EPIGRIDS: Documentation and Validation of Seven Open Synthetic Transmission Grid Cases

Jonathan M. Snodgrass, Scott Greene, Thomas J. Overbye, Christopher L. DeMarco, Bernard C. Lesieutre

eess.SY math.OC ·submitted 2026-11-13 18:17 UTC · v1
benchmark

Abstract

This paper documents and checks EPIGRIDS, seven open synthetic transmission grid cases from four independently built networks, made with an optimization-based construction method instead of the graph-statistics method behind most large public synthetic grids. The cases range from 250 to 78,484 buses, with geolocated substations, voltages up to 765 kV, and line parameters taken from conductor data. Each ships under an open license in three common power flow formats that agree at the solved operating point, and the six larger cases have a companion hourly, bus-level load series for one year. The Texas, Florida, and Michigan, Ohio, and Indiana cases are sub-networks of the Eastern case. Every case solves an alternating-current power flow from its stored operating point. With parallel circuits merged, the Eastern and Western cases are 9 and 16% denser than the real interconnections, while graph-statistics cases on the same footprints lie within 6% and meet more published realism criteria. A full single-outage contingency analysis completes on every case, and in an optimal power flow benchmark every case except the New England base case and one of its 12 operating points solves in polar form.

Comment
10 pages, 2 figures, 6 tables. Submitted to the IEEE Open Access Journal of Power and Energy. Cases: https://doi.org/10.5281/zenodo.23814538; load series: https://doi.org/10.5281/zenodo.24151084; construction method: arXiv:2611.16222

Closest papers

Nearest neighbours by meaning across the whole index.

GridForge: A Tractable Network-Flow Method for Constructing Open, Continental-Scale Synthetic Power Grids

eess.SY ·2026-11-12 ·Jonathan M. Snodgrass, Thomas J. Overbye, Christopher L. DeMarco, Bernard C. Lesieutre
similarity 0.76
Abstract · 30 pages, 10 figures, 7 tables; supplementary material as an ancillary file. Submitted to the International Journal of Electrical Power & En…

The goal of this paper is to construct open, continental-scale synthetic transmission grids with an optimization method that stays tractable. Security restrictions keep models of the real grid out of open research and machine-learning datasets, and optimization-based construction is hard at scale: the number of candidate lines grows combinatorially, so electrically faithful methods prune the candidates in advance. This paper presents GridForge, which keeps every bus pair within physical length limits as a candidate, selects lines with Garver's length-weighted network-flow linear program instead of binary decisions, and resizes them with a sequential direct-current (DC) power flow. Two stages of 13 regional networks are evaluated. Their node-degree distributions are nearly as strongly log-linear as those of the real Eastern and Western Interconnections ($R^2$ of 0.92 to 0.98 against 0.971 and 0.981), although the areas under the fitted lines differ from the real ones by 39.9% on average. On the upper Midwest and Tennessee Valley footprints, resizing lowers the DC power-flow loss from 5.89% to 4.14% and from 14.55% to 7.05%, and the DC optimal power-flow loss from 4.03% to 2.02% and from 5.54% to 2.47%. Without relaxing any line limit, the DC optimal power flow is feasible in 78.81% and 0.82% of the scenarios. Most lines are built at 69 kV. The models span 250 to 78,484 buses, were built on single machines, and are freely redistributable.

0.62

Time to AC-t: When AC-transmission changes capacity expansion planning

eess.SY math.OCphysics.soc-ph ·2026-11-02 ·Lara Booth, Shiva Madadkhani, Ruaridh Macdonald, Priya L. Donti
code/data similarity 0.63
Abstract · 35 pages, 5 figures, 3 tables; plus 16 pages of supplemental information (8 figures, 6 tables). Submitted to Joule

Capacity expansion models often dramatically simplify the physics of how power flows through a transmission network in order to preserve computational tractability. However, with the rapid growth of electrification, large loads, renewables, and storage, increased realism in planning future grids is imperative. We extend the open-source capacity expansion model GenX with AC optimal power flow physics, and analyze generation, storage, and transmission investment decisions for 20-zone, hourly models of Germany and Texas. We compare our results against those using two common approximations, the transport model and DC optimal power flow. We find that total costs and emissions largely agree across all formulations. However, we find substantial differences in outputs related to transmission, generation siting, storage, and reactive-power support between the approximate formulations and the true AC physics formulation. We identify where AC physics changes planning decisions and discuss how to potentially capture these effects without the full computational cost.

