CS Paper Radar

Data-driven Linearization of Operational Dynamics of Soft Open Points in Power Distribution Networks

Shoaib Hussain, Mostafa Farrokhabadi, Hamidreza Zareipour

eess.SY ·submitted 2026-11-19 00:03 UTC · v1
hot direction

Abstract

This paper proposes a novel data-driven linearization of operational power losses in a Soft Open Point (SOP). The proposed learning-based representation, combined with the standard segmentation of the quadratic device capacity inequalities, linearizes the operational dynamics of SOPs in unbalanced power distribution network applications without a significant drop in power loss estimation accuracy. The technique was tested in three applications using a three-phase extension of the IEEE 33-bus network. The case studies include a sizing application for a multi-terminal phase-changing soft open point (PCSOP), an operational optimization application for an active distribution network featuring a PCSOP, and a system simulation engine built for a Deep Reinforcement Learning (DRL) application that trains an agent to optimally dispatch a PCSOP in an unbalanced distribution network. The results of the three case studies were validated against the standard nonlinear AC load-flow representations and point to the efficacy of the proposed solution.

Comment
7 pages, 7 figures, 5 tables

Closest papers

Nearest neighbours by meaning across the whole index.

Scalable Self-Supervised Learning for Multiphase AC-OPF in Distribution Systems with Topology Reconfiguration

eess.SY cs.LGmath.OC ·2026-08-25 ·Hoang T. Nguyen, Shaohui Liu, Reetam Sen Biswas, Varsha Pendyala, Nurali Virani +2 more
similarity 0.65
Abstract · Source code will be published following the review process

The proliferation of distributed energy resources (DERs) in distribution grids enables the active coordination of these assets to reduce costs and enable cleaner operations. Realizing this potential requires solving multiphase AC optimal power flow (AC-OPF) quickly across varying loads, DER availabilities, and topology reconfigurations, at much greater speed and scale than conventional nonlinear solvers. Learning-based surrogates can offer millisecond inference, yet existing methods target largely balanced transmission systems and do not scale to the multiphase, unbalanced, and reconfigurable nature of distribution feeders at utility scale. We present the Penalty + Sequential Linearized Feasibility Seeking (SLFS) algorithm, a self-supervised learning framework for multiphase distribution AC-OPF under switch-induced topology changes. Penalty+SLFS requires no labeled optimal solutions and trains directly from the AC-OPF objective and constraints through a differentiable fixed-point power flow solver, avoiding expensive label generation and admitting robust training procedures. Topology changes are handled efficiently using Sherman-Morrison-Woodbury updates of the admittance-matrix inverse, while an M-step Jacobian approximation accelerates differentiation through the power flow solver. At inference, SLFS repairs any infeasible predictions, providing feasibility guarantees with low computational overhead. On IEEE feeders ranging from 13 to 8,500 nodes, Penalty+SLFS achieves negligible optimality gaps and near-zero constraint violations, delivers up to three orders of magnitude speedups over IPOPT, and remains robust under large distributional shifts, demonstrating a viable path toward real-time, topology-aware AC-OPF for large-scale distribution grids.

0.23

Distribution Grid Reconfiguration and Restoration via Linearizable Multi-phase Power Flow Modeling

eess.SY ·2026-10-26 ·Young-ho Cho, Hao Zhu
similarity 0.61
Abstract

Accurate and tractable power-flow (PF) modeling is essential for distribution grid topology optimization, where the presence of discrete branch-status decisions therein significantly increase the computational complexity. To tackle this challenge, we develop a topology-adaptive, low-complexity neural piecewise-linear (N-PWL) PF model. We propose a sequential layer design that can directly incorporate branch status variables into the PF mapping from branch flows to nodal injections. As a result, our N-PWL model not only preserves the PF branch-node consistency but also facilitates the representation of any unseen topologies without retraining. A low-complexity model design is further pursued to attain a linear NN parameter scaling by using a fixed-size area partition of the feeder. The resulting scalable N-PWL model enables mixed-integer linear programming (MILP) formulations of feeder topology optimization tasks, including distribution network reconfiguration (DNR) and restoration ordering problems (ROP). Numerical studies on the unbalanced, multi-phase IEEE 123-bus feeder demonstrate our N-PWL model outperforms existing end-to-end baselines in PF prediction and, more importantly, can fill the gap by achieving accurate representation of any unseen topologies. For solving DNR/ROP, our model can significantly improve the AC feasibility over linearized PF models, with a notable reduction of computation time compared with AC-PF based nonlinear formulations, particularly under a large number of topology decisions.

