CS Paper Radar

A Primal-Dual Formulation for Pricing Static Voltage Stability Services within a Unit Commitment Model

Peng Wang, Luis Badesa

eess.SY ·submitted 2026-09-10 12:06 UTC · v1

Abstract

In modern power systems with high penetration of Inverter-Based Resources (IBR), most converters operate in Grid-Following (GFL) mode. Some buses exhibit inherently low Short-Circuit Ratios (SCRs), a property majorly shaped by network topology. The integration of GFL-IBR onto such weak buses thus demands attention to static voltage stability. To address this issue, market mechanisms have been proposed to incentivize generators to provide voltage stability services, such as commitment of synchronous generators for reducing the equivalent impedance at low SCR buses and adaptive reactive power support from GFL-IBR. To compute shadow prices for these services, previously proposed methods such as the `restricted' and `dispatchable' approaches may fail to guarantee operating cost recovery for voltage-stability service providers. As the resulting prices are determined purely from a social surplus maximization objective, the profitability of units is entirely overlooked. This suggests that new pricing methodologies are needed to satisfy cost-recovery requirements. Therefore, this paper proposes a pricing method based on a primal-dual formulation. Case studies demonstrate that the proposed method can consistently produce revenue-adequate shadow prices, enabling all participating units to recover their costs without supplementary uplift payments.

Closest papers

Nearest neighbours by meaning across the whole index.

Shadow Pricing in Transient Stability-Constrained Optimal Power Flow

eess.SY ·2026-10-13 ·Alex Coelho, Araceli Hernandez, Luis Badesa
similarity 0.72
Abstract · 10 pages

Transient stability constraints alter the economic dispatch of power systems, while the resulting price signals and their implications for market settlement remain insufficiently characterized. Existing approaches identify stability-related components in locational marginal prices, without deriving shadow prices for individual assets, such as generators and loads, or analyzing the resulting settlement. To address this gap, this paper derives shadow prices from a transient stability-constrained optimal power flow in which the differential-algebraic equations governing the system dynamics are embedded through direct discretization. Each shadow price decomposes into a nodal energy component and a stability component, the latter formed by the dual variables of the dynamic equations in which the power of the asset appears. Shadow prices are therefore asset-specific: co-located generators and loads are assigned the same nodal energy component, but can be subject to different stability components when their transient behaviors differ. Case studies on the WECC 9-bus system and a modified IEEE 39-bus system show that settlement at the proposed shadow prices allocates the cost of the stability constraints among the assets without any side payment. An asset that reduces the stability margin is charged its stability component, whereas an asset that improves it is paid, and no generator is dispatched at a loss.

0.29

Minimizing Bid Cost Recovery for Energy Storage with Uniform Pricing

eess.SY ·2026-09-18 ·Yaxuan Yu, Jingguan Liu, Cong Chen
published similarity 0.63
Abstract · Accepted to the 65th IEEE Conference on Decision and Control (CDC 2026)

We study in-market uniform pricing and out-of-market bid cost recovery (BCR) payments in rolling-window dispatch for real-time power system operations with energy storage resources (ESRs). Due to intertemporal state-of-charge (SOC) constraints, ESR operations are temporally coupled, and existing in-market locational marginal pricing (LMP) may fail to compensate ESR's intertemporal opportunity costs, thereby triggering out-of-market BCR payments. We show that positive BCR is unavoidable when dispatched generators or ESRs have supply-side bids higher than the demand-side bid. We further identify an intertemporal coupling indicator associated with binding SOC constraints and demonstrate empirically that positive BCR arises only when this indicator is active, revealing that BCR is fundamentally driven by intertemporal coupling. In the simulation, we compare a BCR-minimizing uniform pricing scheme (UP-BCR) with existing real-time pricing methods under forecast uncertainty and show that UP-BCR substantially reduces BCR and demand payments relative to LMP while maintaining zero merchandising surplus in a copper-plate model.

