CS Paper Radar

Phase Locking in Oscillator Networks with Uncertain and State-Dependent Couplings

Iva Bačić, Philipp C. Böttcher, Marc Hunkemöller, Carsten Hartmann, David Gross, Andrea Benigni, Dirk Witthaut

eess.SY nlin.AOmath.DSmath.OCphysics.soc-ph ·submitted 2026-11-04 13:03 UTC · v1

Abstract

Phase locking in oscillator networks depends critically on the interaction strengths between coupled units. In many applications, however, these couplings are uncertain, state dependent, or time varying. We derive rigorous conditions for phase locking in Kuramoto-type networks when each coupling strength is known only within prescribed bounds. Building on a convex formulation of the nonlinear fixed-point equations, we obtain edge-wise error bounds for arbitrary feasible approximations that hold uniformly over all admissible couplings. These bounds yield sufficient conditions for the existence of phase-locked states with prescribed phase-difference limits. We illustrate the framework for AC power grids with uncertain voltage magnitudes and adaptive oscillator networks with state-dependent couplings. For the latter, the bounds can be further tightened by exploiting the state dependence of the couplings.

Closest papers

Nearest neighbours by meaning across the whole index.

Linear Approximations Provide Rigorous Conditions for Phase Locking in Oscillator Networks and Power Grids

eess.SY nlin.AOmath.OCphysics.soc-ph ·2026-10-17 ·Iva Bačić, Carsten Hartmann, Philipp C. Böttcher, David Gross, Andrea Benigni +1 more
similarity 0.85
Abstract

Synchronization is a fundamental collective phenomenon in many natural and engineered networks. The stable operation of oscillator networks, such as electric power grids, requires phase locking with phase differences across edges below a given threshold. A central question is whether a given network supports such a state. In this contribution, we extend a convex optimization formulation of the nonlinear fixed point equations of the Kuramoto model, that also describe lossless power grids. Based on this formulation, we derive rigorous and tight bounds on the error introduced by an arbitrary approximation of the original model, in particular linear approximations. The bounds yield edge-wise regions of trust around the approximation, within which the true nonlinear solution must lie. They further provide sufficient and necessary conditions for phase locking under prescribed phase difference limits. Numerical experiments show that the bounds are tight over a broad range of parameters.

0.41

Fixed-Time Voltage Regulation in Distribution Networks with Impedance Awareness

eess.SY ·2026-10-01 ·Nilanjan Roy Chowdhury, Venkatesh Sarangan
similarity 0.57
Abstract · 8 pages, 6 figures

This letter introduces an optimization-based fixed time control algorithm for solving the voltage regulation problem of a radial and balanced power distribution network. The proposed algorithm requires no prior knowledge of the exact network impedance (resistance and reactance), yet guarantees voltage convergence to the predefined safe limit within a fixed time-window. We embrace results from Fixed-time stability (FxTs) and Control Lyapunov function (CLF) to analyze the stability and robustness of the underlying algorithm and then synthesize it leveraging the Quadratic Programming (QP) approach. We first analytically provide sufficient conditions on the control gains and the design parameters, that can ensure voltage regulation in fixed-time. Thereafter we transform the existing voltage regulation problem into an equivalent QP-based optimization framework and translate the aforesaid conditions to find feasible solutions for voltage stability. We empirically verify the efficacy of our proposed algorithm on the IEEE-33 bus distribution network and compare its performance against other existing robust control methods.

0.29

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part II: Unstable Subsystems

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.56
Abstract · 15 pages, 13 figures

Part I of this paper presented a decentralised framework for certifying small-signal stability in AC grids using frequency-domain quadratic constraints on individual grid subsystems. Part II extends the framework to a broader class of networks that contain unstable subsystems. In particular, we show that such unstable subsystems arise in many common scenarios, even when the aggregate system is stable and well behaved. Such subsystems must be stabilised by the closed-loop network interconnection, which complicates decentralised stability analysis. A stable hybrid representation resembling the power (PQ) model at low frequencies and the impedance (IV) model at high frequencies is then defined, to which the stability framework of Part I can be applied, allowing plug-and-play compatible conditions to be formulated. Furthermore, we show that at low frequencies, the characteristic loci in the Nyquist plot of the return ratio in this hybrid representation decouple into unbounded and bounded branches along the classical $P$-$δ$ / $Q$-$V$ separation, and give sufficient conditions on each branch for ensuring system stability. The results are validated on the Kundur two-area system, where stability is certified, with a decentralised, plug-and-play compatible grid code covering the frequency ranges in which electromagnetic interactions arise.

0.30

Explicit Convex Inner Approximation of TSO-DSO Flexibility Regions via Exact Second-order Cone Relaxation in Radial Networks

eess.SY ·2026-10-20 ·Wenyu Liu, Mario Paolone
benchmark similarity 0.54
Abstract · 10 pages, 4 figures

Accurate representations of the flexibility in distribution grids via tractable algorithms are essential for TSO-DSO coordination. However, flexibility region (FR) estimation based on nonlinear optimal power flow (OPF) generally lacks feasibility guarantees, while conventional convex relaxations may suffer from inexactness. This paper proposes a framework for constructing explicit inner approximations of active-reactive power FRs in radial networks based on the augmented relaxed OPF (AR-OPF). First, less-conservative sufficient conditions for the AR-OPF exactness are derived and extended to generalized objectives. Furthermore, an interior-feasibility analysis is established, guaranteeing that the entire region enclosed by the traced boundary is AC feasible under the proposed sufficient conditions. Building on these theoretical results, two adaptive algorithms are developed to construct explicit inner approximations and numerically convex representations of FRs. Numerical evaluations on different benchmark networks demonstrate consistently small relaxation residuals and high flexibility area retention in most cases, showing that the proposed methods provide a grounded approach to construct operationally admissible FRs for TSO-DSO coordination.

