Loadability Assessment for Large-Load Integration: From Repeated Power Flow Tracing to Historical Trajectory Transfer

Yihan Huang, Yang Weng

eess.SY ·submitted 2026-11-20 22:33 UTC · v1

Abstract

Integrating large data-center loads requires utilities to evaluate voltage-stability loading margins under different generation and demand conditions. Continuation power flow (CPF) traces P--V curves through successive prediction and correction steps, but related assessments can repeatedly reconstruct similar nonlinear behavior. Reusing an operating point as an initial guess does not capture the subsequent voltage response. This paper proposes a continuation method that transfers finite segments of historical power flow (PF) trajectories. Each segment is aligned with the present state and continuation direction, supplementing the CPF tangent predictor with previously computed nonlinear curve shape. Short Newton tests evaluate compatibility with the present PF equations, and an attention-based selector combines their results with network conditions, loading patterns, and recent continuation states. Numerical correction and fold refinement determine accepted solutions and the loading limit. The analysis bounds prediction error through differences in trajectory curvature and establishes sufficient conditions for local correction and branch preservation. Studies on modified IEEE 14- and 118-bus systems under renewable-generation and data-center load variations demonstrate reduced online computation and higher observed recovery of specified continuation solutions than Adaptive CPF. For loading-limit assessment, paired online speedups are 4.88--21.62$\times$ over Adaptive CPF and 1.53--4.77$\times$ over holomorphic embedding with arc-length parametrization (HEAP) across the tested scenarios.

Closest papers

Nearest neighbours by meaning across the whole index.

Voltage Stability Assessment with Path-Coupled Load Growth and Corrective Generator Response

eess.SY ·2026-08-15 ·Lanqing Shan
similarity 0.64
Abstract

Voltage stability margin assessment is essential for the secure operation of renewable-dominated power systems. Conventional continuation-based methods evaluate the margin along predefined load-growth paths with fixed generator partic- ipation, while practical operation allows generators to be redis- patched to alleviate voltage stress and reshape the power-flow trajectory as the system approaches voltage collapse. This paper proposes a path-coupled margin assessment approach that incor- porates corrective generator response into static voltage stability margin assessment. In the proposed approach, the load-growth direction and generator response direction are simultaneously determined at each continuation step, enabling the assessment trajectory to account for generator response while tracing the system toward voltage collapse. The voltage stability margin is then evaluated by the cumulative active load increase along this coupled trajectory. Based on the obtained trajectory and collapse point, a feasible redispatch direction is further derived to improve the margin of the current operating state. The economic cost of voltage stability enhancement is quantified through a marginal stability cost, providing an economic indicator for additional sta- bility support. Case studies on various test systems demonstrate that the proposed framework can effectively capture the impact of corrective generator redispatch on voltage stability assessment, provide effective guidance for margin enhancement, and quantify the cost associated with voltage stability improvement.

0.34

Scalable Voltage-Stability Dataset Generation Via Boundary-Proximity Indicators Clustering

eess.SY ·2026-08-28 ·Rock Agon, Robin Preece, Jovica V. Milanović
similarity 0.58
Abstract · Submitted to MedPower Conference 2026

This paper proposes a scalable framework for voltage-stability dataset generation. Voltage-stability-constrained planning increasingly relies on machine-learning surrogates but training them requires large datasets labelled by continuation power flow (CPF) results, which is computationally costly. To address this, this paper proposes a framework that uses hierarchical clustering on boundary-proximity indicators to reduce the number of required CPF evaluations. The proposed approach combines (i) uniform sampling of feasible operating space using Hit-and-Run Markov Chain Monte Carlo, (ii) structured stress directions via maximin Latin hypercube sampling (LHS), (iii) sensitivity-guided perturbations to target weak buses, and (iv) clustering-based representative CPF labelling that reconstructs the voltage stability margins of unlabelled operating points from representative cluster medoids. Results on the IEEE 39-bus system show that the proposed framework significantly reduces CPF evaluations by 95.45% while preserving high accuracy and boundary fidelity for both regression and classification tasks. The reduced surrogates remain structurally consistent with their full-CPF dataset counterparts, demonstrating the suitability and scalability of the proposed approach for operation and planning optimization.

