Understanding the limits of snapshot-based fault diagnosis in distribution networks

Ba Tu Phung, Huy Hoang Le, Kim-Anh Nguyen

cs.AI ·submitted 2026-11-13 10:24 UTC · v1

Abstract

Inverter-based resources weaken fault currents in distribution networks, and snapshot-based diagnosis, which classifies a fault from voltage phasors at a few buses at one instant, offers a cheap first-stage screen. Its published accuracies, however, rest on different noise assumptions and do not show whether the error comes from the classifier, the features, the measurement error, or the fault resistance. This paper separates these sources on three IEEE test feeders and a public data set with distributed generation, using four feature sets, thirteen classifiers, and measurement error defined by total vector error classes. The classifier is not the limiting factor, because the full phasor snapshot classifies every fault correctly without noise, and the remaining error comes from measurement error on high-impedance faults. Three voltage sensors classify 90-96% of faults at the 1% accuracy class and 96-99% with distribution micro phasor measurement units (micro-PMUs). A discriminability-margin placement selects them from simulations alone in under one second and matches the best of twelve placement methods. The results show when snapshot-based diagnosis can be trusted.

Closest papers

Nearest neighbours by meaning across the whole index.

The Price of a Cycle: A Phasor -vs- Sampled-Value Comparison for Streaming Fault Classification on the IEEE 9-Bus System

eess.SY ·2026-10-03 ·Emad Abukhousa, Khaled Muhmmed Nor Muhmmed, Abdulaziz Qwbaiban, Saman Zonouz, A. P. Sakis Meliopoulos
benchmark similarity 0.63
Abstract

Transmission-line fault classification is a time-critical protection function, and recent machine-learning methods classify fault type directly from voltage and current measurements. The input to such a classifier can be supplied as sampled-value windows of raw measurements, which preserve sub-cycle structure, or as phasor-domain sequence components, which are physically interpretable but require a causal one-cycle observation window before a phasor estimate is available. This paper measures the cost of that observation window, the price of a cycle, through a controlled comparison of the two representations for streaming fault-family classification on the standard synchronous WSCC/IEEE 9-bus system. The comparison holds the simulated system, the measured channels, the eleven-class event-family taxonomy, the training procedure, and the streaming decision layer constant, and uses six configurations: 40- and 80-sample sampled-value inputs and one-cycle phasor inputs, each evaluated with a multilayer perceptron (MLP) and a one-dimensional convolutional neural network (CNN). All six configurations classify every event successfully, yet the sampled-value representation reaches the correct class earlier in every model pair. The 40-sample sampled-value MLP attains the strongest result, with 99.34% fault-window accuracy, 99.79% normal accuracy, a 0.21% false-fault rate, a 0.65% false-normal rate, and a 2.81 ms mean first-correct delay, and it Pareto-dominates the other five configurations. A matched-window comparison at eighty samples confirms that the timing advantage follows from the representation rather than from the window length. On this clean synchronous benchmark, the one-cycle phasor representation does not return an accuracy or stability benefit sufficient to offset its delay.

0.31

GCN-Based Model for Fault Classification in Distribution Networks under Harmonic Distortion

eess.SP ·2026-09-23 ·Fathima Razeeya Mohamed Razick, Syed Muhammad Ahsan, Petr Musilek
published similarity 0.61
Abstract · Accepted and presented at the IEEE Power and Energy Society General Meeting 2026, Montreal, Canada, July 19-23, 2026

The increasing integration of distributed energy resources introduces new challenges for accurate fault detection and classification in distribution networks. This paper presents a topology-aware graph convolutional network-based model for fault classification under inverter-induced harmonic distortion. The model uses pre-fault and post-fault voltage and current phasors, including harmonic components, mapped to the IEEE 34-bus system topology. The simulation data generated in OpenDSS encompass varying levels of penetration of solar photovoltaics (30%, 50%, 70%) and current total harmonic distortion (0%, 1%, 3%, 5%) across multiple fault types: single line-to-ground, line-to-line, double line-to-ground, and three-phase-to-ground. A differential evolution algorithm is employed to optimize the hyperparameters of the network, resulting in a three-layer model that achieves an F1-score of 0.98. Stress testing across scenarios confirms high robustness and minimal class confusion. The results demonstrate that a graph convolutional network-based model can effectively classify distribution faults under varying photovoltaic penetration levels and harmonically distorted conditions. Comparative analyses with convolutional neural network, long short-term memory, and multi-layer perceptron architectures demonstrate that the proposed model delivers superior classification performance, particularly under the most stressed condition with 70% photovoltaic penetration and 5% harmonic distortion.

