CS Paper Radar

Stochastic Distribution Network Reconfiguration under Load Uncertainty

Celso Cavellucci, Fábio Luiz Usberti

eess.SY ·submitted 2026-10-08 15:36 UTC · v1

Abstract

This paper investigates distribution network reconfiguration under demand uncertainty using a two-stage stochastic formulation. The network topology is selected in the first stage, whereas the electrical variables are determined separately for each scenario. The deterministic equivalent is formulated as a MISOCP problem that accounts for power balances, losses, voltage constraints, and radiality. Experiments on 12 networks, ranging from 17 to 10,561 nodes, consider three demand scenarios. Reconfiguration reduced expected losses in all instances, with reductions ranging from 3.23% to 65.23% and averaging 31.76%, while also reducing the number of voltage violations in the ex post evaluation by approximately 55%. Eleven of the 12 problems were solved to optimality within the prescribed time limit. However, the additional benefit of stochastic modeling was negligible because of the homothetic structure of the scenarios considered, which preserves the spatial distribution of loads. The results show that spatially heterogeneous scenarios are important for the representation of uncertainty to meaningfully affect reconfiguration decisions.

Closest papers

Nearest neighbours by meaning across the whole index.

Robust Optimal Network Reduction for Distribution Systems

eess.SY ·2026-11-16 ·Omid Mokhtari, James Bagrow, Mads R. Almassalkhi, Samuel Chevalier
similarity 0.60
Abstract

Network reduction replaces large networks with smaller equivalents to speed up power flow and optimization studies. Optimal Kron-based Reduction of Networks (Opti-KRON) finds the optimal set of nodes to faithfully represent a large-scale radial network for representative loading scenarios. Under unseen nodal injections, however, its accuracy can drop. This paper extends Opti-KRON to uncertain nodal injections using robust uncertainty sets and a Wasserstein ambiguity set, with voltage magnitude error guarantees. To improve scalability, we develop a presolve screening step to eliminate redundant constraints and variables while preserving the feasible set. We also adopt adversarial constraint generation to reduce memory requirements by iteratively adding worst-case nodal injections. On a real 8,387-node feeder at a threshold of 0.001~p.u., the reduction removes 49.9% of the nodes. For one uncertainty set, adversarial constraint generation cuts the required memory by a factor of more than 18.

0.28

Cascading Contingency Analysis of Modern Power Systems Using a Stochastic Hybrid Systems Framework

eess.SY eess.SP ·2026-11-10 ·Masoud H. Nazari, Hamid Varmazyari
published similarity 0.59
Abstract · This paper was accepted at the 2026 North American Power Symposium (NAPS)

This paper presents a cascading contingency analysis and risk assessment framework that incorporates probabilistic mode transitions motivated by stochastic hybrid system (SHS) concepts together with power-flow-based stress evaluation. A two-stage modeling approach is adopted in which sensitivity-based analysis is first used to identify candidate cascading transitions, followed by DC power flow re-evaluation to accurately capture post-contingency stress redistribution, islanding behavior, and load shedding. A probabilistic propagation model is constructed using mode-dependent transition probabilities derived from line loading conditions. A Cascading Risk Index (CRI) is introduced to quantify the expected load shedding accumulated over cascade progression. Case studies on the IEEE 39-bus system demonstrate that the proposed framework captures diverse cascading routes under multiple initiating outages and identifies critical propagation patterns that are not revealed by N-1/N-2 screening. The results highlight the importance of SHS modeling in assessing cascading risk and providing a scalable framework for resilience evaluation in modern power systems.

0.43

Coordinated Conservation Voltage Reduction and Network Topology Reconfiguration in Active Distribution Networks

eess.SY ·2026-10-12 ·Rida Fatima, Hassan Zahid Butt, Xingpeng Li
similarity 0.59
Abstract