0.24

Fair Dynamic Operating Envelopes using Distributed Multi-Period Optimal Power Flow and Jain Index for Active Distribution Networks

eess.SY cs.CE ·2026-08-24 ·Pedro Salomão Quessongo, Daniel Gebbran, Clodomiro Unsihuay-Vila
similarity 0.61
Abstract · 10 pages, submitted to CLAGTEE 2026 Conference

Dynamic operating envelopes (DOEs) are increasingly used to publish time-varying export limits that keep distribution networks within operational limits. Purely technical DOE allocation, however, can systematically privilege electrically favorable prosumers, while embedding fairness directly into a single-period optimal power flow (OPF) objective mixes network feasibility, equity and efficiency in a way that obscures the cost of fairness. This paper proposes a two-stage, multi-period framework that addresses both of these. Initially, a technical distributed OPF computes network-feasible export envelopes. The subsequent stage then applies a dynamic aggregate export budget and redistributes capacity through cumulative proportional fairness, limiting the additional curtailment by an admissible efficiency budget. The resulting fair DOEs are treated as first-stage decisions, while battery storage provides scenario-dependent recourse under demand and renewable uncertainty. The operational problem is solved by a calibrated regional alternating direction method of multipliers (ADMM) on a lossless LinDistFlow model and independently validated using AC power flow. We observe a trade-off between increases in curtailment \emph{versus} improvements on fairness, as expected, reaching Jain fairness indices close to unity. Results show that considering both storage (which alleviates curtailment impact) and multi-period fairness (which increases curtailment) is an interesting approach for modern DOE design, which in turn requires a multi-period, co-designed approach.

0.54

Computation of Price Signals for Controlling Flexible Prosumers in Distribution Grids Incorporating Stochasticity and Fairness

eess.SY ·2026-10-13 ·Plouton Grammatikos, Chloé Voirol, Pierre Roduit, Fabrizio Sossan
similarity 0.61
Abstract

This paper proposes a method for distribution system operators (DSOs) to design spatially fair dynamic price signals for flexible prosumers, accounting for both distribution grid constraints and the stochastic behavior of prosumers. Since locational pricing can introduce price unfairness when grid constraints are active, the proposed approach includes mechanisms to enforce price fairness across the network. The method involves the DSO solving a scenario-based optimal power flow (OPF) problem to derive, similarly to locational marginal prices in transmission systems, the Lagrange multipliers associated with grid constraints and to compute individualized price signals for each prosumer under various PV generation and demand scenarios. Subsequently, two methods are introduced to aggregate these individualized prices into a single fair price across prosumers. Their performance is evaluated through simulations on a model distribution grid, comparing prosumer revenues, grid constraint violations, and analyzing the impact of fairness on reducing cost variance among prosumers.

0.22

Reducing Data-Center Load Transfers with Ride-Through-Aware Voltage Control

eess.SY ·2026-11-05 ·Siyu Lu, Yang Weng
similarity 0.61
Abstract · 10 pages, 5 figures

Fault-induced transfers of large data centers to backup supply can cause abrupt reductions in grid-served demand. Coordinating reactive-power support to mitigate these transfers requires consideration of facility-specific voltage--duration ride-through characteristics, particularly when support capacity is limited. This paper develops a ride-through-aware extension of quadratic voltage control that assesses voltage deviations relative to the admissible margins specified by these characteristics. We establish four design requirements that jointly express envelope-based severity, duration dependence, and preventive voltage-restoration incentives. Within a multiplicatively gated quadratic class, we derive necessary and sufficient conditions for satisfying these requirements and construct an explicit family of envelope-normalized objectives. We apply the proposed objectives to reactive-power coordination and evaluate their performance on the IEEE 14-bus, New England 39-bus, and NPCC 140-bus systems. Comparisons with Volt/VAR control, conventional nominal-voltage tracking, and recent data-center voltage-control methods demonstrate improved data-center retention under matched reactive-power support constraints. In the IEEE 14-bus study, the proposed controller reduces the mean data-center disconnection rate by 44.8\% and grid-demand loss by 27.4\% compared with the best-performing baseline. These results highlight the benefit of incorporating data-center ride-through requirements into reactive-power allocation.

