SPARC: Substation-to-Peering Assessment of Resilience and Cascades

Tanya Shreedhar, Kevin Vermeulen, Amreesh Phokeer, Italo Cunha, Fernando Kuipers

cs.NI ·submitted 2026-10-14 12:09 UTC · v1

Abstract

Internet Exchange Points (IXPs) operate from colocation facilities that draw power from regional grids and store limited backup fuel. In April 2025, the Iberian blackout kept the Spanish grid down for 16 hours, beyond the 12 hours of fuel required by the industry standard, while traffic at major Iberian IXPs fell by up to 70%. Yet operators cannot tell which facilities a grid event cuts off, whether it outlasts their backup, or where traffic from a failed IXP goes. We present SPARC, which maps power-grid and Internet dependencies from substations to IXPs and their traffic. Using open data validated against transmission operators, SPARC links 552 facilities hosting 275 IXPs to the substations that likely feed them. We spread grid events over this map and measure failover through controlled BGP withdrawals on the PEERING testbed. Disabling the most-shared 16% of facility-feeding substations cuts power to half of all IXP presences (an IXP at one facility), under half of what randomized maps require. Losing the 5% most central substations cuts power to 0.1% of IXP presences directly but to 9-52% once the grid splits into disconnected islands. Traffic often fails over to nearby sites that share the failing grid: a cascade affecting four metropolitan areas sends up to 40% of one area's monitored addresses to another of the four. We introduce SPARC-Shield to select substations to harden or facilities whose backup to extend. Against an attacker disabling ten substations, hardening the ten selected by SPARC-Shield reduces offline IXP presence by 72%, compared with 52% for the best standard ranking.

Comment
40 pages, 17 figures, including appendices

Closest papers

Nearest neighbours by meaning across the whole index.

Grid Trouble in Paradise: Uncovering Vulnerable Distributed Energy Resources and Their Grid-Level Risks

cs.CR eess.SY ·2026-09-07 ·Anna Raymaker, Samuel Talkington, Zeezoo Ryu, Richard Asiamah, Emad Abukhousa +6 more
top venue similarity 0.58
Abstract · 20 pages, 10 Figures, To appear in the Proceedings of the 2026 ACM SIGSAC Conference on Computer and Communications Security (CCS '26)

Grid-connected solar distributed energy resources (DERs), such as solar inverters and monitoring platforms, have been deployed at unprecedented scale over the past few years, with global solar capacity more than doubling since 2022. To support monitoring and control, many of these systems are Internet-connected and configured by installers or end users, yet the real-world scale of their Internet exposure and the implications for power grid operation remain poorly understood. In this paper, we present an Internet-scale evaluation of exposed and vulnerable solar DER infrastructure, and assess the risk that compromised DERs can pose to energy grids. We develop a method for accurately identifying solar DERs from Internet scanning data, and discover a diverse population of over 66,000 Internet-exposed solar DERs. We detect that at least 10,000 of these DERs may have known CVEs, such as unauthenticated monitoring and control endpoints. To assess the risk that these vulnerable DERs pose to a power grid, we use an electric grid network for Oahu, Hawaii, established and used by the power system research community, and conduct a power system analysis. Our evaluation shows that by compromising exposed DERs, attackers can cause voltage and line flow violations across multiple locations in the Oahu network, resulting in a range of consequences from degraded power quality to damaged power system components to power outages. Ultimately, our work brings to light the emerging threat of grid-connected DERs, and provides directions for improving energy security.

0.44

Disjoint in Name Only: Illusory Resilience in the Internet

cs.NI ·2026-10-19 ·Subhadeep Sahoo, Hrishikesh B Acharya
similarity 0.55
Abstract

Internet path diversity is usually verified at the logical layer: two alternatives may share no AS or IP link yet traverse the same facility, conduit, or submarine landing zone. We call this gap illusory resilience and define the Illusory Resilience Index (IRI) as the latent hazard-weighted physical overlap of a logically disjoint path pair. To detect such hidden exposure without carrier underlay maps, we audit three public signals: correlated BGP withdrawals during documented physical incidents, operator interconnection-footprint overlap, and shared submarine landing zones. Two signals survive calibration; the 60-second BGP signal does not. Across 47 operators in ten regions, same-region pairs have substantially greater listed facility overlap than cross-region pairs, and one Marseille campus colocates 153 operator pairs. Across 68 cable systems in twelve corridors, 31-100% of candidate within-corridor pairs share a 25 km coastal hazard zone; two corridors are fully saturated, and the same rule recovers ten of eleven cable pairs documented as co-damaged in 2024. The rejected temporal predicate has a 0.444 null firing rate and no hits among twelve monitored positive pairs. Public data therefore expose substantial shared-risk structure behind nominal diversity and identify where stronger physical-path verification is warranted.

