The Price of a Cycle: A Phasor -vs- Sampled-Value Comparison for Streaming Fault Classification on the IEEE 9-Bus System

Emad Abukhousa, Khaled Muhmmed Nor Muhmmed, Abdulaziz Qwbaiban, Saman Zonouz, A. P. Sakis Meliopoulos

eess.SY ·submitted 2026-10-03 00:17 UTC · v1
benchmark

Abstract

Transmission-line fault classification is a time-critical protection function, and recent machine-learning methods classify fault type directly from voltage and current measurements. The input to such a classifier can be supplied as sampled-value windows of raw measurements, which preserve sub-cycle structure, or as phasor-domain sequence components, which are physically interpretable but require a causal one-cycle observation window before a phasor estimate is available. This paper measures the cost of that observation window, the price of a cycle, through a controlled comparison of the two representations for streaming fault-family classification on the standard synchronous WSCC/IEEE 9-bus system. The comparison holds the simulated system, the measured channels, the eleven-class event-family taxonomy, the training procedure, and the streaming decision layer constant, and uses six configurations: 40- and 80-sample sampled-value inputs and one-cycle phasor inputs, each evaluated with a multilayer perceptron (MLP) and a one-dimensional convolutional neural network (CNN). All six configurations classify every event successfully, yet the sampled-value representation reaches the correct class earlier in every model pair. The 40-sample sampled-value MLP attains the strongest result, with 99.34% fault-window accuracy, 99.79% normal accuracy, a 0.21% false-fault rate, a 0.65% false-normal rate, and a 2.81 ms mean first-correct delay, and it Pareto-dominates the other five configurations. A matched-window comparison at eighty samples confirms that the timing advantage follows from the representation rather than from the window length. On this clean synchronous benchmark, the one-cycle phasor representation does not return an accuracy or stability benefit sufficient to offset its delay.

Closest papers

Nearest neighbours by meaning across the whole index.

Understanding the limits of snapshot-based fault diagnosis in distribution networks

cs.AI ·2026-11-13 ·Ba Tu Phung, Huy Hoang Le, Kim-Anh Nguyen
similarity 0.63
Abstract

Inverter-based resources weaken fault currents in distribution networks, and snapshot-based diagnosis, which classifies a fault from voltage phasors at a few buses at one instant, offers a cheap first-stage screen. Its published accuracies, however, rest on different noise assumptions and do not show whether the error comes from the classifier, the features, the measurement error, or the fault resistance. This paper separates these sources on three IEEE test feeders and a public data set with distributed generation, using four feature sets, thirteen classifiers, and measurement error defined by total vector error classes. The classifier is not the limiting factor, because the full phasor snapshot classifies every fault correctly without noise, and the remaining error comes from measurement error on high-impedance faults. Three voltage sensors classify 90-96% of faults at the 1% accuracy class and 96-99% with distribution micro phasor measurement units (micro-PMUs). A discriminability-margin placement selects them from simulations alone in under one second and matches the best of twelve placement methods. The results show when snapshot-based diagnosis can be trusted.

0.31

Protection-Oriented Assessment of Machine Learning-Based Fault Detection in Power Systems

cs.LG eess.SP ·2026-11-13 ·Julian Oelhaf, Georg Kordowich, Changhun Kim, Christian Bergler, Andreas Maier +2 more
publishedhot direction similarity 0.62
Abstract · 9 pages, 3 figures, 5 tables. Accepted for oral presentation at the 21st International Conference on Developments in Power System Protection…

Machine learning (ML)-based fault detectors are increasingly proposed for power system protection, yet aggregate metrics can obscure the consequences of false and missed trips. We present a protection-oriented assessment of three ML detectors and a sequence-current reference on PROTECT-90, comprising 9,022 simulated fault episodes on a 90 kV double-circuit line. The assessment combines five window conditions, causal window-end labelling, episode-grouped cross-validation, and operating-point selection under a fixed security budget. It reports security, dependability, detection timing, decision margins, and episode-level nuisance assertions. Gradient-boosted trees, a convolutional neural network, and logistic regression achieve AUC-ROC values above 0.999, yet at a security budget of $10^{-3}$ their developed-fault missed-trip rates range from 0.007% to 1.99%. Post-clearing false-trip rates of approximately 0.12-0.16% per window coexist with nuisance assertions in 11.3-19.1% of episodes. Among the analysed physical descriptors, missed trips are most consistently associated with higher fault resistance within the sampled range. An analytical current proxy suggests a fault-current gradient only partly reproduced by waveform-derived current (rank correlation 0.62). No single topology state or faulted phase consistently dominates within the sampled domain. Because PROTECT-90 contains fault episodes only, security is assessed on pre-fault and post-clearing windows rather than independent non-fault disturbances.

