Abstract

Accurate time synchronization is essential for distributed systems. Conventional methods, such as satellite-based synchronization and communication-based approaches, face challenges including signal vulnerability and dependence on communication delay symmetry. This paper proposes a novel time synchronization principle based on traveling wave (TW) measurements in power grids. By leveraging the inherent symmetry of forward and backward TW propagation, the proposed method achieves high-precision time distribution without relying on external time references. The methodology is validated through electromagnetic transient simulations on a modified IEEE 14-bus system. The results demonstrate that under normal conditions, the proposed approach achieves microsecond-level synchronization accuracy. These findings suggest that the TW-based time synchronization principle is a potential alternative to traditional methods, offering improved security and reduced dependence on communication quality.

Comment
6 pages, 4 figures, 4 tables

Closest papers

Nearest neighbours by meaning across the whole index.

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.56
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.28

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.53
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Channel Modeling of Single Wire Earth Return Networks for Narrowband Power Line Communication and Sensing: A Field-Validated High-Frequency Digital Twin

eess.SP eess.SY ·2026-08-21 ·Wania Anoosh, Cagil Ozansoy, Douglas Gomes, Mike Faulkner, Kristi Beqirllari
similarity 0.51
Abstract · 14 pages, 16 figures, 4 tables

Upgrading Single-Wire Earth Return (SWER) networks for smart grid capabilities requires a reliable communications technology. Narrowband Power Line Communication (NB-PLC) is a potential low cost solution. Real-world deployment is challenging due to the severe, frequency-dependent attenuation caused by complex earth-return paths and heterogeneous network infrastructure. To accurately characterize the communication channel, this paper develops a high-frequency (up to 300 kHz) digital twin of an operational SWER network. The digital twin integrates a segment-by-segment transmission line model with Vector Network Analyzer (VNA) measurements of physical grid hardware, replacing standard uniform assumptions with empirical component responses. Parametric sensitivity analysis demonstrates that distributed environmental factors, such as soil moisture and line sag, act as uniform magnitude offsets. Conversely, the conductor's magnetic permeability and local injection-transformer impedances dictate the channel's resonant spectral shape. Furthermore, cross-brand analysis proves that utilizing generic transformer models introduces significant prediction errors, confirming that accurate simulation requires manufacturer- and tap-specific data. Validated against in-situ field measurements from three transmitters, this digital twin replicates the path loss and dominant frequency-selective fading of the physical grid. Yielding a Root Mean Square Error (RMSE) between 4.65 dB and 9.73 dB across the three transmit paths, the model provides a practically reliable framework for deploying NB-PLC across rural SWER infrastructure.

0.33

On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation Assumptions

eess.SP ·2026-11-06 ·Chetan Mishra, Luigi Vanfretti, Jaime Delaree Jr. and, Kevin D. Jones
similarity 0.51
Abstract

Recent work highlights the inadequacy of standard synchrophasors in capturing high-frequency grid dynamics, including data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. This letter shows how synchrophasor ambient data spectrum itself contains information on attenuation, which provides a way to identify critically impacted measurements and potentially estimate and undo the effect. Results are shown for synthetic data as well as actual synchrophasor estimates from digital fault recorders (DFRs) within the Dominion Energy system.

0.14

Dual-Purpose SSB Design for Joint Time-Frequency Synchronization Using Relocated DMRS

eess.SP ·2026-10-15 ·Sadiq Iqbal, Abdelali Arous, Huseyin Arslan
benchmark similarity 0.51
Abstract · 13 pages, 9 figures, transaction

The synchronization signal block (SSB) is designed to synchronize a capable user-equipment (UE) with the base-station (BS) in recent cellular networks. However, the same SSB cannot be utilized by a narrowband, low-complexity, and low-power internet of things (IoT) device for synchronization. To address this limitation, this paper proposes a dual-purpose SSB (DP-SSB) to enable low-complexity IoT synchronization using the existing SSB, while ensuring uninterrupted conventional UE operation. Specifically, selected demodulation reference signal (DMRS) symbols are contiguously mapped to some physical resource blocks (PRBs) in the second and fourth symbols of the DP-SSB. These DMRS symbols are further optimized using a receiver-aware least square (LS) approach to impose a distinct time-domain structure at the output of the IoT front-end. At the IoT receiver, a reduced-rate observation of the DP-SSB is obtained after narrowband filtering and decimation that is exploited for energy detection and sequential time-frequency (TF) synchronization. For the UE, primary synchronization signal (PSS) and secondary synchronization signal (SSS)-based synchronization is preserved, while the effect of relocated DMRS on the channel estimation and physical broadcast channel (PBCH) reception is assessed. The performance of the proposed DP-SSB is evaluated in terms of detection probability, TF synchronization accuracy, IoT receiver computational complexity, and UE-side PBCH decoding. Simulation results validate the analytical detection characterization and demonstrate reliable low-power IoT synchronization performance compared with the benchmark synchronization schemes while maintaining conventional UE operation.

0.26

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.50
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.34

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.49
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

Unifying Power Flow and Electromagnetic Transient Modeling

eess.SY ·2026-09-08 ·Tina Gao, Aayushya Agarwala, Timothy McNamara, Lawrence Pileggi
similarity 0.49
Abstract

Grid tools are separated by timescales: steady-state analysis is performed by power flow (PF), whereas the fastest dynamics are captured by electromagnetic transient (EMT) simulation. Although operating at varying timescales, different tools should produce consistent results when analyzing the same grid conditions. However, the PF steady-state solution does not match the time-to-infinity EMT response. This mismatch exists because simplified device models in PF are inconsistent with the "ground truth" EMT models derived from first principles. As inverter-based resources (IBRs) and data centers strip away inertia and operating reserves, approximations used in PF risk grid security by missing violations. To address this, we introduce a steady-state framework that uses full-physics EMT models for high-fidelity steady-state grid analysis. The challenge lies in systematically formulating algebraic frequency-domain representations of dynamic power devices that are naturally described in state-space form. Our tool, SALT (Steady-state After Last Transients), constructs steady-state representations that exactly capture grid device physics when embedded into transmission networks. The approach exploits the structural properties of power device models and the single-harmonic, balanced nature of the transmission system. Results demonstrate SALT achieves EMT steady-state accuracy while delivering a 1x10^6 times speedup. We demonstrate that SALT can capture security threats in contingency scenarios without exception --- whereas PF-based analyses reported 75% fewer rated line violations, 18% fewer Q-limit violations, and 7% fewer voltage violations.

0.20