0.20

A Bayesian Adaptive Spectral Surrogate Model for Efficient Probabilistic Optimal Power Flow Evaluation

eess.SY ·2026-09-01 ·Xiaoting Wang, Xiaozhe Wang, Gregory Kish, Yunwei, Li
top venue similarity 0.60
Abstract · 18 pages, 15 figures. To appear in IEEE Transactions on Power Systems

This paper presents an adaptive stochastic spectral embedding (ASSE) method to solve the probabilistic AC optimal power flow (AC-OPF), a critical aspect of power system operation. The proposed method can efficiently and accurately estimate the probabilistic characteristics (e.g., mean, variance, median, and quantile-based metrics) of AC-OPF solutions while minimizing power losses. Based on estimated AC-OPF decisions (i.e., generator outputs), the confidence interval (CI)-based production cost index can be determined. Specially, an adaptive domain partition strategy is adopted to guide refinement domain selection and partition. The Bayesian compressive sensing-based coefficient calculation algorithm is integrated to enhance its performance. Numerical studies on modified IEEE 9-bus and IEEE 118-bus systems demonstrate that the proposed ASSE method offers accurate and fast evaluations compared to Monte Carlo simulations. Comparisons with a sparse polynomial chaos expansion, Gaussian process regression, and deep neural networks, further illustrate its efficacy in accurately assessing the responses with strongly localized behavior and non-symmetric distributions, providing practical decision-making bounds for generator outputs and operating costs under uncertainty.

0.42

A Deficiency-Based Approach for Unbalanced Three-Phase Distribution System Expansion Planning

eess.SY ·2026-10-12 ·Eli Brock, Miguel Heleno, Javad Lavaei, Somayeh Sojoudi
benchmark similarity 0.60
Abstract · 12 pages, 1 figure, 3 tables. This work has been submitted to the IEEE for possible publication. Copyright may be transferred without notice…

Distribution planners typically characterize grid needs through power flow studies and fit upgrades to those needs by hand. More principled one-shot optimization methods either do not scale or misrepresent unbalanced three-phase networks. This paper proposes an iterative planning process that alternates between two problem classes with mature off-the-shelf solvers. An optimal power flow (OPF) problem quantifies the deficiency of a candidate portfolio by optimizing the dispatch of controllable devices and measuring thermal and voltage violations on a common scale, with an optimal value of zero exactly at adequate portfolios. The OPF multipliers give a first-order approximation of the relief each investment candidate would provide. We bound the error of this approximation and show that structural properties of the deficiency guard it against overestimation. Building on this property, a heuristic cutting-plane search uses a mixed-integer linear program to propose each next portfolio from these approximations. On six unbalanced three-phase feeders from the SMART-DS dataset, the search outperforms a linearized optimization-based benchmark, and the results agree across five variants of the deficiency.

0.21

Day-ahead Coordination of Virtual Power Plants within Active Distribution Networks using Deterministic Bi-Level Optimization

cs.CE math.OCeess.SY ·2026-09-15 ·Laura M. Barajas-Arguello, Rafael A. Núñez-Rodríguez, Daniel Gebbran, Clodomiro Unsihuay-Vila
theory similarity 0.60
Abstract

This paper proposes a deterministic bilevel optimization framework for the coordinated operation of Virtual Power Plants (VPPs) embedded in an active distribution network. The Distribution System Operator (DSO) acts as the upper-level leader, minimizing a weighted combination of expenditure, active losses and voltage deviation subject to nonlinear AC power flow constraints, while each VPP operates as a lower-level follower that maximizes its profit under the uniform price signal issued by the DSO. Unlike most existing formulations, which linearize the lower-level subproblem to obtain a Mixed-Integer Linear Program (MILP), the proposed model retains the full AC Optimal Power Flow (AC-OPF) equations, producing a bilevel Mixed-Integer Nonlinear Program (MINLP). The lower-level problem is replaced by its Karush-Kuhn-Tucker (KKT) optimality conditions and the Strong Duality Theorem, yielding a single-level Mathematical Program with Equilibrium Constraints (MPEC). Complementarity conditions are then linearized via the Fortuny-Amat big-M transformation. The framework is validated on the IEEE 33-bus feeder over a 24-hour horizon, with four distributed resources aggregated into a single VPP. Compared with individual dispatch against a regulated time-of-use tariff, aggregation reduces active losses by 10.5 %, the accumulated voltage deviation by 18.3 %, and the bus-hours below 0.95 p.u. from 132 to 29. These gains cost 0.31 % in social cost and 0.26 % in DSO expenditure, while the rent of the aggregator is preserved.