0.34

Multi-Library Feature Engineering and Statistically Validated Classification for Power Swing Detection and Stability Assessment

eess.SP cs.LG ·2026-11-16 ·Pallav Kumar Bera, Samita Rani Pani, Ranjeeta Patel
published similarity 0.62
Abstract · Accepted at Annual Conference of the IEEE Industrial Electronics Society (IECON) 2026; 52nd Edition; Doha, Qatar

Faults occurring during power swings, and the evolution of a swing into an unstable condition, cause distance-relay maloperation and cascaded outages. This paper identifies faults, faults during power swings, and power swings, and distinguishes stable from unstable swings in a 9-bus WSCC system modeled in PSCAD/EMTDC. Three time-series feature libraries (tsfresh, TSFEL, and tsfeatures) are applied to the 3-phase relay voltages and currents, giving 3286 statistical, temporal, spectral, and fractal descriptors per event window. A two-step feature selection (Boruta all-relevant filtering followed by RFECV- and SHAP-guided minimal-optimal pruning) reduces the feature set to 18 compact, non-redundant features. 14 classifiers spanning linear, kernel/instance-based, probabilistic, neural, and tree-ensemble/boosting families are then benchmarked under repeated stratified cross-validation, with model differences assessed by a Friedman/Nemenyi omnibus-and-post-hoc test and a Nadeau--Bengio corrected paired t-test. Rotation Forest (ROF) identifies the three event types with 99.98% and SVM-RBF distinguishes stable from unstable swings with 97.97% balanced accuracy. The results show that automated, library-driven feature extraction combined with rigorous statistical model comparison achieves near-perfect discrimination while retaining feature-level interpretability through SHAP importance.

0.35

One-Cycle Fault Classification and Faulted-Line Identification on the PROTECT-90 Dataset: An Initial Application Benchmark

eess.SY cs.LG ·2026-10-02 ·Emad Abukhousa, Abdulaziz Qwbaiban, Saman Zonouz, A. P. Sakis Meliopoulos
benchmarkcode/data similarity 0.61
Abstract

Open electromagnetic-transient datasets are beginning to make reproducible learning-based protection studies possible, but the practical use of these datasets still requires application-level benchmarks that define timing, sensing, and validation assumptions. This paper presents an initial application benchmark on the recently released PROTECT-90 dataset for two protection-oriented tasks: fault-type classification and discrete faulted-line identification. A compact one-dimensional convolutional neural network (CNN) is evaluated using post-inception windows of 0.25, 0.5, 1, and 2 cycles under strict episode-wise splitting. A non-convolutional multilayer perceptron (MLP) is also trained as an architecture-control baseline. The results show that both tasks are nearly saturated under full observability, with one-cycle test accuracies of 99.84% for fault type and 100.00% for line identification. The main performance variation appears under reduced observability: current-only inputs preserve line identification accuracy at 100.00%, whereas voltage-only inputs reduce line identification accuracy to 53.09% with the CNN and 50.57% with the MLP. This indicates that the limiting factor is measurement information rather than neural architecture. Additional stratified checks show stable performance across topology states and fault-resistance bins, while CPU inference contributes only 0.528 ms to the one-cycle total decision time of 20.53 ms.

0.29

A Topology-Aware Neural Network for Fault Location With Missing Measurements

eess.SY ·2026-10-27 ·Fan Jiang, Linhan Fang, Xingpeng Li, Kaushik Rajashekara
similarity 0.59
Abstract

This paper proposes a topology-aware neural network-based fault locator (TANFL) for radial distribution feeders, which uses voltage and current phasors obtained after the decay of fault induced transients, as well as feeder connection relationships and line parameters, as inputs. The shared bus encoder, bus readout module, and gated line readout module work together to identify the faulty bus or line and estimate the continuous fault location on the selected line. During training, explicit missing data indicators and random bus data block masking are introduced, enabling a single trained model to handle both complete measurement sets and scenarios where any permitted bus measurement device fails. On the IEEE 15 bus feeder, this paper compares TANFL with a conventional multilayer perceptron (MLP) and the formula-based localization method under identical data, measurement availability scenarios, and evaluation metrics. On the test partition, TANFL outperforms the conventional MLP; with complete measurements, its line fault location performance is slightly lower than that of the formula-based method, but in the average results for scenarios with one missing bus measurement block, its accuracy is the highest among the three methods at a 5% tolerance.