0.25

When Gigawatts of Computational Load Disappear: Cycle-Space Certificates for Grid Synchronization and Transient Stability

eess.SY math.DSphysics.soc-ph ·2026-09-23 ·Michael Chertkov
similarity 0.56
Abstract · 13 pages, 2 figures

Rapid growth of data centers and artificial-intelligence services is producing computational loads at scales once associated mainly with largest power plants. Recent grid events show that a routine transmission disturbance can cause several gigawatts of data-center demand to disconnect or transfer to backup nearly at once. This article revisits the classical synchronization and transient-stability theory needed to reason about such events. We organize four lines of work---graph-based synchronization conditions, winding-number descriptions of nonlinear power flow, separable convex network optimization, and direct energy methods---into a single cycle-space certificate framework for the lossless fixed-voltage model. The static layer gives an exact strict-cohesion test within a prescribed winding cell and reveals the widely used Dörfler--Chertkov--Bullo test as a quadratic surrogate of the same convex problem. The dynamic layer converts the critical-energy calculation into a finite family of convex boundary problems. Standard MATPOWER benchmarks illustrate both what the stronger static test gains and where it gains nothing: the 118-bus case admits $16.2\%$ more loading than the sufficient screen, while the 39-bus case is bridge-limited and the thresholds coincide. A stylized $2.7$-GW 39-bus event further shows that transient margin can change by about a factor of two depending on where balancing power is supplied, even when every final balanced operating point remains statically feasible. The result is a tutorial synthesis and an extensible deterministic certificate for emerging gigawatt-scale computational-load contingencies.

0.53

Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids

eess.SY ·2026-11-17 ·Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
similarity 0.56
Abstract · 5 pages, 2 figures, submitted to PESGM 2027

The rapid deployment of artificial intelligence data centers (AIDCs) introduces gigawatt-scale, highly nonlinear, and fast-varying electronic loads that challenge grid voltage regulation, frequency stability, and disturbance ride-through. Capturing their transient behavior during grid faults and rapid computational workload swings requires high-fidelity electromagnetic transient (EMT) simulations rather than root mean square models. However, limited methodologies exist to audit the component-level adequacy of EMT AIDC models. This paper proposes a software-agnostic, 41-point fidelity framework spanning 11 categories that synthesizes 37 criteria from an existing modeling guideline with four novel requirements: frequency ride-through compliance, disaggregated fan and chiller cooling loads, temperature-dependent thermal response, and DC information technology (IT) load representations. Applying this framework to the four publicly available AIDC models in PSCAD/EMTDC reveals varying degrees of completeness: while the models capture IT load transitions, uninterruptible power supplies, and transfer switches for bulk stability studies, critical gaps remain in electro-thermal cooling coupling, internal protective relaying, and site-level controls. Addressing these gaps will enable comprehensive protection coordination and ride-through compliance studies.

0.23

Identifiability-Guided Composite Load Modeling of AI Data Centers

eess.SY ·2026-10-14 ·Ding Lin, Jianhui Wang, Meng Yue, Tianqiao Zhao
similarity 0.55
Abstract

The rapid growth of AI data centers introduces large, workload-dependent loads whose protection and reconnection behavior can affect power-system transient stability. Calibrating dynamic models of such loads is challenging because treating all associated elements as freely estimable may lead to weakly identified or physically confounded parameterizations. This paper proposes an identifiability-guided calibration framework for a composite load model with separate IT, cooling, and auxiliary branches. A nuisance-projected Fisher-information criterion characterizes the local identifiability of the cooling-motor composition, while a workload non-equivalence result shows that voltage-only recalibration cannot reproduce workload-dependent responses. Guided by these results, a grey-box estimator trained with branch-level supervision learns the workload-to-power relation and the cooling composition, while retaining a prescribed UPS protection law and an externally anchored reconnect-ramp duration. The learned workload relation is then distilled into a closed form for transient-stability simulation. Evaluation using 300,000 MIT Supercloud GPU power-utilization samples and 12,600 IEEE 39-bus fault scenarios yields an aggregate active-power $R^2$ of 0.948, compared with 0.856 for an LSTM baseline. Removing branch-level supervision preserves relatively high aggregate accuracy but substantially degrades cooling-component recovery. Under unseen deep voltage sags, the proposed model achieves a transient $R^2$ of 0.750, compared with 0.033 for the LSTM. Closed-loop simulations further show that cooling composition and protection behavior can affect retained-load states and voltage responses near protection thresholds.

