Modular Model Order Reduction for Inverter-Based Power Systems with Stability and Accuracy Guarantees

Hanqing Zhang, Pudong Ge, Mohammad Fahim Shakib, Adrià Junyent-Ferré, Balarko Chaudhuri, Luuk Poort, Lars A. L. Janssen, Giordano Scarciotti

eess.SY ·submitted 2026-10-01 20:54 UTC · v1

Abstract

This paper proposes a modular model order reduction framework for large-scale power grids integrated with renewable energy sources. The proposed framework has the advantage of reducing individual sub-areas independently while retaining the power grid interconnection structure. Moreover, given a user-defined accuracy specification on the overall reduced-order interconnected power grid, corresponding target specifications for the individual reduced sub-areas are determined: satisfaction of such individual specifications guarantees the overall user-defined accuracy specification, while also preserving the stability of the overall reduced-order interconnected power grid. The proposed framework is validated on a modified IEEE 118-bus system (where synchronous generators have been replaced by inverter-based resources) by assessing the accuracy specification satisfaction of the overall reduced-order interconnected power grid, in terms of frequency response, stability, active power, and sub-synchronous behaviour when injected with disturbances.

Comment
10 pages, submitted to IEEE Transactions on Power Systems

Closest papers

Nearest neighbours by meaning across the whole index.

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.64
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.36

An Analytical Review of Model Order Reduction Methodologies of Converter-Dominated Power Systems for Stability Studies

eess.SY ·2026-10-02 ·Goran Grdenić, Marco Fraccaro, Josipa-Pina Milišić
similarity 0.60
Abstract · 53 pages, 4 figures

The rapid integration of renewable energy sources is transforming modern electric power systems into converter-dominated networks characterized by complex multi-timescale dynamics and new stability interactions over a wide frequency range. Accurate analysis of these phenomena requires high-fidelity models of transmission networks and power electronic converters, which often result in large-scale differential-algebraic systems with significant computational burden. This paper provides an analytical review of model order reduction techniques for converter-rich power systems, with particular emphasis on the key equations employed in the reduction process. Advantages and limitations of commonly used strategies, including timescale-based singular perturbation, projection-based, operator-based, data-driven, and machine-learning based methods, are discussed. The synthesis highlights key challenges related to harmonic interactions and multi-frequency dynamics, and outlines directions for the development of computationally efficient yet dynamically accurate reduced-order models for future power systems.

0.29

Impact of Reduced-Order Modelling on Sum-of-Squares Region-of-Attraction Certification for Grid-Forming and Grid-Following Converters

eess.SY math.OC ·2026-11-10 ·Chenxi Yuan, Jeremy D. Watson, Neville R. Watson
similarity 0.60
Abstract · 13 pages, 5 figures, 3 tables

With the increasing penetration of power-electronic equipment, the transient stability of grid-forming (GFM) and grid-following (GFL) converters is increasingly characterized through the region of attraction (ROA) of the post-fault equilibrium. Sum-of-squares (SOS) programming yields certified inner approximations of the ROA, yet its computational cost grows rapidly with system order. Reduced-order models are therefore widely used to reduce computational cost and, more importantly, to enable analytical investigation. However, ROA analyses based on these models often assume that reproducing the converter's transient response, or retaining more dynamics in the correct time-frame, is sufficient to preserve the ROA of the full-order system. Using time-domain ODE simulations as a reference, the SOS-based ROA of each reduced-order GFM and GFL model is assessed against both its own simulated ROA and that of the corresponding full-order model, thereby separating SOS-induced conservativeness from model-order-induced ROA distortion. The results indicate that increasing reduced-order model complexity does not necessarily improve SOS-based ROA fidelity. In the cases examined, more complex reduced-order models yield lower SOS coverage of the full-order reference ROA, despite closer ODE-boundary agreement in some regions. Model selection should therefore consider both full-order ROA fidelity and certified coverage of the practical operating range, rather than model complexity alone.