0.51

HydroJEV: A one-second, training-free screen for cyber-attack and fault attribution in water distribution networks

cs.AI ·2026-10-01 ·Tianwei Mu, Shengyan Jiang, Mingzhe Yuan, Qing Luo, Min Xiao +3 more
benchmark similarity 0.58
Abstract · 41 pages, 19 figures

When a SCADA alarm is raised in a water distribution network, operators must decide quickly whether it reflects a cyberattack, a physical fault, a normal transient or a faulty sensor. Supervised classifiers need labelled incidents that utilities rarely have, and frontier large language models (LLMs) take tens of seconds per decision. We tested whether Jev, a training-free model that returns class probabilities in about one second, can serve as the first tier of this triage. On a four-class cause-attribution benchmark built on the C-Town network in EPANET, Jev was compared with a hand-written rule tree, a supervised classifier and seven cloud LLMs on identical evidence in four sealed, pre-registered rounds. With only a label-free prior correction, Jev matched the rule tree (macro-F1 0.62-0.64 against 0.56-0.61 in distribution) and exceeded the supervised classifier by 0.36-0.42 on event subtypes absent from its labels, in all four rounds, and it outperformed the classifier whenever fewer than about four labelled events per class were available. Jev also decided 20-40 times faster than frontier LLMs. Accepting only benign Jev verdicts confirmed by the rule tree spared an LLM reviewer 35-38% of windows on fresh sealed sets without loss of macro-F1. Transferred unchanged to two further networks, this gated cascade stayed within the non-inferiority margin of its reviewer on all four sets. A fast, training-free screen can therefore take over about a third of the review load in SCADA anomaly triage while preserving the accuracy of deliberate review.

0.34

A Systematic Evaluation of Machine Learning Methods for Fault Detection and Line Identification in Electrical Power Grids

cs.LG eess.SP ·2026-09-15 ·Julian Oelhaf, Georg Kordowich, Paula Andrea Pérez-Toro, Tomás Arias-Vergara, Andreas Maier +2 more
publishedhighly cited similarity 0.57
Abstract · Accepted at ICASSP 2025. 5 pages, 4 figures. Published version: DOI 10.1109/ICASSP49660.2025.10890544

The integration of renewable energy sources into the electrical grid introduces complex challenges in fault detection and coordination of grid recovery mechanisms. Traditional relay protection systems, which operate based on static rules and predefined thresholds, are inadequate for addressing these challenges, particularly in detecting and isolating faults such as short circuits. Consequently, the conventional methodologies applied to electrical network protection frequently fail to achieve optimal performance in fault detection, especially in terms of adherence to safety standards and the selective limitation of damage. Recent research indicates that machine learning (ML)-based approaches can effectively tackle these issues; however, variations in grid configurations and analysis windows have impeded consistent comparative assessments. In this study, we assess the efficacy of various ML models in detecting electrical faults and pinpointing defective transmission lines within a 10 ms measurement interval - a critical time-frame for real-time operational viability, for the first time. The most effective model attained an F1 score of 0.991 +/- 0.018 and demonstrated a processing time of 0.342ms +/- 0.509ms.

0.52

A simulation based dataset of faults and events for machine learning in power systems

eess.SY ·2026-08-20 ·Georg Kordowich, Jonathan Loebel, Julian Oelhaf, Andreas Maier, Siming Bayer +2 more
similarity 0.56
Abstract

The integration of inverter-based renewable energy sources into electric grids challenges conventional power system protection. Machine learning-based solutions can address these challenges by utilizing available data in modern smart grids. However, the lack of open datasets prevents reproducibility and fair comparisons between different approaches and their results, which hinders further progress. Therefore, this paper presents EvEMTBench, a synthetic dataset of faults and events generated using electromagnetic transient simulations. The physical plausibility of the power system simulation is ensured by validating the simulation parameters against established literature and providing comprehensive documentation of the simulation procedure. The dataset is designed for training, fine-tuning, and benchmarking machine learning models by providing synchronized point-on-wave voltage and current measurements at 9600 Hz across a diverse set of topologies and voltage levels. The inclusion of a wide range of fault and operating events allows the utilization of EvEMTBench for different tasks like incipient fault detection, fault localization, or event detection.

0.50