0.23

Expediting AC Contingency Analysis using a Basecase Machine Learning Model

eess.SY ·2026-09-29 ·Md Obaidur Rahman, Vassilis Kekatos
similarity 0.62
Abstract · 10 page, 7 figures

Grid planning and operation under increasingly variable operating conditions require fast and accurate AC power flow (AC-PF) contingency analysis for numerous line outages. While ML models can accelerate these computations, existing approaches often require either training separate models for different contingencies or a single model using data from multiple topologies. Both approaches incur substantial offline data generation and training costs. To address this gap, this work proposes a fixed-point framework that reuses a single ML model trained exclusively on basecase topology data to predict post-contingency AC-PF states under any non-critical single-line outage. We analyze the proposed method's convergence under the DC model approximation and derive its convergence rate in terms of network parameters. As a side result, we show that power transfer distribution factors (PTDFs) for non-critical lines have magnitudes less than one. We further characterize the ML training region to accommodate PF specifications encountered during fixed-point iterations and derive bounds on ML prediction errors for post-contingency state estimates. Numerical tests on a 6,717-bus synthetic Texas system demonstrate convergence across all non-critical single-line outages, with prediction errors remaining close to those of basecase. The proposed framework offers a favorable tradeoff between the speed of DC solvers and Newton-Raphson accuracy.

0.11

Benchmarking a Grid Foundation Model for AC Optimal Power Flow: Feasibility and Warm-Start Results on Synthetic Texas and South Carolina Grids

eess.SY ·2026-11-17 ·Tam Kemabonta, Brighton Ombuki, Vladimir Abdelnour
similarity 0.62
Abstract · 5 pages, 3 figures, 2 tables. Submitted to the 2027 IEEE PES General Meeting

Learning-based surrogates for alternating-current optimal power flow (AC-OPF) are often judged by the gap between their objective value and that of a nonlinear solver, which does not show that a prediction satisfies power balance and network limits. This paper tests whether predictions from the pretrained foundation model GridSFM-Open 1.1.0, recently released by Microsoft, are feasible AC-OPF operating points and whether they are useful initial values for a nonlinear solver. The model was evaluated zero-shot and after fine-tuning on 10, 100, and 1,000 labeled scenarios (FT10, FT100, and FT1000) on 500 scenarios for each of two synthetic grids, ACTIVSg2000 (Texas) and ACTIVSg500 (South Carolina), with Ipopt, MATPOWER MIPS, and pandapower PIPS as solver references. The lowest Texas median cost gap, 0.44\% for FT100, coincided with thermal violations in 24.1\% of cases and a median maximum bus power mismatch of 89 MW and 197 Mvar. Texas zero-shot predictions had a median maximum mismatch of 648 MW and 1,641 Mvar, and every South Carolina case violated a thermal limit for every model variant. Seeding Ipopt with FT1000 predictions gave geometric-mean solve-time speedups of 1.55x on South Carolina and 1.12x on Texas (p = 0.06, not significant at the 5\% level), while zero-shot seeds slowed South Carolina solves (0.26x). A small objective gap therefore did not indicate feasibility: although median zero-shot inference took only 1.32 s on Texas and 0.157 s on South Carolina on a shared host, every prediction still required a nonlinear solver, and fine-tuned predictions gave modest, grid-dependent warm-start speedups while zero-shot predictions slowed convergence on one grid. GridSFM may therefore be useful for initializing a nonlinear solver, but obtaining feasible AC-OPF solutions still required the solver.

0.32

Topology-adaptive Estimation of Maximum Voltage Unbalance for Distribution Networks with Finite-sample Guarantee

eess.SY ·2026-10-14 ·Jinbao Wang, Jun Liu, Shiliang Zhang, Xuehui Ma, He Zhang
similarity 0.62
Abstract

High penetration of single-phase distributed power production and frequent topology changes can significantly increase voltage unbalance in distribution networks. Reliable probabilistic power flow (PPF) assessment for the network, therefore, must account for topology-dependent power-flow equations, numerical error in the voltage unbalance factor (VUF), and finite-sample uncertainty in power measurements. In this paper, we propose Topology-Adaptive Certified Quantile Estimation (TACQE) to estimate the maximum VUF across monitored electric buses. Following a local network change, TACQE updates the cross-couplings among power-flow sequences, and certifies candidate PPF solutions against the updated nonlinear equations. The resulted power-flow state enclosures provide rigorous bounds on the maximum VUF. Furthermore, we derive independent reference-solver evaluations to calibrate discrepancies from the reference PPF solution. This leads to a uniform sampling bound that yields simultaneous upper-tail probabilities and quantiles, which provides a finite-sample guarantee for the estimated maximum-VUF distribution over an entire range of VUF thresholds. From our numerical simulations across 101 fixed-topology quantiles, it demonstrates that the designed TACQE can provide a fast candidate post-change power flow solution where it reuses most of the previous network model and modifies only the affected bus blocks.

