Who Gets the Grid Capacity? Allocating Dynamic Access Among Multiple Virtual Power Plants

Nakul Sreekanth, Jun He, Andrew L. Liu, S. Sivaranjani

eess.SY ·submitted 2026-11-16 23:10 UTC · v1

Abstract

Virtual power plants (VPPs) trade in the same wholesale market and share distribution lines and transformers, and uncoordinated, profit-maximizing VPPs can push a shared transformer past its thermal limit or drive a feeder voltage out of band. The utility, which only observes the front-of-the-meter net injection at each bus, must keep the network safe from that net injection alone. We allocate a 24-hour active and reactive operating envelope to each VPP by a Benders decomposition: the utility sets a trial envelope, each VPP solves its private convex portfolio problem, and the returned value and dual gradient become supporting cuts that rebuild its value function while its schedule, state, and cost stay private. The envelope carries the transformer's thermal state across hours, bounds a joint conditional value-at-risk over forecast uncertainty, and is re-optimized each hour with the current hour committed. On a reduced IEEE-13 feeder with real load and prices, an active-power-only implementation lowers the transformer's peak-temperature CVaR from 254 to 97\,$^\circ$C at a 28\% value give-up and holds the transformer below its limit where nameplate access breaches it.

Closest papers

Nearest neighbours by meaning across the whole index.

Price-Optimized EV and Heat-Pump Scheduling Can Exceed Uncoordinated Feeder Peaks

eess.SY ·2026-10-05 ·Tatjana Hein, Lukas P. Wagner, Alex Bernhard, Felix Ocker
publishedcode/data similarity 0.67
Abstract · Accepted at 2026 IEEE IES ONCON

Electric vehicles and heat pumps add large, time-flexible loads to low-voltage feeders. When each household independently minimizes its own charging cost against the same electricity price, this flexible demand piles into the cheapest hours, and the resulting synchronization can stress the feeder more than uncoordinated operation does. This work quantifies that effect on a rural low-voltage feeder with photovoltaics (97 buses, 250 kVA transformer) in 913 simulation runs that compare seven strategies across four seasons, device penetrations of up to 90 %, 208 price weeks from 2022-2025, and heterogeneous heat pumps. At 30 % penetration of each device, this decentralized cost minimization drives the transformer to 253 % of rated capacity, more than three times the peak of non-optimized Fixed-random charging with the same mobility and charged energy, and 478 % with electric vehicles alone at 90 % penetration, with undervoltage at the far end of the longest feeder arm. It exceeds Fixed-random and Fixed-times charging in every winter, spring, and autumn price week, and each 30 pp of heat-pump penetration raises its peak by about 110 pp, twelve times as much as without optimization. Centralized peak minimization removes all demand-driven violations. In the heat-pump-free summer case at 60 % photovoltaics, midday reverse power flow sets a transformer floor of 128.9 % that no strategy undercuts, since no commuting electric vehicle is at home at the export peak. With a time-variable grid fee added to the spot price, the weekly peak of decentralized cost minimization falls into the reduced-fee window in 99 of the 104 fee-active price weeks, compared with 53 without the fee, while keeping at least 89.8 % of its height, so the fee relocates rather than removes the synchronization. The simulation and optimization code is available at https://github.com/lukas-wagner/SynchronizationEffectsAnalysis.

0.64

Resource-Aware Rolling-Horizon Controller for Renewable-Based Virtual Power Plants Providing Automatic Frequency Restoration Reserves

eess.SY ·2026-09-25 ·Marco Vinicio Avendaño-Caiza, Juan Diego Rios-Peñaloza, Javier Roldán-Pérez, José Luis Rodríguez-Amenedo, Milan Prodanovic
similarity 0.63
Abstract · Submitted to a scientific journal for possible publication. 10 pages, 11 figures

Virtual power plants (VPPs) are an effective solution for increasing the penetration of renewable energy sources (RES) in power systems. Moreover, VPPs can provide ancillary services if generators and loads are closely connected and properly coordinated. This aspect has been addressed in several studies, yet they mostly focus on the dispatch optimisation level, leaving real-time operation aspects unresolved. To close this gap, a central controller for VPPs based on a rolling-horizon optimisation is proposed in this work. Its main objective is to maximise revenues while delivering frequency restoration services. A day-ahead optimisation firstly defines the power setpoint and the upward and downward reserves of the VPP. Then, the rolling-horizon optimiser, executed every minute, distributes the power and reserve references between the VPP units to achieve their close tracking while taking into account resource availability (wind speed, irradiance, etc.), operational constraints and battery degradation. The effectiveness of the controller is tested using a two-area interconnected power system under different RES generation and demand profiles. The simulations are performed in MATLAB/Simulink and include detailed dynamic models of the VPP elements, demonstrating the applicability of the algorithm to real systems. The day-ahead and the rolling-horizon optimisation problems are modelled using YALMIP and solved using Gurobi. The obtained results demonstrate the VPP supporting grid frequency restoration by optimally allocating its resources, even under the presence of forecast uncertainty.

