Loadability Limits Under Periodic Load Forcing

Maitraya Avadhut Desai, Gustavo Valverde, Gabriela Hug

eess.SY ·submitted 2026-08-21 16:10 UTC · v1

Abstract

The static loadability limit, defined as the demand at which the equilibrium equations lose their solution, is the standard basis for interconnection screening of large new loads. This letter shows that when part of the demand varies periodically, as for data-center loads, the steady state is a forced periodic orbit whose loadability limit differs from the static one. The classical optimization argument is extended directly from equilibria to fixed points of the period map. At the limit, the monodromy matrix acquires a Floquet multiplier at +1, so the generic instability is a cyclic fold of the orbit rather than a saddle-node of equilibria. The limit is therefore a function of the forcing frequency, which no static computation can capture. Additionally, with the network Jacobian turning singular along the cycle, singularity-induced instability is extended to orbits. On a four-bus test system, a static margin of 2.5 p.u. shrinks to 0.53 p.u. near the swing frequency, the instability mechanism switches from voltage collapse to a rotor-angle fold, and cold starts fail at amplitudes where the orbit still exists. A static analysis reproduces none of these effects.

Closest papers

Nearest neighbours by meaning across the whole index.

Forced Oscillations in Power Systems Induced by Data Centers Hosting AI Workloads

eess.SY ·2026-09-23 ·Jovan Krajacic, Georgia Pierrou, Maitraya Desai, Gabriela Hug, Gustavo Valverde
similarity 0.61
Abstract · Revised and extended version of the manuscript previously posted on TechRxiv: https://www.techrxiv.org/doi/full/10.36227/techrxiv.176127304.…

Power swings in large Data Centers (DTCs) running Artificial Intelligence (AI) workloads can excite poorly damped modes in power systems. The resulting forced oscillations can lead to flicker, equipment disconnection, or blackouts. This paper investigates the risks of such load fluctuations for different system strengths and damping conditions. Using an analytical approach based on transfer functions, we identify critical DTC locations in the power grid at which load fluctuations could induce the largest forced oscillations and further characterize the harmonic spectrum of the resulting system response. Depending on the frequency and magnitude of the DTC load fluctuations, forced oscillations can become unbounded. The underlying instabilities are classified into saddle-node bifurcations of the forced periodic response and impasse-surface encounters, using Floquet multipliers and the minimum singular value of the algebraic Jacobian. Furthermore, the impact of different duty cycles and harmonic components beyond the fundamental oscillation frequency in square-wave load profiles is analyzed. Finally, the interaction of two oscillating DTCs is investigated for different locations and forcing frequencies, considering both synchronized and unsynchronized operation. The findings can help system operators to define new regulations on the maximum load fluctuations permitted for DTC facilities at specific grid locations, without negatively affecting the stability and operation of the system.

0.56

When Gigawatts of Computational Load Disappear: Cycle-Space Certificates for Grid Synchronization and Transient Stability

eess.SY math.DSphysics.soc-ph ·2026-09-23 ·Michael Chertkov
similarity 0.57
Abstract · 13 pages, 2 figures

Rapid growth of data centers and artificial-intelligence services is producing computational loads at scales once associated mainly with largest power plants. Recent grid events show that a routine transmission disturbance can cause several gigawatts of data-center demand to disconnect or transfer to backup nearly at once. This article revisits the classical synchronization and transient-stability theory needed to reason about such events. We organize four lines of work---graph-based synchronization conditions, winding-number descriptions of nonlinear power flow, separable convex network optimization, and direct energy methods---into a single cycle-space certificate framework for the lossless fixed-voltage model. The static layer gives an exact strict-cohesion test within a prescribed winding cell and reveals the widely used Dörfler--Chertkov--Bullo test as a quadratic surrogate of the same convex problem. The dynamic layer converts the critical-energy calculation into a finite family of convex boundary problems. Standard MATPOWER benchmarks illustrate both what the stronger static test gains and where it gains nothing: the 118-bus case admits $16.2\%$ more loading than the sufficient screen, while the 39-bus case is bridge-limited and the thresholds coincide. A stylized $2.7$-GW 39-bus event further shows that transient margin can change by about a factor of two depending on where balancing power is supplied, even when every final balanced operating point remains statically feasible. The result is a tutorial synthesis and an extensible deterministic certificate for emerging gigawatt-scale computational-load contingencies.

0.53

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.55
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.34

Designing Grid-Aware Dynamic Specifications for Large Data Center Loads

eess.SY ·2026-09-16 ·Ashutossh Gupta, Vassilis Kekatos
similarity 0.53
Abstract · 10 pages, 8 figures, IEEE TPWRS

As data center (DC) loads increasingly penetrate the power grid, there is an urgent need for grid operators to provide clear dynamic specifications to DC owners to ensure safe grid operation. To this end, we study two salient behaviors of large language model (LLM) training loads: abrupt ramps at job initiation and termination, which induce transient frequency excursions, and sustained periodic oscillations during training, which result in oscillatory steady-state behavior. For ramping loads, we show that nodal rotor frequencies can be accurately approximated by the center-of-inertia (COI) frequency and derive analytical expressions for its nadir and rate of change of frequency (RoCoF). These expressions determine allowable combinations of ramp times and steady-state load demands satisfying prescribed frequency limits. For oscillatory loads, we derive spectral specifications on their Fourier coefficients and show that the admissible coefficient set can be approximated by a polytope. We further obtain a compact representation via its maximum-volume inscribed ellipsoid, which we show is axis-aligned. Numerical tests on the WECC 179-bus system demonstrate that the resulting specifications remain valid for higher-order nonlinear dynamics. The proposed framework provides actionable specifications for regulating the dynamic behavior of large DC loads and informing load-shaping mechanisms within the data center ecosystem.

