Sparse Generalized-Admittance AC Power Flow for Fast Contingency Analysis and Remedial-Action Assessment

Pierre Artoisenet, Noémie Verstraete

eess.SY ·submitted 2026-09-12 20:20 UTC · v1

Abstract

Repeated AC power-flow calculations are common tasks in transmission system operations, in particular for contingency analysis and remedial-action assessment. For large networks, their cumulative runtime can become a computational bottleneck in operational processes. This paper develops a sparse reformulation of the generalized bus-admittance power-flow method known as PFPD. Loads and generators are represented by fixed shunt admittance terms on the diagonal of the admittance matrix, while corrective nodal currents are iteratively computed to match the constant-power and regulated-voltage constraints. In contrast to the original formulation, the slack bus is treated as a fixed-voltage boundary and removed from the admittance block decomposition. The resulting iteration reuses sparse LU factorizations of the initial generalized non-slack matrix and its PQ block, without explicitly forming dense inverse matrices. The same formulation admits two initialization modes: an unsolved base case using the same flat-start shunt heuristic as in the primary PFPD method, and repeated post-action calculations initialized from a solved operating point. Localized topology and parameter changes are expressed as low-rank admittance updates and the resulting admittance matrices are inverted by means of the Woodbury identity. An optional local-network formulation can provide an warm start before full-network refinement. N-1 experiments on the 1354-bus and 9241-bus PEGASE systems and the 6717-bus synthetic Texas system yield average per-contingency speedups between 14.4 and 18.0 relative to pandapower. On transformer tap-position actions, the method is 2.8--2.9 times faster than pandapower and 7.2--29.9 times faster than PowSyBl OpenLoadFlow.

Comment
8 pages, 1 figure

Closest papers

Nearest neighbours by meaning across the whole index.

Unifying Power Flow and Electromagnetic Transient Modeling

eess.SY ·2026-09-08 ·Tina Gao, Aayushya Agarwala, Timothy McNamara, Lawrence Pileggi
similarity 0.57
Abstract

Grid tools are separated by timescales: steady-state analysis is performed by power flow (PF), whereas the fastest dynamics are captured by electromagnetic transient (EMT) simulation. Although operating at varying timescales, different tools should produce consistent results when analyzing the same grid conditions. However, the PF steady-state solution does not match the time-to-infinity EMT response. This mismatch exists because simplified device models in PF are inconsistent with the "ground truth" EMT models derived from first principles. As inverter-based resources (IBRs) and data centers strip away inertia and operating reserves, approximations used in PF risk grid security by missing violations. To address this, we introduce a steady-state framework that uses full-physics EMT models for high-fidelity steady-state grid analysis. The challenge lies in systematically formulating algebraic frequency-domain representations of dynamic power devices that are naturally described in state-space form. Our tool, SALT (Steady-state After Last Transients), constructs steady-state representations that exactly capture grid device physics when embedded into transmission networks. The approach exploits the structural properties of power device models and the single-harmonic, balanced nature of the transmission system. Results demonstrate SALT achieves EMT steady-state accuracy while delivering a 1x10^6 times speedup. We demonstrate that SALT can capture security threats in contingency scenarios without exception --- whereas PF-based analyses reported 75% fewer rated line violations, 18% fewer Q-limit violations, and 7% fewer voltage violations.

0.20

Co-Optimization of Network Topology and Variable Impedance Devices under Dynamic Line Ratings Using Iterative McCormick Relaxation

eess.SY ·2026-10-27 ·Junseon Park, Hyeongon Park, Rahul K. gupta
benchmark similarity 0.56
Abstract

Grid Enhancing Technologies (GETs), such as Network Topology Optimization (NTO), Dynamic Line Rating (DLR), and Variable Impedance Devices (VIDs) are increasingly deployed in power transmission grids to address congestion and improve grid utilization. However, their growing adoption necessitates coordinated operation to fully exploit their benefits. This paper presents a unified co-optimization framework that integrates NTO, DLR, and VID to alleviate congestion and minimize operational costs. NTO is modeled using a node-breaker formulation to provide enhanced switching granularity, while DLR incorporates weather-dependent parameters, including wind speed and ambient temperature, to dynamically adjust transmission limits. The resulting formulation is a mixed-integer nonlinear program due to power flow constraints with bilinear VID terms, and discrete topology decisions. To improve tractability, we propose using a McCormick relaxation approach to linearize bilinear terms. Furthermore, we propose an iterative refinement of the McCormick relaxation scheme to enhance solution accuracy. The proposed framework is validated through detailed analyses on the IEEE 118-bus system, along with additional case studies on other benchmark systems to assess scalability. Results demonstrate that the proposed approach improves solution accuracy compared to standard McCormick relaxation, achieves solution quality close to the nonlinear formulation, and maintains computational efficiency.

0.29

Plug-in Estimation Method for Topology and Admittance Estimation in Electric Grids

eess.SY ·2026-10-21 ·Norak Rin, Iman Shames, Ian R. Petersen, Nanduni I. Nimalsiri, Elizabeth L. Ratnam
benchmark similarity 0.56
Abstract

This paper proposes a scalable method for topology and admittance estimation in electric power grids. Our proposed plug-in estimation method incorporates precise phasor measurement unit data to estimate planned or unplanned grid topology and admittance parameter changes. Our plug-in estimation method decouples the problem into two stages: (i) constructing and averaging voltage coefficient matrices and current vectors from phasor data, and (ii) estimating admittance parameters via a least-squares regression approach with thresholding to recover the network topology. Rigidity matrix theory underpins the design of our plug-in estimation method --- to determine the data requirements (e.g., necessary and sufficient conditions) for accurate estimation of the grid topology and admittance parameters. By means of numerical simulations on the IEEE 13-node, 123-node, and European low voltage test feeders, we demonstrate the scalability of our plug-in estimation method and benchmark the computational time against a structured total least squares method. Our simulation results highlight the practicality of the proposed method for topology and admittance estimation in large-scale electric networks, including electric grids with partial topology information.

