k probability configurations yields improved estimates; however, sampling the same number from a distribution gives a more robust result of similar accuracy, as well as error estimates. Including correlation in the distribution model introduces small changes, showing that standard Bernoulli distributions suffice in most cases. The sampling approach is also applicable to large-load interconnection and should be of interest for planning both generation and large-load projects.

0.31

Locational Marginal Pricing for Adaptive Robust Look-Ahead Dispatch with Casual Affine Recourse

eess.SY ·2026-09-04 ·Aidan Looney, Qian Zhang, Le Xie
similarity 0.56
Abstract · 12 pages, 3 figures, 5 tables

This paper develops a marginal pricing mechanism for adaptive robust look-ahead economic dispatch (LAED) under net-load uncertainty. In current market practice, deterministic multi-interval dispatch can misprice flexibility when forecast error is large. Fully adaptive robust (FAR) dispatch captures this uncertainty, but competing worst-case trajectories can imply different marginal values of demand, leaving no single price for market settlement. We propose causal affine recourse (CAR) as a tractable, price-forming approximation. CAR replaces independently optimized trajectory-specific schedules with a causal affine response policy, yielding a market-clearing model that retains the standard energy and congestion decomposition of DC Locational Marginal Pricing. We then demonstrate that CAR-LMP together with a ramp-adjusted current settlement supports dispatch-following and eliminates current-period lost opportunity costs. We solve the CAR problem by deriving a robust counterpart and present computational evidence on exact small DC instances, a ten-generator system, and an IEEE 300-bus public-network case. These simulations show that the proposed prices collapse exactly to deterministic LAED-LMP when robustness is inactive, remain stable in loose-ramp regimes, and produce economically meaningful price shifts when flexibility is scarce. The proposed pricing mechanism provides a practical bridge between adaptive robust dispatch and market-based pricing.

0.28

Modeling of Network Constraints in Large-scale Capacity Expansion Optimization of Power Grids

eess.SY math.OC ·2026-08-28 ·Yu Weng, Lara Booth, Priya L. Donti, Ruaridh Macdonald
publishedtheoryhot direction similarity 0.56
Abstract

Capacity expansion modeling plays a critical role in optimizing the deployment of new generation, storage, and transmission, typically at national and regional levels. To support long-term planning, these models consider a large set of energy technologies and policies, along with decades of weather and demand data. Realistic capacity expansion models thus become high-dimensional optimization problems, with hundreds of millions of variables and constraints, which are challenging to solve. A common strategy to address this complexity is to omit non-linear, non-convex AC optimal power flow (ACOPF) constraints and instead use linearized power balance equations or transport formulations. While these simplifications improve tractability, they limit our understanding of how power flow and the physical properties of power networks impact investment decisions across generation, storage, and transmission infrastructure. This paper addresses this gap by extending the GenX capacity expansion model to incorporate fixed point theorem-based network constraints. These embed ACOPF-based considerations while maintaining the tractability of the planning model, nearly preserving the dimensionality of the transport formulation and incurring only modest runtime increases. This approach is much cheaper than embedding ACOPF directly, making it appropriate for large-scale capacity planning problems. We compare our approach to the original transport-based GenX model as well as a non-linear, non-convex version that incorporates the full ACOPF constraints, for a case study of the ISO New England grid.

0.47

Zero-Sum Power Factor Games

eess.SY math.OC ·2026-08-20 ·Cameron Khanpour, Samuel Talkington, Mathieu Dahan, Daniel K. Molzahn
similarity 0.54
Abstract

Variable active power injections arising from device behavior or compromised dispatch complicate voltage regulation in electric power networks with distributed energy resources (DERs). An operator can limit the resulting voltage deviations by remotely selecting DER reactive power parameters before observing the active power injections. IEEE Standard 1547-2018 specifies constant power factor as one such control mode, coupling each device's reactive power to its realized active power. Using a linear voltage model, we formulate the operator's decision as a robust minimax problem in which the operator minimizes the largest feasible aggregate voltage deviation. We solve this problem by expressing the power factor decisions through continuous reactive to active power ratios and exactly decomposing the payoff according to the signs of the voltage deviations. When every feasible voltage residual remains on its initial side of nominal, the resulting ratios cancel each injection's contribution and yield a closed form minimax strategy. We identify realistic DER ratings for which this strategy applies and quantify the regulation capacity lost under restricted power factor ranges. Numerical tests check the cancellation computation, solve the complete minimax problem directly at a representative DER rating, and compare the linear voltage predictions with nonlinear AC power flow.