0.48

A Topology-Aware Neural Network for Fault Location With Missing Measurements

eess.SY ·2026-10-27 ·Fan Jiang, Linhan Fang, Xingpeng Li, Kaushik Rajashekara
similarity 0.61
Abstract

This paper proposes a topology-aware neural network-based fault locator (TANFL) for radial distribution feeders, which uses voltage and current phasors obtained after the decay of fault induced transients, as well as feeder connection relationships and line parameters, as inputs. The shared bus encoder, bus readout module, and gated line readout module work together to identify the faulty bus or line and estimate the continuous fault location on the selected line. During training, explicit missing data indicators and random bus data block masking are introduced, enabling a single trained model to handle both complete measurement sets and scenarios where any permitted bus measurement device fails. On the IEEE 15 bus feeder, this paper compares TANFL with a conventional multilayer perceptron (MLP) and the formula-based localization method under identical data, measurement availability scenarios, and evaluation metrics. On the test partition, TANFL outperforms the conventional MLP; with complete measurements, its line fault location performance is slightly lower than that of the formula-based method, but in the average results for scenarios with one missing bus measurement block, its accuracy is the highest among the three methods at a 5% tolerance.

0.51

A Benchmark Graph Dataset for Transient Stability Assessment of the IEEE 9-Bus System: 20,000 Scenarios with Full Generator Trajectories

eess.SY ·2026-08-18 ·Hussein Suprême, Martin de Montigny, Arnaud Zinflou
publishedbenchmark similarity 0.58
Abstract · Descriptor Open dataset IEEE9

Transient stability assessment determines whether a power system retains synchronism after a large disturbance. Machine-learning surrogates can accelerate it, but progress is limited by the lack of open datasets that combine dynamic ground truth, network graph structure, and machine parameters. We release a benchmark of 20,000 three-phase-to-ground fault scenarios on the IEEE 9-bus system. Each scenario couples an AC power-flow operating point with a detailed electromagnetic-transient simulation of the post-fault response. Every record provides the network as an attributed graph (nine buses, eighteen directed branches, ten node and twelve edge features), the full rotor-angle and speed trajectories of the three generators, the static machine constants, the fault description, and a center-of-inertia binary stability label. Wide load and generation scalings across eighteen fault locations yield a near-balanced distribution (48.96\% stable, 51.04\% unstable). Generation is deterministic and fully reproducible through fixed seeds and public code. The dataset is distributed on IEEE DataPort under a persistent DOI and supports stability classification, trajectory prediction, margin and critical-clearing-time estimation, and the comparison of topology-aware, physics-based, and hybrid learning methods.

0.43

Cyber-physical attack detection approaches in the wide-area measurement system

cs.LG ·2026-10-30 ·Zakaria El Mrabet, Prakash Ranganathan
published similarity 0.57
Abstract

Improving situational awareness within the Smart Grid is an effective preventive measure to detect potential anomalies, and avoid their adverse consequences. A wide area measurement system (WAMS) based Phasor Measurement Unit (PMU) can assist in improving visibility within the grid by collecting relevant measurements including magnitude, phase angle, frequency, voltage, and current, with a precise GPS-based timestamp. So far, there are more than 2500 PMUs deployed in the North American power grid, where each of which generates between 30 and 60 samples/s, roughly 1.5 TB/month of streamed data. Thus, processing such large PMU streams requires expensive computational resources and faster algorithms. This paper provides state-of-the-art cyber and physical anomalies in the WAMS and analyses their impact on the integrity and availability of the system. Next, it investigates the current anomaly detection approach in historical and streaming PMU data, including conventional machine learning and hybrid approaches, and assesses their advantages and main drawbacks. Lastly, it sheds light on the importance of handling missing PMU data and concept drifts.

