CS Paper Radar

Stimulated Oscillations in Renewable Energy Integrated Power Systems - Part I : Mechanism and Analysis Methods

Peng Zhang

eess.SY ·submitted 2026-08-17 13:27 UTC · v1
unusual

Abstract

Oscillation is a critical issue that power systems have long faced. Especially over the past two decades, with the large-scale inte-gration of renewable energy into the grid, oscillation problems have posed a serious threat to the secure operation of power systems. However, the current literature has not fully explained the oscillation mechanism of renewable energy integrated power systems (REIPSs). In this paper, the underlying mechanism of stimulated oscillations is explored, with novel analytical methods proposed. Firstly, it is explained from both mathematical formu-las and physical interpretations that for an oscillation mode characterized by a pair of complex conjugate poles, the oscilla-tion risk under disturbance depends on the relative positional relationship between the corresponding poles and all other poles and zeros on the complex plane, rather than their standalone locations, i.e., the stability perceived by classical theory. Then the underlying mechanism of high amplitude oscillations induced by closely-located poles under even slight disturbance is clarified. On this basis, a theoretical framework for stimulated oscilla-tions applicable to REIPSs, covering its definition, mechanism, and methods, is proposed. Finally, this paper discusses the rela-tionship between the stimulated oscillation theory proposed herein and the classical stability-based theory, revealing that the research findings surpass rather than negate the classical theo-ries.

Comment
Submitted to IEEE Transactions on Power Systems, 8 pages, 9 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Stimulated Oscillations in Renewable Energy Integrated Power Systems - Part II: Methodology of Oscillation Mitigation

eess.SY ·2026-08-30 ·Peng Zhang
similarity 0.80
Abstract · 8 pages, 8 figures

As presented in Part I of this series, closely located poles can produce high-amplitude oscillations even under small perturba-tions, which are referred to as stimulated oscillations. As the second installment of this series, this paper develops a method-ology for stimulated oscillation mitigation. Firstly, the logical relationship between system stability and oscillation risk is in-vestigated, clarifying that stability is neither a necessary nor a sufficient condition for oscillation risk. Secondly, the dominant factors affecting the pole and zero position on the complex plane, as well as their effectiveness and limitations are analyzed. For feedback control systems in particular, the influence of feedback paths on the pole-zero distribution of closed-loop systems is ana-lyzed. On this basis, a methodology for stimulated oscillation mitigation is proposed. Combined with the reduced-order trans-fer function of systems with closely separated poles, the order relation and configuration of poles and zeros for the feedback path transfer function, together with the criteria for gain selec-tion, are elaborated. Finally, a parameter tuning scheme for the poles, zeros and gain of the feedback path transfer function is presented. The proposed methodology for stimulated oscillation mitigation based on feedback control is not restricted to specific devices and can serve as a methodological reference for the design of diverse oscillation suppression schemes.

0.12

DC Voltage Control Dominated Oscillations in Electromechanical Frequency Range - Insights from Synchronous Coefficient Reduction Effect of IBR Plants and Network Interactions

eess.SY ·2026-11-09 ·Qiang Fu, Siqi Bu
top venue similarity 0.51
Abstract

Large-scale integration of inverter-based resources (IBRs) is widely known to cause subsynchronous oscillations. This paper investigates a distinct class of oscillations that occur in the electromechanical frequency range (EFR), referred to as EFOs, and are dominated by the DC voltage control (DVC) loops of grid-following IBRs rather than synchronous generator-like controls or phase-locked loops (PLLs). Although open-loop oscillation modes of DVC loops are subsynchronous, the corresponding closed-loop dominant oscillation mode related to DVC can shift downward into the EFR without retuning the control parameters. This frequency shift is caused by network-mediated interactions among the IBRs, which introduce a negative synchronous coefficient into the DVC oscillation loop. This synchronous coefficient reduction effect (SCRE) becomes stronger as the IBR plant scale increases and/or as the minimum eigenvalue of the network admittance matrix decreases. Furthermore, a complex vector-based stability analysis method is proposed, and a stability criterion for DVC-EFOs is derived. Finally, the analytical conclusions are validated using a practical power system configuration implemented in Simulink. The SCRE differs from traditional explanations, in which the open-loop oscillation modes are already located in the EFR, and provides new insight into DVC-dominated oscillations in the EFR for integration of IBR plants.

0.42

An Analytical Review of Model Order Reduction Methodologies of Converter-Dominated Power Systems for Stability Studies

eess.SY ·2026-10-02 ·Goran Grdenić, Marco Fraccaro, Josipa-Pina Milišić
similarity 0.50
Abstract · 53 pages, 4 figures

The rapid integration of renewable energy sources is transforming modern electric power systems into converter-dominated networks characterized by complex multi-timescale dynamics and new stability interactions over a wide frequency range. Accurate analysis of these phenomena requires high-fidelity models of transmission networks and power electronic converters, which often result in large-scale differential-algebraic systems with significant computational burden. This paper provides an analytical review of model order reduction techniques for converter-rich power systems, with particular emphasis on the key equations employed in the reduction process. Advantages and limitations of commonly used strategies, including timescale-based singular perturbation, projection-based, operator-based, data-driven, and machine-learning based methods, are discussed. The synthesis highlights key challenges related to harmonic interactions and multi-frequency dynamics, and outlines directions for the development of computationally efficient yet dynamically accurate reduced-order models for future power systems.