0.17

A unified power-grid representation for reuse across network structures and computational tasks

eess.SY ·2026-09-07 ·Yanhao Huang, Changqing Liu, Zichang Wang, Qianhong Wu
similarity 0.61
Abstract

Data-driven power-system models are typically developed for specific grids and computational tasks, but their performance can deteriorate markedly or even fail when network structures or analytical objectives change. This paper develops a unified grid representation that separates physical-grid description from downstream computation. A self-supervised encoder represents each grid as a variable number of fixed-dimensional node, branch and global vectors under a common latent description. Although pretrained only on systems with at most 270 buses, the frozen encoder transfers without adaptation to a 70,000-bus network, more than 250 times larger in bus count, while preserving 0.7919 bus-correspondence accuracy. The same representation supports four independently trained downstream tasks: power-flow calculation, reactive-power adjustment, operating-condition generation and transient-stability assessment. On the previously unseen 70,000-bus grid, power-flow calculation achieves mean errors of 0.108$^{\circ}$ in phase angle and 3.8$\times$10\textsuperscript{-6} p.u. in voltage magnitude. Reactive-power adjustment achieved a 75\% PSASP-verified correction rate on the previously unseen 70,000-bus grid, while operating-condition generation delivered at least one PSASP-verified feasible state for 82.2\% of requests on previously unseen 400--1,000-bus grid families. For transient-stability assessment, the frozen encoder achieves accuracy within 0.8 percentage points of full encoder adaptation under matched training conditions. These results demonstrate that a unified power-grid representation can be learned once and reused unchanged across structurally different power systems and heterogeneous computational tasks.

0.47

Steady-State Equivalent Circuit Model for Data Center Loads

eess.SY ·2026-08-18 ·Muhammad Hamza Ali, Peng Sang, Hyeon Woo, Hyein Kang, Sungyun Choi +1 more
similarity 0.61
Abstract

Planners currently represent data centers as aggregate constant-PQ or ZIP loads in steady-state interconnection and contingency studies. These aggregate models are computationally convenient. However, they obscure the electrical relationship between computational workloads, server utilization, and grid-side demand. They ignore the internal power-electronic conversion stages of IT loads and assume homogeneous workload distributions across the compute clusters. This hides operating-point-dependent converter losses and efficiency variations. We propose a steady-state equivalent-circuit model (ECM) for data centers, which explicitly builds circuit models for IT loads, power supply units, cooling, and auxiliary systems. For power supply units, the equivalent circuit model explicitly represents internal power-electronic conversion stages. For IT loads, we develop a utilization-dependent server power model, and we combine it with loss-aware ECMs of power supply units. This approach captures the grid-side impact of heterogeneous workload distributions while preserving compatibility with conventional power-flow analysis. We evaluate this data center ECM in large-scale transmission power flows, using Monte Carlo simulations under heterogeneous and homogeneous cluster utilization. In comparison with the fixed-efficiency constant-PQ model, the ECM predicts that the most stressed line exceeds its thermal limit in about 30% of Monte Carlo samples. The results further show that homogeneous server utilization overstates line-loading variability by 17%-46% relative to heterogeneous server utilization, depending on the intra-cluster workload correlation.

0.47

Grid Topology Optimization for Congestion Management Under High Renewable Penetrations and Discrete Load Growth

eess.SY ·2026-09-13 ·Giacomo Bastianel, Hakan Ergun, Line Roald
similarity 0.60
Abstract

Transmission grids are increasingly stressed by the fluctuating nature of renewable energy sources and by increasing electricity demand. Such grids were mainly built for a different generation fleet and load conditions. Grid topology optimization offers the possibility to redistribute power flows by modifying the busbar topology of substations in the grid. However, the combinatorial explosion of feasible busbar configurations makes topology optimization impractical for system operators. This paper proposes a methodology to identify a small subset of high-value busbar topologies to capture the economic benefit of topology optimization across a range of renewable-demand patterns. The optimization model is based on a LPAC approximation of the optimal power flow formulation, and AC-feasibility checks of the optimal topology applied to the IEEE 118-bus test case. In the test case, we select two distinct pairs of substations (46-49 and 24-69) and we optimize their topology separately over 365 clustered timesteps with different wind and load conditions. For each pair, we identify the four most recurrent optimal topologies and evaluate their performance under standard, and congested conditions, with and without a discrete load growth. Results show that selecting from this reduced set of topologies reduces total generation costs by up to 0.147% compared to a plain AC-OPF. In addition, we show the influence of topology optimization on the hosting capacity of selected busbars under discrete load growth. Our findings provide a practical methodology for system operators to select a subset of optimal busbar topologies to be used in their grid for different wind-load conditions, resulting in decreasing generation costs without the computational and operational risks of real-time switching decisions.

0.24