0.28

Data Center Load Reductions: Attribution, Measurement Limits, and Estimation

eess.SY ·2026-10-28 ·Abdallah Alalem Albustami, Ahmad F. Taha, Mohammad Alwahdanee, Zuhaib Shakeel Muhammad
similarity 0.54
Abstract

Hundreds of gigawatts of data center loads are seeking interconnection in the United States given the massive growth of artificial intelligence and cloud computing. In recent years, several incidents of data centers reducing their loads by hundreds to thousands of megawatts have been documented, raising grid reliability concerns. U.S. regulators have since ordered reliability standards for the integration of computational loads, and the North American Electric Reliability Corporation (NERC) now calls on transmission owners to install disturbance recorders at these facilities to support root cause analysis. Such recorders usually observe only electrical quantities at the point of interconnection (POI). A sudden load reduction can be caused by a change in workload or a switch to backup supply. This work shows when POI measurements can distinguish the two mechanisms. It is established that they can produce identical POI voltage and current in a quasi-static constant power model, and during the transient their separation depends on the reduction relative to measurement noise, the clearing time, the dynamics through which workload reaches the POI, and the recorder bandwidth. When POI data are insufficient, an estimator that uses workload data is proposed to determine how much of the facility stayed connected. The results of this work identify the measurements and grid information utilities need to determine why data center load dropped.

0.31

RIPE Atlas Measurements and Geolocation Providers: A Longitudinal Consistency Evaluation

cs.NI ·2026-10-19 ·Jonatas Marques, Oliver Gasser
similarity 0.54
Abstract · New Directions in IP Geolocation (NewGeo) Workshop, Monday, October 12, 2026 - Karlsruhe, Germany

IP geolocation supports many Internet services and operations, including but not limited to content delivery, fraud detection, content localization, and regulatory compliance. However, assessing the reliability and accuracy of IP geolocation providers is challenging and only partially explored. In this paper, we present a longitudinal study evaluating the consistency between RIPE Atlas latency measurements and location estimates from four popular geoproviders as a proxy for geolocation quality. Analyzing six months of data we observe mostly stable consistency levels through time, with fluctuations largely related to changes to the mix of targets being measured by RIPE Atlas each day. We also observe that consistency levels can differ greatly between geoproviders, with IPinfo leading DB-IP (the next best) by 5.4 percentage points for IPv4 and 11.5 percentage points for IPv6. Finally, the analysis reveals distinct degradation patterns across providers for different subsets of IP addresses. For example, for IPv4 router addresses, MaxMind consistency is 10.7 percentage points worse than in the general case while IPinfo is only 1.6 percentage points worse; for IPv6, the pattern flips and routers are geolocated more consistently than non-routers by all providers.

0.32

EnergyNet in Practice: Long Grid, Short Grids and Mobility-Based Energy Peering

eess.SY ·2026-10-07 ·Jonas Birgersson, Max Collins, Marc A. Weiss, Jimmy Chen, Daniel Kammen +8 more
position similarity 0.53
Abstract

Electrification is planned as a network problem: more demand, more upstream capacity, local resources waiting for reinforcement. We argue that a material part of that bill, in money and time, follows from architecture, not electrification itself, and propose the Short Grid as the deployment unit: a locally controlled building, block or campus whose demand, generation, storage and local market operate behind Energy Routers enforcing an approved connection envelope to the Long Grid. Because the envelope governs exchange, not installed capacity, local resources can grow and many sites can build in parallel at the pace of PV and EV installation, not grid reinforcement. PV and EV batteries dominate today, but the architecture is general: any generation or storage, fixed or mobile, fits behind the same boundary and interfaces. EnergyNet Operators coordinate exchange among Short Grids and with the Long Grid; protection stays local; Vehicle-to-EnergyNet (V2EN) and Mobility-Based Energy Peering (MEP) make mobility-financed batteries accessible within and between them; priority-based operation protects critical services in shortage. We test it in models, not yet the field: a ten-building neighbourhood in Lund, Sweden; a bus-linked microgrid pair at Stanford and Half Moon Bay; and a proposed 20-site network in Rockaway, New York. Households and services are the largest demand category in Sweden, Denmark, Norway, California and New York (484 TWh/yr); halving their grid imports would be about 242 TWh. Europe's network investment to 2040 is estimated above EUR 1.2 trillion; modelling shows it depends on system design. Negagrid value, following the negawatt, counts network investment avoided, downsized or deferred, net of local substitute costs. "Don't pay twice": build coordinated local capability first; reinforce the Long Grid for what remains.