0.35

Coordinated Conservation Voltage Reduction and Network Topology Reconfiguration in Active Distribution Networks

eess.SY ·2026-10-12 ·Rida Fatima, Hassan Zahid Butt, Xingpeng Li
similarity 0.59
Abstract

Distribution networks rely on conservation voltage reduction (CVR) and network topology reconfiguration (NTR) to manage demand, distributed energy resources (DERs), and tighter operating margins. Yet these strategies are typically deployed independently, despite coupled effects on feeder voltages, losses, and loading. This paper addresses that gap by developing a day-ahead mixed-integer second order cone programming (MISOCP) framework that jointly optimizes feeder head voltage control and network reconfiguration. The formulation incorporates AC branch flow constraints, ZIP load models, DERs, battery energy storage systems, and multi substation radiality. Using modified IEEE 33 bus and 123 bus systems, four configurations isolate the individual and coordinated effects of CVR and NTR. On the 33-bus system under mixed ZIP loading, NTR reduces active energy loss by 2.50%, while coordinated operation reduces it by 2.91% relative to SDN and produces a 2.46% CVR induced active load reduction relative to SDNTR. Under constant impedance loading, coordinated operation reduces active energy loss by 17.65% relative to SDN, while CVR reduces active load by 14.61% relative to SDNTR. DER portfolio scaling shows a nonmonotonic coordinated load reduction response, strongest at 20% penetration and decreasing at higher levels. On the 123 bus system, NTR reduces losses by 19.3%, while CVR reduces voltage dependent load energy by 2.3 to 2.4%. Under loading stress, SDN becomes infeasible at 120% loading, whereas CEDNTR remains feasible. Overall, the results demonstrate complementary, operating condition dependent benefits shaped by load composition, DER portfolio scaling, feeder topology, voltage margins, and source constraints, highlighting the value of joint optimization.

0.29

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.56
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.55
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.33

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part I

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.55
Abstract · 15 pages, 10 figures

The rise of renewable generation in AC power systems calls for small-signal stability assessment methods that do not rely on centralised, system-wide models. In this two-part paper, we present a decentralised stability framework based on frequency-domain conditions imposed on local subsystems (many admitting equivalent graphical interpretations) which collectively imply the stability of the entire grid. The framework generalises many previously reported results, with added flexibility and plug-and-play compatibility provided by the additional degrees of freedom of the imposed conditions, the ability to mix conditions across frequency ranges, conditions on extended subsystems that couple buses to their connecting lines and loads, and a method to incorporate unstable subsystems. Detailed, heterogeneous device and line models are accommodated in the frequency domain using impedance, admittance, and power-flow models, making the framework suitable as a foundation for grid codes that enable plug-and-play functionality in inverter-dominated grids. Part I focuses on stable impedance and admittance representations and Part II extends the results to unstable subsystems, which are shown to be fundamentally present in many grid models. The results of Part I are validated on a modified 9-bus case study, demonstrating the reduced conservatism and significance of the proposed approach.

0.54

Multi-time-scale Control of Power Systems

eess.SY math.OC ·2026-10-26 ·Emiliano Dall'Anese, John W. Simpson-Porco, Florian Dorfler, Saverio Bolognani, Sairaj Dhople
survey similarity 0.55
Abstract · Submitted for publication

The power grid has been dominated by large synchronous generators and clearly separated control layers. Today, power-electronics energy conversion interfaces are rapidly being deployed calling for another look at system-level control hierarchies. This article examines how multi-time-scale modeling, feedback control, and feedback optimization can help reinterpret the traditional organically grown hierarchy of primary control, automatic generation control, and economic dispatch, and enable new approaches for control of contemporary power systems. Beginning with an overview of power system models and conventional operational practices, the article develops connections to modern control architectures that can coordinate heterogeneous resources, account for operational constraints, and exploit faster actuation without overlooking first-principles physics.

0.28