0.18

Fair Dynamic Operating Envelopes using Distributed Multi-Period Optimal Power Flow and Jain Index for Active Distribution Networks

eess.SY cs.CE ·2026-08-24 ·Pedro Salomão Quessongo, Daniel Gebbran, Clodomiro Unsihuay-Vila
similarity 0.62
Abstract · 10 pages, submitted to CLAGTEE 2026 Conference

Dynamic operating envelopes (DOEs) are increasingly used to publish time-varying export limits that keep distribution networks within operational limits. Purely technical DOE allocation, however, can systematically privilege electrically favorable prosumers, while embedding fairness directly into a single-period optimal power flow (OPF) objective mixes network feasibility, equity and efficiency in a way that obscures the cost of fairness. This paper proposes a two-stage, multi-period framework that addresses both of these. Initially, a technical distributed OPF computes network-feasible export envelopes. The subsequent stage then applies a dynamic aggregate export budget and redistributes capacity through cumulative proportional fairness, limiting the additional curtailment by an admissible efficiency budget. The resulting fair DOEs are treated as first-stage decisions, while battery storage provides scenario-dependent recourse under demand and renewable uncertainty. The operational problem is solved by a calibrated regional alternating direction method of multipliers (ADMM) on a lossless LinDistFlow model and independently validated using AC power flow. We observe a trade-off between increases in curtailment \emph{versus} improvements on fairness, as expected, reaching Jain fairness indices close to unity. Results show that considering both storage (which alleviates curtailment impact) and multi-period fairness (which increases curtailment) is an interesting approach for modern DOE design, which in turn requires a multi-period, co-designed approach.

0.54

DOE-Constrained Distributed Battery Coordination in Unbalanced Distribution Networks

eess.SY ·2026-11-09 ·Bohang Fang, Anderson Toler, Lijun Ding, Wenqi Cui, Cong Chen
similarity 0.60
Abstract · 8 pages; substantially revised version with a new title, revised formulation and theoretical results, and updated numerical results

Dynamic operating envelopes (DOEs) provide injection and withdrawal limits for distributed energy resource scheduling while respecting network operational constraints. This paper develops a risk-aware DOE framework for distributed battery operation in unbalanced three-phase networks using a semidefinite program (SDP). We derive sufficient conditions for exactness of the SDP relaxation, ensuring that the recovered operating points corresponding to the DOE vertices satisfy all voltage and nodal power injection constraints of the original AC network model. The method computes hourly active-power DOEs under uncertain load conditions and incorporates them directly into a 24-hour battery operation problem. On a modified IEEE 13-bus feeder, empirical comparisons with unconstrained arbitrage and local Volt--VAR/Volt--Watt control show that DOE-constrained battery scheduling eliminates the observed out-of-sample voltage violations while retaining 94.6\% of the unconstrained arbitrage profit.

0.29

Power Setpoint Tracking for Large-Scale EV Charging: Transformer-Constrained Charging Policy Learning with Self-Tuning Constraint Prices

cs.LG eess.SY ·2026-11-19 ·Daniyal Sajedi-Hosseini, Yoshihiko Fujisawa, Shubham Singh, Lei Zhou, Katsuki Fujisawa +3 more
similarity 0.60
Abstract · 13 pages, 7 figures, 6 tables. Submitted to IEEE Transactions on Transportation Electrification

