Reinsertion-Aware Parameter Estimation of the WECC Composite Load Model via Closed-Loop Equivalent-Network Co-Estimation

Jong Ha Woo, Victor Daldegan Paduani, Zishuo Yang, Yu Ma, Qi Xiao, Ning Lu

eess.SY ·submitted 2026-10-25 18:55 UTC · v1
benchmark

Abstract

Measurement-based parameter estimation of the WECC composite load model (CMLD) commonly relies on voltage replay, where measured voltage is imposed on an isolated CMLD and its parameters are optimized to reproduce measured active and reactive power. However, this open-loop formulation neglects the two-way dynamic interaction between the load and grid, potentially causing large errors when the estimated model is reinserted into dynamic grid simulations. To address this limitation, we propose a closed-loop parameter estimation framework that alternately estimates the CMLD parameters and a five-parameter equivalent network representing the external grid. This framework restores load-grid interaction during estimation and enables voltage, active power, and reactive power to jointly constrain the parameter estimation. Compared with four baseline methods, the proposed approach achieves the highest reinsertion accuracy in both the CMLD benchmark and transmission and distribution (T&D) co-simulation environments. In the T&D case, it reduces active-power, reactive-power, and voltage errors by 73%, 64%, and 62%, respectively. The identified model also maintains improved reinsertion accuracy under disturbances not used for estimation, demonstrating transferability beyond the identification event.

Comment
10 pages, 10 figures, 7 tables. Submitted to IEEE Transactions on Power Systems

Closest papers

Nearest neighbours by meaning across the whole index.

Topology-adaptive Estimation of Maximum Voltage Unbalance for Distribution Networks with Finite-sample Guarantee

eess.SY ·2026-10-14 ·Jinbao Wang, Jun Liu, Shiliang Zhang, Xuehui Ma, He Zhang
similarity 0.60
Abstract

High penetration of single-phase distributed power production and frequent topology changes can significantly increase voltage unbalance in distribution networks. Reliable probabilistic power flow (PPF) assessment for the network, therefore, must account for topology-dependent power-flow equations, numerical error in the voltage unbalance factor (VUF), and finite-sample uncertainty in power measurements. In this paper, we propose Topology-Adaptive Certified Quantile Estimation (TACQE) to estimate the maximum VUF across monitored electric buses. Following a local network change, TACQE updates the cross-couplings among power-flow sequences, and certifies candidate PPF solutions against the updated nonlinear equations. The resulted power-flow state enclosures provide rigorous bounds on the maximum VUF. Furthermore, we derive independent reference-solver evaluations to calibrate discrepancies from the reference PPF solution. This leads to a uniform sampling bound that yields simultaneous upper-tail probabilities and quantiles, which provides a finite-sample guarantee for the estimated maximum-VUF distribution over an entire range of VUF thresholds. From our numerical simulations across 101 fixed-topology quantiles, it demonstrates that the designed TACQE can provide a fast candidate post-change power flow solution where it reuses most of the previous network model and modifies only the affected bus blocks.

0.17

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.59
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.25

Equivalent Modeling of Load-Side Systems With Distributed Renewable Generation Considering Fault Responses and Nodal Voltage Coherence

eess.SY ·2026-09-21 ·Yuqi Cao, Chen Shen, Shaowei Huang, Ying Chen, Hongyi Zhu
similarity 0.57
Abstract · Submitted to IEEE Transactions on Power Systems

Operating conditions and fault severity change both the initial states and control modes of active distribution networks. Direct capacity aggregation can therefore lose the power responses required for transmission-system dynamic analysis. This paper develops a procedure for generating low-order physical electromagnetic transient equivalents from a small set of representative operating conditions. Device power, ride-through states, load mechanical states, and local sequence voltages are combined with electrical distance to form response families. Response reconstruction and terminal simulation errors determine the retained architecture, after which bounded sensitivity calculations determine effective dynamic coefficients. The architecture and coefficients are then fixed. For a new operating condition, capacity and power balances, voltage-dependent load relations, and an initialization correction generate the model parameters from static inputs and power-flow results. A representative severe fault establishes a template for each fault type, which is reused across fault depths. Aggregation and switching-time bounds explain the roles of voltage coherence and state separation. Comparisons with direct aggregation show improved terminal responses across operating conditions and several fault types, with the largest gains under severe unbalanced faults. The method provides a reusable physical equivalent for operating-condition studies and fault-depth screening.

0.17

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.57
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Identifiability-Guided Composite Load Modeling of AI Data Centers

eess.SY ·2026-10-14 ·Ding Lin, Jianhui Wang, Meng Yue, Tianqiao Zhao
similarity 0.56
Abstract

The rapid growth of AI data centers introduces large, workload-dependent loads whose protection and reconnection behavior can affect power-system transient stability. Calibrating dynamic models of such loads is challenging because treating all associated elements as freely estimable may lead to weakly identified or physically confounded parameterizations. This paper proposes an identifiability-guided calibration framework for a composite load model with separate IT, cooling, and auxiliary branches. A nuisance-projected Fisher-information criterion characterizes the local identifiability of the cooling-motor composition, while a workload non-equivalence result shows that voltage-only recalibration cannot reproduce workload-dependent responses. Guided by these results, a grey-box estimator trained with branch-level supervision learns the workload-to-power relation and the cooling composition, while retaining a prescribed UPS protection law and an externally anchored reconnect-ramp duration. The learned workload relation is then distilled into a closed form for transient-stability simulation. Evaluation using 300,000 MIT Supercloud GPU power-utilization samples and 12,600 IEEE 39-bus fault scenarios yields an aggregate active-power $R^2$ of 0.948, compared with 0.856 for an LSTM baseline. Removing branch-level supervision preserves relatively high aggregate accuracy but substantially degrades cooling-component recovery. Under unseen deep voltage sags, the proposed model achieves a transient $R^2$ of 0.750, compared with 0.033 for the LSTM. Closed-loop simulations further show that cooling composition and protection behavior can affect retained-load states and voltage responses near protection thresholds.