Distribution networks rely on conservation voltage reduction (CVR) and network topology reconfiguration (NTR) to manage demand, distributed energy resources (DERs), and tighter operating margins. Yet these strategies are typically deployed independently, despite coupled effects on feeder voltages, losses, and loading. This paper addresses that gap by developing a day-ahead mixed-integer second order cone programming (MISOCP) framework that jointly optimizes feeder head voltage control and network reconfiguration. The formulation incorporates AC branch flow constraints, ZIP load models, DERs, battery energy storage systems, and multi substation radiality. Using modified IEEE 33 bus and 123 bus systems, four configurations isolate the individual and coordinated effects of CVR and NTR. On the 33-bus system under mixed ZIP loading, NTR reduces active energy loss by 2.50%, while coordinated operation reduces it by 2.91% relative to SDN and produces a 2.46% CVR induced active load reduction relative to SDNTR. Under constant impedance loading, coordinated operation reduces active energy loss by 17.65% relative to SDN, while CVR reduces active load by 14.61% relative to SDNTR. DER portfolio scaling shows a nonmonotonic coordinated load reduction response, strongest at 20% penetration and decreasing at higher levels. On the 123 bus system, NTR reduces losses by 19.3%, while CVR reduces voltage dependent load energy by 2.3 to 2.4%. Under loading stress, SDN becomes infeasible at 120% loading, whereas CEDNTR remains feasible. Overall, the results demonstrate complementary, operating condition dependent benefits shaped by load composition, DER portfolio scaling, feeder topology, voltage margins, and source constraints, highlighting the value of joint optimization.

0.30

Models of Electric Vehicle Charging Demands in Distribution Grid Operation: A Review

eess.SY ·2026-10-06 ·Dipayan Sarkar, Qifeng Li
survey similarity 0.59
Abstract

The rapid integration of electric vehicles (EVs) into the transportation system has introduced a new class of load into power distribution systems (PDS), i.e., EV charging demand (EVCD). The spatiotemporal variability of EVCD poses fundamental challenges for distribution system operators (DSOs), particularly in ensuring secure and reliable network operation. Accurately representing EVCD as a parameter within the distribution optimal power flow (DOPF) problem is a prerequisite for reliable, cost-efficient PDS operation, yet no universally accepted modeling framework has emerged. The existing contributions span a wide spectrum of assumptions, mathematical formulations, and solution paradigms. This article presents a systematic review of methods and models employed to represent EVCD within DOPF frameworks from the DSO's operational perspective. The existing EVCD modeling methods are classified into two primary categories based on EVCD representation: deterministic models and uncertainty-aware models. The two main categories are further divided into several subcategories. This paper aims to provide a comprehensive review on models for integrating EVCD into PDS operation and planning.

0.26

Efficient Quantile-Resolved Hosting Capacity Assessment on Nodal Level for Low-Voltage Grids

eess.SY ·2026-09-08 ·Maximilian Köhler, Edwin Mora, Mathias Duckheim, Stefan Niessen
similarity 0.59
Abstract · Submitted to IEEE PES ISGT Europe 2026. 5 pages, 3 figures. Keywords: Hosting Capacity, Uncertainty, Distribution Grid, Distributed Energy R…

Hosting capacity - the maximum additional capacity a network can accommodate without violating operational limits - is a key metric in distribution system planning and operation. Decisions on grid reinforcements and the deployment of flexibility management require not only the worst-case HC but also an understanding of the distribution of HC under different likelihoods in load and generation patterns. Quantile-resolved HC distributions provide this view by expressing HC as a function of an acceptable operational limit exceedance likelihood. Monte Carlo sampling is the established approach for computing such distributions but demands large computational resources. Approximations sacrifice either accuracy, the ability to capture uncertainty correlations, or scalability when assessing real-world networks. This paper introduces a computationally efficient method for calculating distributions for quantile-resolved HC. It uses a representation of load samples as multivariate normal distribution, propagated through a linearized power flow model. This allows for leveraging a re-parametrized AC-OPF problem for each hosting capacity quantile. Benchmarking against Monte Carlo-based methods on realistic LV networks demonstrates that the proposed method achieves comparable accuracy with a mean deviation of approx. 3%, while reducing computational time by orders of magnitude. For the exemplary networks the computational time decreases from 11 min to 2 s, and 38 h to 50 s, respectively. The method's scalability is also suitable for recalculation in 15-minute cycles encountered in DSO practice for e.g., real-time grid management.