0.68

A Novel Open Phase Detection Method with Synchronized Phasors for Distribution Systems

eess.SY ·2026-08-23 ·Jinlei Xing, Longhua Mu
similarity 0.57
Abstract · 10 pages

An effective open phase detection is one of the unsolved challenges for utilities. Open phase detection is expected to detect the broken power line before it falls to the ground, to prevent the ignition of wildfires. The existing open phase detection methods are normally based on abnormal currents or voltages due to three phase unbalances after open phase events. For a complicated distribution feeder with multiple branches, current-based methods usually have a limited protection range, and voltage-based methods possibly failed due to the recreated voltage on the open phase due to back-feed. This paper presents a new open phase detection method based on the connection impedance of two measuring points, which is calculated with the synchronized phasors. Under an internal open phase condition, the calculated positive-sequence impedance is much larger than the impedance under other conditions, and its sign is negative. This new method is applicable for a distribution feeder with a closed-loop configuration, or DER units connected at the load side. It is almost not impacted by back-feed. This new method only requires point-to-point communication. This method can be easily implemented in the existing recloser controllers or RTUs. It is scalable, cost effective, and reliable.

0.30

A Systematic Evaluation of Machine Learning Methods for Fault Detection and Line Identification in Electrical Power Grids

cs.LG eess.SP ·2026-09-15 ·Julian Oelhaf, Georg Kordowich, Paula Andrea Pérez-Toro, Tomás Arias-Vergara, Andreas Maier +2 more
publishedhighly cited similarity 0.57
Abstract · Accepted at ICASSP 2025. 5 pages, 4 figures. Published version: DOI 10.1109/ICASSP49660.2025.10890544

The integration of renewable energy sources into the electrical grid introduces complex challenges in fault detection and coordination of grid recovery mechanisms. Traditional relay protection systems, which operate based on static rules and predefined thresholds, are inadequate for addressing these challenges, particularly in detecting and isolating faults such as short circuits. Consequently, the conventional methodologies applied to electrical network protection frequently fail to achieve optimal performance in fault detection, especially in terms of adherence to safety standards and the selective limitation of damage. Recent research indicates that machine learning (ML)-based approaches can effectively tackle these issues; however, variations in grid configurations and analysis windows have impeded consistent comparative assessments. In this study, we assess the efficacy of various ML models in detecting electrical faults and pinpointing defective transmission lines within a 10 ms measurement interval - a critical time-frame for real-time operational viability, for the first time. The most effective model attained an F1 score of 0.991 +/- 0.018 and demonstrated a processing time of 0.342ms +/- 0.509ms.

0.52

DER-Fault: A Simulation-Based Fault Dataset for DER-Integrated Distribution Systems Under Diverse Operating Conditions

eess.SP ·2026-09-28 ·Fathima Razeeya Mohamed Razick, Petr Musilek
similarity 0.56
Abstract · 10 pages, 4 figures, Associated dataset available on Zenodo

The growth of distributed energy resource (DER) integration introduces greater variability in distribution system operating conditions, creating a need for comprehensive datasets for developing and evaluating data-driven fault diagnostic methods. This paper presents \textbf{DER-Fault}, a simulation-based dataset generated in OpenDSS using the Iowa 240-bus distribution system with photovoltaic (PV) generation, electric vehicle (EV) charging, and vehicle-to-grid (V2G) operation. To capture annual load variability while maintaining a manageable number of simulation cases, 60 representative operating conditions are selected from 8,760 hourly load profiles, covering peak, off-peak, transition, typical weekday, and typical weekend conditions. Six DER scenarios with varying PV and EV penetration levels and V2G participation are considered. The dataset includes normal operation and ten short-circuit fault classes, with varying fault resistance. Pre- and post-fault voltage and line-current phasor measurements are recorded at selected measurement locations, resulting in 19,800 simulation cases. Technical validation demonstrates broad coverage of annual loading and DER operating conditions, distinct phase-specific responses corresponding to the simulated fault types, and a consistent reduction in voltage-phasor disturbance with increasing fault resistance. The resulting dataset provides a structured resource for developing and evaluating machine-learning and other data-driven methods for fault detection, classification, and localization in DER-integrated distribution systems.

0.26