0.14

Expediting AC Contingency Analysis using a Basecase Machine Learning Model

eess.SY ·2026-09-29 ·Md Obaidur Rahman, Vassilis Kekatos
similarity 0.60
Abstract · 10 page, 7 figures

Grid planning and operation under increasingly variable operating conditions require fast and accurate AC power flow (AC-PF) contingency analysis for numerous line outages. While ML models can accelerate these computations, existing approaches often require either training separate models for different contingencies or a single model using data from multiple topologies. Both approaches incur substantial offline data generation and training costs. To address this gap, this work proposes a fixed-point framework that reuses a single ML model trained exclusively on basecase topology data to predict post-contingency AC-PF states under any non-critical single-line outage. We analyze the proposed method's convergence under the DC model approximation and derive its convergence rate in terms of network parameters. As a side result, we show that power transfer distribution factors (PTDFs) for non-critical lines have magnitudes less than one. We further characterize the ML training region to accommodate PF specifications encountered during fixed-point iterations and derive bounds on ML prediction errors for post-contingency state estimates. Numerical tests on a 6,717-bus synthetic Texas system demonstrate convergence across all non-critical single-line outages, with prediction errors remaining close to those of basecase. The proposed framework offers a favorable tradeoff between the speed of DC solvers and Newton-Raphson accuracy.

0.11

Volt-VAr-Watt Optimization in Four-Wire Low-Voltage Networks: Exact Nonlinear Models and Smooth Approximations - Extended Version

eess.SY ·2026-09-14 ·Sleiman Mhanna, Frederik Geth, Lucas Quiertant, Pierluigi Mancarella
top venue similarity 0.59
Abstract · Extended version of the article published in IEEE Transactions on Power Systems, vol. 41, no. 5, pp. 3663-3677, 2026. DOI: 10.1109/TPWRS.202…

The proliferation of distributed energy resources is increasing the prevalence of both overvoltages and undervoltages in low-voltage (LV) distribution networks. Smart inverter functionalities, such as Volt-VAr and Volt-Watt control, can regulate voltage at the consumer level but are challenging to capture in optimization models due to their nondifferentiability. This paper proposes three nonlinear models for four-wire unbalanced optimal power flow that incorporate these nonsmooth functions without binary or integer variables. The first model encodes these nonsmooth functions directly as user-defined functions using control flow, a feat enabled by many state-of-the-art algebraic modeling languages. The second and third introduce bespoke smooth approximations with tunable approximation errors to address potential numerical issues arising from nondifferentiability, improving reliability while maintaining accuracy. All three methods are evaluated on real four-wire unbalanced LV networks with varying rooftop solar adoption levels, including a 539-bus system with 302 smart inverters. This paper is not only the first to demonstrate accurate, reliable, and tractable Volt-Var-Watt optimization (VVWO) on real four-wire unbalanced LV network models, but it also establishes that optimization-based, non-incremental methods offer superior reliability compared to commonly used incremental (quasi-steady-state) approaches.

0.61

PowerModels-ACOPF-AI: On-the-Fly Machine Learning Approach for Solving AC Optimal Power Flow Integrating Renewable Energy Sources

eess.SY ·2026-09-16 ·Bhuban Dhamala, Jose Tabarez, Anup Pandey
benchmark similarity 0.59
Abstract

The increasing complexity of modern power systems, driven by high renewable penetration, load variability, and operational uncertainty, demands fast and reliable solutions to the AC optimal power flow problem (AC-OPF). Traditional optimization methods, though accurate, often struggle with scalability and high computational burdens, making them impractical for real-time use in large networks. This paper introduces PowerModels-ACOPF-AI, a two-stage Bayesian Neural Network (BNN) surrogate designed to predict generator set points, bus voltages, and phase angles with uncertainty. The framework integrates a performance-sensitive on-the-fly learning mechanism that identifies regions of degraded prediction accuracy and dynamically retrains with additional AC-OPF solutions generated by PowerModels.jl. This self-adaptive loop ensures robust performance, enabling the model to maintain accuracy under novel or highly variable operating conditions. Validation on benchmark test systems of different sizes, namely the 30-bus, 200-bus, and 500-bus networks, demonstrates strong generalization capability, efficient handling of stochastic renewable injections, and the ability to provide rapid, uncertainty-aware predictions. Beyond predictive accuracy, the proposed approach offers practical value as both a real-time advisory tool for system operators and a fast initializer for conventional solvers, thus supporting resilient and efficient grid operation in future power systems.

0.16