0.29

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.50
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.22

Source--Grid Coupling in Power System Oscillations: Observational Equivalence, Feedback Detectability, and Modal Interaction

eess.SY eess.SP ·2026-09-17 ·Kai Sun, Bin Wang
similarity 0.50
Abstract · Submitted to IEEE Transactions on Power Systems

The conventional distinction between forced and natural oscillations treats the oscillation source as external to a fixed power-system boundary. This paper develops a coupling-aware dynamical interpretation by explicitly accounting for the directionality of source-grid coupling. It examines when prescribed forcing and a one-way autonomous source are observationally equivalent, and when grid measurements can distinguish the presence of grid-to-source feedback. Matched interface signals yield exact equivalence under the same deterministic grid initial-value problem and measurement map. Bidirectional feedback enables source-grid eigenvalue interaction in the augmented autonomous model, while a reduced two-mode model shows that the interaction depends jointly on loop coupling and complex modal separation. The resulting framework establishes source-grid coupling directionality as a feedback-based dynamical boundary and clarifies when feedback can be inferred from grid-side measurements and why weak feedback may remain unresolved. Simulation studies on a two-area system demonstrate feedback detection within a calibrated source family, while source-model mismatch can be confounded with feedback. A WECC 243-bus system study demonstrates feasibility on a large system and shows that feedback detection need not require exact candidate selection.

0.24

Multi-Period Bilevel Coordination of Primary and Secondary Frequency Regulation for Grid-Forming Battery Energy Storage

eess.SY ·2026-11-04 ·Wenju Shang, Liangliang Hao, Jiangliang Jin, Yunjian Xu
theory similarity 0.49
Abstract

We study the coordination of primary and secondary frequency regulation by grid-forming battery energy storage systems in islanded microgrids. We formulate the coordination as a multi-period bilevel program, in which the upper level schedules secondary regulation setpoints and each lower level computes primary regulation decisions. Using the lower-level Karush-Kuhn-Tucker conditions, we obtain an exact single-level reformulation with complementarity constraints. To address the numerical difficulties introduced by these constraints, we develop a continuation method that couples the complementarity relaxation parameter with the interior-point barrier parameter and warm-starts successive stages. Under the stated boundedness assumptions and with vanishing subproblem residuals, we prove that every accumulation point is feasible and satisfies a first-order stationarity condition for the reformulated problem (C-stationarity). Numerical results for an islanded microgrid show that the proposed method reduces solution time by 89.3% and peak frequency deviation by 0.53% relative to conventional Scholtes relaxation.

0.26

From Rigid to Adiabatic: Canonical Regularization of AC Networks via Action-Angle Variables

eess.SY ·2026-08-29 ·Feng Ji, Lu Gao, Lihui Yang
similarity 0.48
Abstract

Traditional power system analysis relies on timescale separation and the rigid-network assumption, freezing electromagnetic transients into algebraic power-flow equations via Steinmetz's phasor theory. As grid-forming converter penetration increases, magnetic energy dynamics on transmission lines interact with converter control loops on comparable timescales, challenging this rigid-network assumption. Returning to Faraday's law of electromagnetic induction driven by rotating magnetic fields, this paper models the transmission lines' rotating magnetic fields in action-angle canonical coordinates, regularizes the rigid algebraic constraints of power-flow equations into canonical equations on adiabatic symplectic manifolds, and establishes a port-Hamiltonian standard form for AC power grids. Based on the minimal-counterexample principle and using the equal-area criterion's classical two-machine system, this paper reveals a latitudinal instability channel via Bloch-sphere coordinates: Q-V control releases voltage-amplitude freedom, shifting the stability boundary from the equatorial UEP (unstable equilibrium point) to a saddle point, thereby unifying the analytical frameworks of P-delta angle stability and Q-V voltage stability in power system analysis.

0.27

Linear Approximations Provide Rigorous Conditions for Phase Locking in Oscillator Networks and Power Grids

eess.SY nlin.AOmath.OCphysics.soc-ph ·2026-10-17 ·Iva Bačić, Carsten Hartmann, Philipp C. Böttcher, David Gross, Andrea Benigni +1 more
similarity 0.48
Abstract

Synchronization is a fundamental collective phenomenon in many natural and engineered networks. The stable operation of oscillator networks, such as electric power grids, requires phase locking with phase differences across edges below a given threshold. A central question is whether a given network supports such a state. In this contribution, we extend a convex optimization formulation of the nonlinear fixed point equations of the Kuramoto model, that also describe lossless power grids. Based on this formulation, we derive rigorous and tight bounds on the error introduced by an arbitrary approximation of the original model, in particular linear approximations. The bounds yield edge-wise regions of trust around the approximation, within which the true nonlinear solution must lie. They further provide sufficient and necessary conditions for phase locking under prescribed phase difference limits. Numerical experiments show that the bounds are tight over a broad range of parameters.

0.41