In power setpoint tracking (PST), an operator follows a purchased charging profile without overloading shared transformers or undercharging vehicles. PST is cast as a constrained Markov decision process that minimizes tracking error subject to overload and mean user-satisfaction constraints. Transformer-Constrained Charging Policy Learning (TC-CPL) extends soft actor-critic with proportional-integral Lagrange-multiplier updates from measured violations, a residual on the incumbent dispatcher that is warm-started from its demonstrations, and a transformer-aware encoder shared by all ports. It observes no departure times or states of charge. Simulations (five seeds, 100 paired days) compare it with the incumbent, Round-Robin. On a 600-port, 122-substation district, raw overload falls from 3.59 to 0.0017 kWh/day (overloaded seed-days from 77% to 0.4%), and absolute tracking error falls by 27%. Delivered energy rises by 16%, and satisfaction rises from 0.959 to 0.989. On a 42-kW transformer with household load, overload falls from 1.86 to 0.0014 kWh/day and satisfaction rises from 0.974 to 0.985, but absolute tracking error is 22% higher. Against hand-set fixed multipliers, self-tuning is statistically indistinguishable on the district. On the single transformer, it raises satisfaction by 0.011 at similar overload, but a short sweep found a better-serving fixed pair. The overload multipliers stay below their cap.

0.31

Time to AC-t: When AC-transmission changes capacity expansion planning

eess.SY math.OCphysics.soc-ph ·2026-11-02 ·Lara Booth, Shiva Madadkhani, Ruaridh Macdonald, Priya L. Donti
code/data similarity 0.60
Abstract · 35 pages, 5 figures, 3 tables; plus 16 pages of supplemental information (8 figures, 6 tables). Submitted to Joule

Capacity expansion models often dramatically simplify the physics of how power flows through a transmission network in order to preserve computational tractability. However, with the rapid growth of electrification, large loads, renewables, and storage, increased realism in planning future grids is imperative. We extend the open-source capacity expansion model GenX with AC optimal power flow physics, and analyze generation, storage, and transmission investment decisions for 20-zone, hourly models of Germany and Texas. We compare our results against those using two common approximations, the transport model and DC optimal power flow. We find that total costs and emissions largely agree across all formulations. However, we find substantial differences in outputs related to transmission, generation siting, storage, and reactive-power support between the approximate formulations and the true AC physics formulation. We identify where AC physics changes planning decisions and discuss how to potentially capture these effects without the full computational cost.

0.23

Threshold Pricing for Distributed Scheduling of Flexible Demands in Energy Communities

eess.SY ·2026-08-27 ·Minjae Jeon, Lang Tong, Qing Zhao
similarity 0.60
Abstract

This paper develops a price-based distributed scheduling in an energy community whose members own behind-the-meter renewable generation with deferrable EV charging and price-elastic thermostatic loads. A coordinator transacts with the distribution utility under a Net Energy Metering tariff and broadcasts a community price to which each household responds in its own interest, giving a bilevel stochastic dynamic program that is intractable in general. Our main result characterizes that the joint optimal centralized policy is a two-threshold policy on the community's aggregate renewable generation. Building on this structure, we adopt the Threshold Pricing Rule, which is uniform, individually rational, revenue adequate, and asymptotically optimal in terms of community welfare under a light-traffic condition. Simulations using synthetic and real world data confirm asymptotic optimality and individual surplus gains.

0.25

Prosumer Synchronisation Risk: Impacts of Time-Varying Tariffs on Distribution Network Expansion

eess.SY ·2026-09-02 ·Dillon Zadoks, Alfredo Oneto, Carlo Tajoli, Yi Guo, Philipp Heer +2 more
published similarity 0.59
Abstract

The rapid deployment of distributed energy resources, including heat pumps, electric vehicles, photovoltaics, and battery storage, is reshaping the operation of low-voltage networks. While distribution system operators often aim to develop time-varying tariffs to incentivise network-friendly behaviour and defer reinforcements, they risk triggering prosumer synchronisation. As prosumers follow price signals, their behaviour may synchronise, avoiding existing load peaks while creating undesirable peaks at other times. This paper quantifies the impact on low-voltage network reinforcement needs when shifting from flat tariffs to two time-varying tariffs: Time-of-Use and Real-Time Pricing. Applying a mixed-integer linear model across 471 low-voltage reference networks in Switzerland, we evaluate expansion requirements under projections of distributed energy resource deployment for 2050. In the model, prosumers operate their distributed energy resources in accordance with their subscribed electricity tariff to minimise costs, and the distribution system operator subsequently optimises reinforcements. Our results demonstrate that while adopting time-varying tariffs can reduce reinforcement investment costs by more than 50%, high adoption rates can reverse this declining trend. Specifically, once prosumer adoption exceeds the optimal thresholds of 50% for Time-of-Use and 40% for Real-Time Pricing, reinforcement needs increase by 39% and 134%, respectively, for an additional 20% of tariff adoption.

0.24