0.20

Efficient Co-simulator Integration with Application to Smart Grids

cs.NI ·2026-09-02 ·Talha Ibn Aziz, Jihoon Og, Ioanis Nikolaidis, Omid Ardakanian
benchmark similarity 0.56
Abstract · 12 pages

The evolution of the electric power grid towards a ``smart grid'' is an example of an emerging large-scale cyber-physical system. To study the potential of cyberattacks or other sources of extreme events, high-fidelity co-simulation is one of the few realistic strategies. In this work, we demonstrate a practical and high-performance co-simulation strategy for smart grids, which provides lessons about co-simulation integration that can be carried over to other cyber-physical systems. Specifically, we present a co-simulation platform based on the Mosaik framework that integrates several federates including OpenDSS for power flow, a refined NS-3 for communication networks, and custom Python-based simulators for on-load tap changer control, distributed state estimation, and data collection. We compare synchronization strategies -- exhaustive lock-step time advancement versus an optimized event-driven approach that exploits lower-bound time stamps (LBTS) and next-event prediction -- and introduce targeted refinements to NS-3 event handling and relevance filtering of internal events. Performance is evaluated on two standard IEEE benchmark systems: the 13-node test feeder with tap-changer voltage regulation and a large-scale 33-bus system augmented with 32 European low-voltage feeders (1,793 nodes total) performing distributed state estimation with thousands of phasors and smart meters. Experimental results demonstrate that the refined event-based synchronization that uses LBTS-based NS-3 event filtering reduces execution time by up to 50\% over non-filtered LBTS, and more than 4$\times$ in the tap control scenario compared to naïve lock-step methods, while strictly preserving temporal correctness and simulation accuracy.

0.27

AIDC Microgrid Vulnerability Assessment Under Computing-Power Coordinated Attacks

eess.SY ·2026-08-11 ·Ze Yu, Hongwei Zhen, Chao Shen, Mingyang Sun
similarity 0.56
Abstract

The rapid growth of large language model (LLM) services is expanding AI data centers (AIDCs), increasing electricity demand and associated carbon emissions. Renewable energy integration can mitigate these impacts but also strengthens the coupling between AIDC loads and inverter-interfaced generation, creating cross-domain cyber-physical vulnerabilities. Specifically, adversarial AI requests alter AIDC power demand, whereas inverter control tampering modifies source-side dynamics, and their combined impact on system stability varies with generation forecast and demand response uncertainties. To this end, we propose an uncertainty-aware AIDC microgrid vulnerability assessment framework under computing-power coordinated attacks. First, the framework maps adversarial AI requests to AIDC power variations and represents uncertainties in attack-induced demand responses and photovoltaic (PV) forecasts through confidence-weighted realizations. Then, impedance based stability analysis combines these realizations with bounded inverter parameter tampering to construct attack reachable domains and identify critical attack time windows. Furthermore, a separate criterion identifies fixed coordinated attack vectors that retain destabilizing capability throughout each selected window. Case studies demonstrate that, unlike either attack component applied alone, coordinated attacks within identified critical windows induce sustained inverter frequency oscillations with peak absolute deviations exceeding 20% of nominal frequency, whereas the evaluated out-of-window response remains bounded. The proposed method further identifies critical attack windows and the associated coordinated attack vectors.

0.04

Trajectory Sensitivity-Based Dynamic Assessment of an AI Data Center Under Contingencies

eess.SY ·2026-10-07 ·Arnav Bagga, Saskia A. Putri, Abhishek Banerjee, Xiaofan Wu
similarity 0.56
Abstract · 7 pages, 5 figures

Artificial Intelligence (AI) data centers are emerging as converter-dominated, parameter-rich electrical systems whose dynamic response depends on fast workload-driven demand variations, tightly regulated data-hall converters, and coordinated on-site sources. Assessing such systems by repeatedly solving nonlinear time-domain models for every outage, load realization, and parameter perturbation is computationally expensive and provides limited insight into response sensitivity. This paper presents a trajectory sensitivity (TS)-based dynamic assessment framework for a self-contained AI data center supplied by a 2 kV DC microgrid with a grid-tied interface. The model includes time-varying data-hall load profiles, a voltage source converter (VSC), battery energy storage systems (BESS) units, supercapacitors, and synchronous-generation-side sources. For each disturbance, firstly, TS are computed along the nonlinear disturbance trajectory, capturing the local effect of source trips, data-hall outages, converter controls, and load ramps. Later, the computed TS data is used to estimate system trajectories under simultaneous parameter perturbations. Validation against full nonlinear ODE simulations with $\pm 15\%$ perturbations shows close agreement. In addition, the TS-based approach reduces computational time of dynamic-response evaluations from seconds to milliseconds, demonstrating its potential as a scalable screening tool for AI data center dynamics.

0.17