0.50

A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center

eess.SY ·2026-11-18 ·Advith Natarajan, Xinyang Zhou, Guido Cavraro
similarity 0.49
Abstract

The rapid growth of data centers is creating new interactions between computational workload and power-system dynamics, with potentially significant implications for grid stability. We develop a four-dimensional nonlinear dynamical model of a data center campus interconnected with the bulk power system through a modified Single Machine Infinite Bus system. The model couples generator swing dynamics with a fluid-limit model of computational workload backlog and a grid-interactive data center power controller that incorporates both frequency feedback and computational backpressure. This formulation captures the coupled evolution of generator frequency, rotor angle, computational workload, and data center power consumption, providing a framework for studying the stability implications of flexible data center operation.

0.18

Rented Oscillations: Multi-Tenant Data Center Workload Synchronization Attacks and Mitigation

eess.SY cs.CR ·2026-11-18 ·Zaint A. Alexakis, Li Zhou, S. Gokul Krishnan, Charalambos Konstantinou
similarity 0.48
Abstract

Multi-tenant data center (DC) facilities rent computing capacity on demand, placing controllable load within reach of anyone willing to pay for it. This paper considers a stealthy adversary who rents workstations and runs deliberately unoptimized large language model (LLM) training, synchronizing their consumption into large periodic oscillations while each workload remains individually indistinguishable from benign training. The periodicity of such workloads is characterized experimentally and used to model facility consumption, showing that oscillations emerge from the interaction of concurrent workloads, whether aligned by an adversary or arising naturally. A combined small- and large-signal assessment, under a hardware-grounded threat model whose feasibility is supported by experiments on a supercomputer, locates the oscillatory weak points of the network. MW-scale oscillations are shown to saturate the generators' control limiters, amplifying their effect, while Floquet analysis reveals a lightly damped mode emerging near the forcing frequency. To counter both origins, signal-energy-based detection and mitigation are proposed, the latter re-timing the workloads to minimize the facility's oscillatory energy. The approach is validated through power hardware-in-the-loop (PHIL) experiments and real-time simulations on a surrogate model of the Saudi Arabian transmission network.

0.40

Reliability Value of Long-Duration Energy Storage against Extreme Events in High-Renewable Grids: A Full-Year AC-OPF Assessment

eess.SY ·2026-09-06 ·Jeongdong Kim, Jonggeol Na, Sungho Shin
similarity 0.47
Abstract · 39 pages, 12 figures

Long-duration energy storage (LDES) can mitigate prolonged renewable--load imbalances during Dunkelflaute events, but existing studies rely on zonal or linearized DC network models and inadequately analyze the operational feasibility of the grid across a wide range of full-year renewable, load, and contingency scenarios. To address this gap, this paper introduces a multi-period alternating-current optimal power flow (AC-OPF) formulation that captures the full nonlinear network physics and assesses the reliability value of LDES in high-renewable grids. To evaluate scarcity events spanning multiple days to weeks, full-year operation is modeled as an 8,760-h load-shedding minimization over scenarios sampled from a Gaussian copula model, fitted to 2010--2025 historical wind and bus-level load data, that represents both typical variability and tail events. On a synthetic 200-bus Illinois transmission network, a hybrid fleet of battery energy storage (BESS) and LDES with 50 MW total power reduces annual load shedding by 83.0% on average relative to the base network, versus 68.5% for short-duration BESS alone at equal power. To further account for unexpected line outages throughout the year, the formulation is extended to a multi-day security-constrained AC-OPF. Under N-1contingencies, no feasible operating solution is obtained for the base network, whereas the LDES-equipped network remains feasible in all considered cases, thereby saving the cost of additional generation and transmission capacity. During the contingency period, LDES acts as a backup power supply, requiring only 5.5% more generation on average than the no-contingency base case.

0.21

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part II: Unstable Subsystems

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.47
Abstract · 15 pages, 13 figures

Part I of this paper presented a decentralised framework for certifying small-signal stability in AC grids using frequency-domain quadratic constraints on individual grid subsystems. Part II extends the framework to a broader class of networks that contain unstable subsystems. In particular, we show that such unstable subsystems arise in many common scenarios, even when the aggregate system is stable and well behaved. Such subsystems must be stabilised by the closed-loop network interconnection, which complicates decentralised stability analysis. A stable hybrid representation resembling the power (PQ) model at low frequencies and the impedance (IV) model at high frequencies is then defined, to which the stability framework of Part I can be applied, allowing plug-and-play compatible conditions to be formulated. Furthermore, we show that at low frequencies, the characteristic loci in the Nyquist plot of the return ratio in this hybrid representation decouple into unbounded and bounded branches along the classical $P$-$δ$ / $Q$-$V$ separation, and give sufficient conditions on each branch for ensuring system stability. The results are validated on the Kundur two-area system, where stability is certified, with a decentralised, plug-and-play compatible grid code covering the frequency ranges in which electromagnetic interactions arise.

0.30