0.19

EPIGRIDS: Documentation and Validation of Seven Open Synthetic Transmission Grid Cases

eess.SY math.OC ·2026-11-13 ·Jonathan M. Snodgrass, Scott Greene, Thomas J. Overbye, Christopher L. DeMarco, Bernard C. Lesieutre
benchmark similarity 0.53
Abstract · 10 pages, 2 figures, 6 tables. Submitted to the IEEE Open Access Journal of Power and Energy. Cases: https://doi.org/10.5281/zenodo.23814538…

This paper documents and checks EPIGRIDS, seven open synthetic transmission grid cases from four independently built networks, made with an optimization-based construction method instead of the graph-statistics method behind most large public synthetic grids. The cases range from 250 to 78,484 buses, with geolocated substations, voltages up to 765 kV, and line parameters taken from conductor data. Each ships under an open license in three common power flow formats that agree at the solved operating point, and the six larger cases have a companion hourly, bus-level load series for one year. The Texas, Florida, and Michigan, Ohio, and Indiana cases are sub-networks of the Eastern case. Every case solves an alternating-current power flow from its stored operating point. With parallel circuits merged, the Eastern and Western cases are 9 and 16% denser than the real interconnections, while graph-statistics cases on the same footprints lie within 6% and meet more published realism criteria. A full single-outage contingency analysis completes on every case, and in an optimal power flow benchmark every case except the New England base case and one of its 12 operating points solves in polar form.

0.40

A Community Impact-Centered Network Reduction Method for Power Systems Resilience Planning

eess.SY ·2026-10-27 ·Jiarui Gao, Abigail L. Beck, Rabab Haider
similarity 0.52
Abstract

Power systems resilience planning requires evaluating many hazard scenarios and investment portfolios, often requiring network reduction for computational tractability. The resulting aggregation, however, can obscure community impact data needed for equitable planning. We present a network reduction method that jointly preserves network physics and the spatial distribution of community data. We embed a household-level scarce resource score that characterizes outage impact within optimization-based Kron reductions with two formulations: a scarcity-weighted method that prioritizes vulnerable nodes, and a scarcity-constrained method that bounds data dissimilarity within aggregated clusters. Both are evaluated on a realistic distribution feeder of Galveston Island, Texas and benchmarked against multiple approaches. The scarcity-constrained method performs best, achieving 86% reduction with worst-case voltage errors below 0.01p.u. while preserving the spatial distribution of community data. By explicitly controlling data heterogeneity within and across clusters, the proposed method yields reduced networks that retain decision-relevant community information without sacrificing electrical accuracy.

0.29

Slasher: Power Flexibility for Cloud Datacenters

cs.DC cs.OSeess.SY ·2026-08-26 ·Liuzixuan Lin, Fiodar Kazhamiaka, Alok Gautam Kumbhare, Chaojie Zhang, Jaylen Wang +8 more
similarity 0.52
Abstract · 18 pages, 15 figures

Datacenters consume many megawatts of power, and regularly encounter scenarios that require modulating their power draw. These scenarios include datacenter infrastructure failures, power grid failures, grid services, and more, spanning a diverse range of requirements in terms of the power magnitude, the scope of the reduction, the notice time, and other dimensions. To address these scenarios, we have built Slasher, a general system for modulating the power of \azure datacenters to handle scenarios ranging from individual racks to regional multi-datacenter grid events. Slasher coordinates datacenter resources with the goal of meeting power targets while minimizing negative impact on hosted workloads. In this paper, we review the main power modulation scenarios, characterize the power reduction levers using data from production cloud datacenters, describe Slasher's system architecture, and formulate the cloud datacenter power modulation control problem. We also develop a high-fidelity datacenter simulator and propose a workload impact model, using them to design and evaluate power control algorithms.

0.31