0.50

Prosumer Synchronisation Risk: Impacts of Time-Varying Tariffs on Distribution Network Expansion

eess.SY ·2026-09-02 ·Dillon Zadoks, Alfredo Oneto, Carlo Tajoli, Yi Guo, Philipp Heer +2 more
published similarity 0.59
Abstract

The rapid deployment of distributed energy resources, including heat pumps, electric vehicles, photovoltaics, and battery storage, is reshaping the operation of low-voltage networks. While distribution system operators often aim to develop time-varying tariffs to incentivise network-friendly behaviour and defer reinforcements, they risk triggering prosumer synchronisation. As prosumers follow price signals, their behaviour may synchronise, avoiding existing load peaks while creating undesirable peaks at other times. This paper quantifies the impact on low-voltage network reinforcement needs when shifting from flat tariffs to two time-varying tariffs: Time-of-Use and Real-Time Pricing. Applying a mixed-integer linear model across 471 low-voltage reference networks in Switzerland, we evaluate expansion requirements under projections of distributed energy resource deployment for 2050. In the model, prosumers operate their distributed energy resources in accordance with their subscribed electricity tariff to minimise costs, and the distribution system operator subsequently optimises reinforcements. Our results demonstrate that while adopting time-varying tariffs can reduce reinforcement investment costs by more than 50%, high adoption rates can reverse this declining trend. Specifically, once prosumer adoption exceeds the optimal thresholds of 50% for Time-of-Use and 40% for Real-Time Pricing, reinforcement needs increase by 39% and 134%, respectively, for an additional 20% of tariff adoption.

0.24

Who Gets the Grid Capacity? Allocating Dynamic Access Among Multiple Virtual Power Plants

eess.SY ·2026-11-16 ·Nakul Sreekanth, Jun He, Andrew L. Liu, S. Sivaranjani
similarity 0.58
Abstract

Virtual power plants (VPPs) trade in the same wholesale market and share distribution lines and transformers, and uncoordinated, profit-maximizing VPPs can push a shared transformer past its thermal limit or drive a feeder voltage out of band. The utility, which only observes the front-of-the-meter net injection at each bus, must keep the network safe from that net injection alone. We allocate a 24-hour active and reactive operating envelope to each VPP by a Benders decomposition: the utility sets a trial envelope, each VPP solves its private convex portfolio problem, and the returned value and dual gradient become supporting cuts that rebuild its value function while its schedule, state, and cost stay private. The envelope carries the transformer's thermal state across hours, bounds a joint conditional value-at-risk over forecast uncertainty, and is re-optimized each hour with the current hour committed. On a reduced IEEE-13 feeder with real load and prices, an active-power-only implementation lowers the transformer's peak-temperature CVaR from 254 to 97\,$^\circ$C at a 28\% value give-up and holds the transformer below its limit where nameplate access breaches it.

0.35

Impact of Wind-Solar-Battery Growth on Electricity Prices: Reserve Scarcity and Transmission Congestion

eess.SY ·2026-11-14 ·Haoxiang Wan, Ivan Castillo, Xingpeng Li
similarity 0.58
Abstract · 7 pages, 3 figures, 2 tables. Submitted to IEEE GECA 2027

This paper asks whether sequential wind, solar, and battery storage additions that eliminate unserved energy also remove modeled reserve scarcity and transmission congestion. Thirty-one cumulative portfolio states are evaluated on a modified IEEE 24-bus system for a constructed stressed day using a 24-hour day-ahead unit commitment model with network constraints, co-optimized energy and upward reserve, chronological battery storage, and an approximation of the Electric Reliability Council of Texas operating reserve demand curve. The thermal baseline has 106 MWh of unserved energy, whereas 450 MW of wind is sufficient to serve all demand. However, with 1,500 MW of wind, the hourly modeled reserve scarcity price still reaches \$5,000/MWh because wind output declines after the system peak. Adding 1,800 MW of solar reduces the load weighted daily average modeled reserve scarcity price from \$1,136.2/MWh to \$101.2/MWh and confines modeled reserve scarcity to three evening hours. Adding 250 MW/1,000 MWh of battery storage further lowers the average to \$4.3/MWh and reduces wind curtailment from 631 MWh to 306 MWh. Transmission congestion nevertheless remains: all residual wind curtailment occurs at bus 21, wind capture prices at buses 21 and 23 differ by \$31.8/MWh, and identical battery storage plants yield normalized net energy market revenues of \$201/(MW$\cdot$day) and \$121/(MW$\cdot$day) at buses 19 and 21, respectively. These results show that unserved energy, modeled reserve scarcity, and locational congestion effects measure distinct operating conditions and should be evaluated separately but interpreted together.

0.27