0.23

Quantifying the Cost of Restoring AC Feasibility for Approximate Optimal Power Flow Solutions

eess.SY math.OC ·2026-11-11 ·Sanjay Johnson, Sungho Shin
theory similarity 0.55
Abstract · 5 pages, 4 figures, submitted to 2027 IEEE Power & Energy Society General Meeting

Power system operations rely on approximate solutions of the AC optimal power flow problem, most notably the DC optimal power flow used in security-constrained unit commitment and economic dispatch, while convex relaxations, machine learning surrogates, and other approximations are studied extensively in the academic literature. Because these approximations neglect or relax parts of the AC power flow equations, their solutions must be adjusted before dispatch; for example, the DC optimal power flow, which neglects transmission losses, reactive power, and voltage magnitude variations, is known to produce solutions that are always infeasible. The cost of this adjustment is not adequately understood. This paper proposes a method that quantifies, for any approximate solution, the minimum cost of the adjustments that restore AC feasibility, which is a lower bound on the cost of the heuristic adjustments used in practice. We apply it to the DC optimal power flow, the second-order cone and quadratic convex relaxations, and the AC optimal power flow solved to a loose relative tolerance of $10^{-4}$ instead of $10^{-8}$. Relative to the AC optimal power flow solution obtained from a local nonlinear optimization solver, and even with the minimum adjustment, the DC optimal power flow requires adjusting, on average, generators that account for 15.6% of total generation capacity and incurs a 1.10% cost increase; the convex relaxations require more adjustment (17.2% and 16.9%) but smaller cost increases (0.68% and 0.78%); and the loose-tolerance AC optimal power flow requires 6.1% and incurs 0.42%. These results indicate significant value in operating markets directly on the AC optimal power flow, which avoids the distortion of the dispatch and prices caused by heuristic feasibility restoration.

0.27

Equivalent Modeling of Load-Side Systems With Distributed Renewable Generation Considering Fault Responses and Nodal Voltage Coherence

eess.SY ·2026-09-21 ·Yuqi Cao, Chen Shen, Shaowei Huang, Ying Chen, Hongyi Zhu
similarity 0.55
Abstract · Submitted to IEEE Transactions on Power Systems

Operating conditions and fault severity change both the initial states and control modes of active distribution networks. Direct capacity aggregation can therefore lose the power responses required for transmission-system dynamic analysis. This paper develops a procedure for generating low-order physical electromagnetic transient equivalents from a small set of representative operating conditions. Device power, ride-through states, load mechanical states, and local sequence voltages are combined with electrical distance to form response families. Response reconstruction and terminal simulation errors determine the retained architecture, after which bounded sensitivity calculations determine effective dynamic coefficients. The architecture and coefficients are then fixed. For a new operating condition, capacity and power balances, voltage-dependent load relations, and an initialization correction generate the model parameters from static inputs and power-flow results. A representative severe fault establishes a template for each fault type, which is reused across fault depths. Aggregation and switching-time bounds explain the roles of voltage coherence and state separation. Comparisons with direct aggregation show improved terminal responses across operating conditions and several fault types, with the largest gains under severe unbalanced faults. The method provides a reusable physical equivalent for operating-condition studies and fault-depth screening.

0.17

AC-Aware Steady-State Security Region Characterization via Exclusion Refinement

eess.SY ·2026-10-12 ·Zhirou Wang, Zhengshuo Li, Shuo Yang
similarity 0.55
Abstract

As active power dispatch becomes increasingly coupled with reactive power support and voltage security in modern power systems, AC security regions (AC-SRs) under exact steady-state AC power flow (AC-PF) constraints provide valuable insights into admissible operating boundaries and security margins for security assessment. However, the nonconvexity of exact AC-PF constraints makes it difficult to achieve both accuracy and computational efficiency in AC-SR characterization. To this end, this paper proposes an AC-aware iterative exclusion refinement (AC-ITER) approach that refines a given convex-relaxed AC-SR toward the exact AC-SR by progressively constructing and removing convexlocal exclusion subregions around numerically identified insecure points. Boundary-point searches and dual-based local exclusion cuts provide a tractable approximation of relaxation-induced insecure portions. A statistical certification method based on uniform sampling is developed to support high-confidence assessment of residual-region security and guide termination, while an AC-PF security similarity-based acceleration (AC-SSA) approach is introduced to further accelerate the sampling-based search for insecure operating points. Numerical studies on academic test systems and real-world systems demonstrate the characterization accuracy of AC-ITER and the computational efficiency gained through AC-SSA.

0.27

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.54
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Nonlinear Participation Factor-based Power System Model Reduction Addressing Near-Resonance Conditions

eess.SY math.DS ·2026-09-27 ·Mahsa Sajjadi, Kai Sun
similarity 0.54
Abstract

This paper proposes an adaptive model reduction approach based on nonlinear participation factors (NPFs) which determines the most effective selection of unimportant generators in a power system to be linearized to accelerate time-domain simulation for the entire system. The method enables a dynamic transition between the full-order model, and a hybrid reduced model. It uses modal energies to rank system modes under contingencies, and computes NPFs for highly energized modes based on Normal Form theory. To accelerate the computation of NPFs and make it achievable online, a tensor contraction technique is introduced. The proposed approach is tested on a 48-machine, 140-bus NPCC system using both partitioned and unpartitioned strategies. It demonstrates significant simulation speedup while preserving better accuracy than a linear participation factor-based method if the nonlinear behaviors of the system cannot be ignored, especially when a near-resonance condition is presented.

0.28