0.21

EPIGRIDS: Documentation and Validation of Seven Open Synthetic Transmission Grid Cases

eess.SY math.OC ·2026-11-13 ·Jonathan M. Snodgrass, Scott Greene, Thomas J. Overbye, Christopher L. DeMarco, Bernard C. Lesieutre
benchmark similarity 0.58
Abstract · 10 pages, 2 figures, 6 tables. Submitted to the IEEE Open Access Journal of Power and Energy. Cases: https://doi.org/10.5281/zenodo.23814538…

This paper documents and checks EPIGRIDS, seven open synthetic transmission grid cases from four independently built networks, made with an optimization-based construction method instead of the graph-statistics method behind most large public synthetic grids. The cases range from 250 to 78,484 buses, with geolocated substations, voltages up to 765 kV, and line parameters taken from conductor data. Each ships under an open license in three common power flow formats that agree at the solved operating point, and the six larger cases have a companion hourly, bus-level load series for one year. The Texas, Florida, and Michigan, Ohio, and Indiana cases are sub-networks of the Eastern case. Every case solves an alternating-current power flow from its stored operating point. With parallel circuits merged, the Eastern and Western cases are 9 and 16% denser than the real interconnections, while graph-statistics cases on the same footprints lie within 6% and meet more published realism criteria. A full single-outage contingency analysis completes on every case, and in an optimal power flow benchmark every case except the New England base case and one of its 12 operating points solves in polar form.

0.39

Resilience Enhancement of Distribution Grids Through a Three-Stage Framework for Scheduling Mobile Energy Storage Systems

eess.SY ·2026-09-24 ·Ali Abbasi, Kyri Baker
similarity 0.58
Abstract

As high-impact, low-probability disturbances such as extreme weather events increase in frequency, enhancing power grid resilience has become a critical priority. Mobile Energy Storage Systems (MESSs) have strong potential for helping with this purpose due to their high operational flexibility and fast deployability. They can be rapidly relocated to supply critical loads, support islanded operation, and adapt to changing conditions of the grid, making them a promising addition or alternative to conventional resilience-providing methods. This paper proposes a three-stage framework for scheduling MESS units. In the first stage (Normal Operation), charging/discharging scheduling of MESSs at buses is optimized for economic arbitrage. Upon receiving an early warning signal, the second stage (Proactive Positioning) shifts the focus to resilience. Here, the model determines the optimal staging points within the transportation network to minimize the expected time of arrival at critical loads, considering the probability distribution of line outages. The third stage (Dynamic Relocation) addresses the post-event restoration phase, in which MESSs are relocated in response to grid updates, such as subsequent line failures. Furthermore, a graph neural network-based solution approach is proposed to further enhance computational efficiency in determining the optimal placing of MESS units during the pre-allocation and relocation stages. The simulation results demonstrate that the proposed framework reduces expected energy not served and improves the restoration speed.

0.21

Compound Climate Risk-Aware Electricity Dispatch: Trajectory-Based Modeling for Power System Resilience

eess.SY ·2026-10-29 ·Feiyu Cai, Jing Qiu, Chenxi Zhang, Yi Yang, Yuechuan Tao +1 more
similarity 0.58
Abstract · 10 pages, 8 figures

In recent decades, emerging compound hazards in a changing climate have increasingly threatened power system resilience and posed new challenges to electricity dispatch. Conventional Value-at-Risk (VaR)-based risk-aware dispatch provides a tractable means of managing stochastic net demand deviations caused by distribution feeder outages. However, when applied to temporally compounding events such as tropical cyclone (TC)--blackout--heatwave, conventional net demand risk formulations may assign similar risk levels to a brief outage and an outage with the same instantaneous net demand impact that persists into a subsequent hazard, despite their different requirements for sustained operational flexibility. Moreover, directly incorporating compound risk into electricity dispatch models faces a structural mismatch: the risk is defined by the joint distribution of feeder restoration and subsequent hazards over exponentially many joint states, whereas dispatch models require risk formulations that are tractable in the scheduling decisions. To address these issues, this paper proposes a compound climate risk-aware dispatch framework with a trajectory-based compound risk model, which defines the loss on operating deviations determined by entire feeder connection trajectories, parameterized by uncertain restoration times and coupled with subsequent hazards. Analytical moment-generating functions and equivalent exponential-cone reformulations provide a compact representation of the resulting risk constraints, preserving the relevant dependencies without explicit joint-state enumeration. By leveraging a physics-based spatiotemporal TC--blackout--heatwave hazard model, case studies demonstrate the effectiveness of the proposed method with real-world time-series power outage data from Puerto Rico, including data collected during Hurricane Fiona in 2022.

0.34