0.23

Explicit Convex Inner Approximation of TSO-DSO Flexibility Regions via Exact Second-order Cone Relaxation in Radial Networks

eess.SY ·2026-10-20 ·Wenyu Liu, Mario Paolone
benchmark similarity 0.53
Abstract · 10 pages, 4 figures

Accurate representations of the flexibility in distribution grids via tractable algorithms are essential for TSO-DSO coordination. However, flexibility region (FR) estimation based on nonlinear optimal power flow (OPF) generally lacks feasibility guarantees, while conventional convex relaxations may suffer from inexactness. This paper proposes a framework for constructing explicit inner approximations of active-reactive power FRs in radial networks based on the augmented relaxed OPF (AR-OPF). First, less-conservative sufficient conditions for the AR-OPF exactness are derived and extended to generalized objectives. Furthermore, an interior-feasibility analysis is established, guaranteeing that the entire region enclosed by the traced boundary is AC feasible under the proposed sufficient conditions. Building on these theoretical results, two adaptive algorithms are developed to construct explicit inner approximations and numerically convex representations of FRs. Numerical evaluations on different benchmark networks demonstrate consistently small relaxation residuals and high flexibility area retention in most cases, showing that the proposed methods provide a grounded approach to construct operationally admissible FRs for TSO-DSO coordination.

0.35

Who Gets the Grid Capacity? Allocating Dynamic Access Among Multiple Virtual Power Plants

eess.SY ·2026-11-16 ·Nakul Sreekanth, Jun He, Andrew L. Liu, S. Sivaranjani
similarity 0.53
Abstract

Virtual power plants (VPPs) trade in the same wholesale market and share distribution lines and transformers, and uncoordinated, profit-maximizing VPPs can push a shared transformer past its thermal limit or drive a feeder voltage out of band. The utility, which only observes the front-of-the-meter net injection at each bus, must keep the network safe from that net injection alone. We allocate a 24-hour active and reactive operating envelope to each VPP by a Benders decomposition: the utility sets a trial envelope, each VPP solves its private convex portfolio problem, and the returned value and dual gradient become supporting cuts that rebuild its value function while its schedule, state, and cost stay private. The envelope carries the transformer's thermal state across hours, bounds a joint conditional value-at-risk over forecast uncertainty, and is re-optimized each hour with the current hour committed. On a reduced IEEE-13 feeder with real load and prices, an active-power-only implementation lowers the transformer's peak-temperature CVaR from 254 to 97\,$^\circ$C at a 28\% value give-up and holds the transformer below its limit where nameplate access breaches it.

0.30

Differentiable Electricity-Market Clearing for Gradient-Based Planning

cs.LG cs.CY ·2026-09-02 ·Luca Mungo, Maarten P. Scholl, Arnau Quera-Bofarull
similarity 0.52
Abstract · 9 pages, 4 figures

Planning a large data center is difficult because a facility big enough to matter changes the electricity prices it will pay. Those prices are set by market clearing, a constrained optimization problem solved anew in every operating condition. However, simulating the market tells a planner how a candidate plan performs but not how to improve it. Here we treat market clearing as a differentiable optimization layer: each forward pass solves the market, and reverse-mode automatic differentiation propagates the planning cost back through the cleared prices to the plan. After validating these gradients against finite differences, we apply them to a concrete problem: allocating 50 MW of data-center load across six candidate buses in two synthetic networks, under a fixed cost per active site, evaluated over 36 operating states. Judged against exhaustive enumeration of all site combinations, gradient optimization recovers the continuous allocations almost exactly, with worst-case objective gaps of 2.3\% and 8.5\% of the cost difference between the best and worst single site. Its one systematic error is instructive: near the costs at which a site should close, the smooth relaxation of the discrete site count shrinks the site rather than closing it, so discrete transitions arrive late. Differentiable market clearing thus turns market-aware planning into a problem gradients can search.

0.37