0.20

Co-Optimization of Network Topology and Variable Impedance Devices under Dynamic Line Ratings Using Iterative McCormick Relaxation

eess.SY ·2026-10-27 ·Junseon Park, Hyeongon Park, Rahul K. gupta
benchmark similarity 0.55
Abstract

Grid Enhancing Technologies (GETs), such as Network Topology Optimization (NTO), Dynamic Line Rating (DLR), and Variable Impedance Devices (VIDs) are increasingly deployed in power transmission grids to address congestion and improve grid utilization. However, their growing adoption necessitates coordinated operation to fully exploit their benefits. This paper presents a unified co-optimization framework that integrates NTO, DLR, and VID to alleviate congestion and minimize operational costs. NTO is modeled using a node-breaker formulation to provide enhanced switching granularity, while DLR incorporates weather-dependent parameters, including wind speed and ambient temperature, to dynamically adjust transmission limits. The resulting formulation is a mixed-integer nonlinear program due to power flow constraints with bilinear VID terms, and discrete topology decisions. To improve tractability, we propose using a McCormick relaxation approach to linearize bilinear terms. Furthermore, we propose an iterative refinement of the McCormick relaxation scheme to enhance solution accuracy. The proposed framework is validated through detailed analyses on the IEEE 118-bus system, along with additional case studies on other benchmark systems to assess scalability. Results demonstrate that the proposed approach improves solution accuracy compared to standard McCormick relaxation, achieves solution quality close to the nonlinear formulation, and maintains computational efficiency.

0.29

Expediting AC Contingency Analysis using a Basecase Machine Learning Model

eess.SY ·2026-09-29 ·Md Obaidur Rahman, Vassilis Kekatos
similarity 0.55
Abstract · 10 page, 7 figures

Grid planning and operation under increasingly variable operating conditions require fast and accurate AC power flow (AC-PF) contingency analysis for numerous line outages. While ML models can accelerate these computations, existing approaches often require either training separate models for different contingencies or a single model using data from multiple topologies. Both approaches incur substantial offline data generation and training costs. To address this gap, this work proposes a fixed-point framework that reuses a single ML model trained exclusively on basecase topology data to predict post-contingency AC-PF states under any non-critical single-line outage. We analyze the proposed method's convergence under the DC model approximation and derive its convergence rate in terms of network parameters. As a side result, we show that power transfer distribution factors (PTDFs) for non-critical lines have magnitudes less than one. We further characterize the ML training region to accommodate PF specifications encountered during fixed-point iterations and derive bounds on ML prediction errors for post-contingency state estimates. Numerical tests on a 6,717-bus synthetic Texas system demonstrate convergence across all non-critical single-line outages, with prediction errors remaining close to those of basecase. The proposed framework offers a favorable tradeoff between the speed of DC solvers and Newton-Raphson accuracy.

0.11

Trajectory Sensitivity-Based Dynamic Assessment of an AI Data Center Under Contingencies

eess.SY ·2026-10-07 ·Arnav Bagga, Saskia A. Putri, Abhishek Banerjee, Xiaofan Wu
similarity 0.54
Abstract · 7 pages, 5 figures

Artificial Intelligence (AI) data centers are emerging as converter-dominated, parameter-rich electrical systems whose dynamic response depends on fast workload-driven demand variations, tightly regulated data-hall converters, and coordinated on-site sources. Assessing such systems by repeatedly solving nonlinear time-domain models for every outage, load realization, and parameter perturbation is computationally expensive and provides limited insight into response sensitivity. This paper presents a trajectory sensitivity (TS)-based dynamic assessment framework for a self-contained AI data center supplied by a 2 kV DC microgrid with a grid-tied interface. The model includes time-varying data-hall load profiles, a voltage source converter (VSC), battery energy storage systems (BESS) units, supercapacitors, and synchronous-generation-side sources. For each disturbance, firstly, TS are computed along the nonlinear disturbance trajectory, capturing the local effect of source trips, data-hall outages, converter controls, and load ramps. Later, the computed TS data is used to estimate system trajectories under simultaneous parameter perturbations. Validation against full nonlinear ODE simulations with $\pm 15\%$ perturbations shows close agreement. In addition, the TS-based approach reduces computational time of dynamic-response evaluations from seconds to milliseconds, demonstrating its potential as a scalable screening tool for AI data center dynamics.

0.17