0.35

When Gigawatts of Computational Load Disappear: Cycle-Space Certificates for Grid Synchronization and Transient Stability

eess.SY math.DSphysics.soc-ph ·2026-09-23 ·Michael Chertkov
similarity 0.51
Abstract · 13 pages, 2 figures

Rapid growth of data centers and artificial-intelligence services is producing computational loads at scales once associated mainly with largest power plants. Recent grid events show that a routine transmission disturbance can cause several gigawatts of data-center demand to disconnect or transfer to backup nearly at once. This article revisits the classical synchronization and transient-stability theory needed to reason about such events. We organize four lines of work---graph-based synchronization conditions, winding-number descriptions of nonlinear power flow, separable convex network optimization, and direct energy methods---into a single cycle-space certificate framework for the lossless fixed-voltage model. The static layer gives an exact strict-cohesion test within a prescribed winding cell and reveals the widely used Dörfler--Chertkov--Bullo test as a quadratic surrogate of the same convex problem. The dynamic layer converts the critical-energy calculation into a finite family of convex boundary problems. Standard MATPOWER benchmarks illustrate both what the stronger static test gains and where it gains nothing: the 118-bus case admits $16.2\%$ more loading than the sufficient screen, while the 39-bus case is bridge-limited and the thresholds coincide. A stylized $2.7$-GW 39-bus event further shows that transient margin can change by about a factor of two depending on where balancing power is supplied, even when every final balanced operating point remains statically feasible. The result is a tutorial synthesis and an extensible deterministic certificate for emerging gigawatt-scale computational-load contingencies.

0.53

Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective Control

eess.SY math.DS ·2026-10-19 ·Cheng Feng
similarity 0.51
Abstract

The grid integration of large data centers poses a growing power-system stability challenge. Rapidly varying computing demand can induce oscillations, while the facilities must provide a prescribed response to grid disturbances. Existing controls address load fluctuations and grid support but do not establish their jointly achievable performance. This paper derives fundamental limits and develops a source-selective controller for simultaneous oscillation isolation and grid support. A coupled closed-loop model gives a condition for distinguishing disturbance sources and reveals a direct isolation-support conflict under grid-import-power feedback alone; additional electrical measurements can remove this pointwise conflict but leave a conditional cross-frequency sensitivity limit. Guided by these limits, we design a local residual-feedback storage controller through convex frequency-domain optimization with stability, isolation, and grid-response constraints across operating points. Tests on a single-generator interconnection and a modified nine-bus network show stronger oscillation isolation than equal-order optimized comparators while meeting the prescribed grid response across operating points.

0.22

Harmonic Stability of Power Systems: A Control-Theoretic Definition and Assessment Criteria

eess.SY ·2026-08-20 ·N. Bhoir, A. Sarkar, J. E. Machado, J. Schiffer
similarity 0.50
Abstract

Harmonic interactions have become a defining dynamic stability phenomenon in converter-based power systems (CBPSs). However, a formalization of the notion of harmonic stability in the context of nonlinear dynamical systems is not available thus far. In this paper, we propose a definition of harmonic stability formulated as a combination of two standard stability notions, namely, bounded-input bounded-output (BIBO) and internal stability properties with respect to any nominal periodic trajectory. Moreover, we rigorously show that the local harmonic stability of any nominal periodic trajectory of nonlinear CBPSs is implied by the stability properties of its linear time-periodic (LTP) approximation. In addition, to enable computationally tractable stability assessment, we develop a framework based on harmonic state-space (HSS) representations of LTP models. In particular, we provide time-invariant linear matrix inequality (LMI) conditions to certify harmonic stability. The proposed methodology is illustrated on a grid-following converter system, where the HSS-based analysis numerically confirms harmonic stability around the periodic operating trajectory.

0.29

Controller- and Communication-Aware Flexibility Margins for Electric Distribution Networks

eess.SY ·2026-10-14 ·Saif R. Kazi, Kaarthik Sundar
similarity 0.50
Abstract · 11 pages

This paper develops a framework for quantifying operational flexibility in radial electric distribution systems under coupled active- and reactive-load uncertainty. Flexibility is defined as the largest scaling of a prescribed uncertainty set that can be accommodated while satisfying network and actuator limits under a given control architecture. We consider a one-sided Euclidean set for robust demand-growth capability, with a direct extension to bidirectional variations. Under LinDistFlow, controllable distributed resources and feeder-head exchange with the upstream grid jointly balance active-power disturbances, while local Volt/VAR feedback regulates reactive power. The resulting affine closed-loop disturbance response admits exact second-order-cone robust counterparts. For fixed Volt/VAR gains, a convex reformulation jointly optimizes the flexibility margin and active-power participation factors, including feeder-head participation. A sparse load-to-generator feedforward map further captures communication constraints. Numerical studies on the Iowa-240 feeder demonstrate how the amount of control authority and communication structure shape the achievable flexibility margin.

0.24