Stimulated Oscillations in Renewable Energy Integrated Power Systems - Part II: Methodology of Oscillation Mitigation

Peng Zhang

eess.SY ·submitted 2026-08-30 02:48 UTC · v1

Abstract

As presented in Part I of this series, closely located poles can produce high-amplitude oscillations even under small perturba-tions, which are referred to as stimulated oscillations. As the second installment of this series, this paper develops a method-ology for stimulated oscillation mitigation. Firstly, the logical relationship between system stability and oscillation risk is in-vestigated, clarifying that stability is neither a necessary nor a sufficient condition for oscillation risk. Secondly, the dominant factors affecting the pole and zero position on the complex plane, as well as their effectiveness and limitations are analyzed. For feedback control systems in particular, the influence of feedback paths on the pole-zero distribution of closed-loop systems is ana-lyzed. On this basis, a methodology for stimulated oscillation mitigation is proposed. Combined with the reduced-order trans-fer function of systems with closely separated poles, the order relation and configuration of poles and zeros for the feedback path transfer function, together with the criteria for gain selec-tion, are elaborated. Finally, a parameter tuning scheme for the poles, zeros and gain of the feedback path transfer function is presented. The proposed methodology for stimulated oscillation mitigation based on feedback control is not restricted to specific devices and can serve as a methodological reference for the design of diverse oscillation suppression schemes.

Comment
8 pages, 8 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Stimulated Oscillations in Renewable Energy Integrated Power Systems - Part I : Mechanism and Analysis Methods

eess.SY ·2026-08-17 ·Peng Zhang
unusual similarity 0.80
Abstract · Submitted to IEEE Transactions on Power Systems, 8 pages, 9 figures

Oscillation is a critical issue that power systems have long faced. Especially over the past two decades, with the large-scale inte-gration of renewable energy into the grid, oscillation problems have posed a serious threat to the secure operation of power systems. However, the current literature has not fully explained the oscillation mechanism of renewable energy integrated power systems (REIPSs). In this paper, the underlying mechanism of stimulated oscillations is explored, with novel analytical methods proposed. Firstly, it is explained from both mathematical formu-las and physical interpretations that for an oscillation mode characterized by a pair of complex conjugate poles, the oscilla-tion risk under disturbance depends on the relative positional relationship between the corresponding poles and all other poles and zeros on the complex plane, rather than their standalone locations, i.e., the stability perceived by classical theory. Then the underlying mechanism of high amplitude oscillations induced by closely-located poles under even slight disturbance is clarified. On this basis, a theoretical framework for stimulated oscilla-tions applicable to REIPSs, covering its definition, mechanism, and methods, is proposed. Finally, this paper discusses the rela-tionship between the stimulated oscillation theory proposed herein and the classical stability-based theory, revealing that the research findings surpass rather than negate the classical theo-ries.

0.31

An Analytical Review of Model Order Reduction Methodologies of Converter-Dominated Power Systems for Stability Studies

eess.SY ·2026-10-02 ·Goran Grdenić, Marco Fraccaro, Josipa-Pina Milišić
similarity 0.55
Abstract · 53 pages, 4 figures

The rapid integration of renewable energy sources is transforming modern electric power systems into converter-dominated networks characterized by complex multi-timescale dynamics and new stability interactions over a wide frequency range. Accurate analysis of these phenomena requires high-fidelity models of transmission networks and power electronic converters, which often result in large-scale differential-algebraic systems with significant computational burden. This paper provides an analytical review of model order reduction techniques for converter-rich power systems, with particular emphasis on the key equations employed in the reduction process. Advantages and limitations of commonly used strategies, including timescale-based singular perturbation, projection-based, operator-based, data-driven, and machine-learning based methods, are discussed. The synthesis highlights key challenges related to harmonic interactions and multi-frequency dynamics, and outlines directions for the development of computationally efficient yet dynamically accurate reduced-order models for future power systems.

0.29

Reduced-Order Model Characterization of Nonlinear Sustained Oscillations

eess.SY math.DS ·2026-09-27 ·Kaiyang Huang, Dan Wilson, Kai Sun
similarity 0.53
Abstract

Nonlinear sustained oscillations involving inverter-based resources can happen when device and network interactions produce an attracting limit cycle around an unstable equilibrium. A damping controller must then describe nonlinear dynamics over the region between the two invariant sets, where a local equilibrium linearization can be insufficient. In this paper, a controlled phase--isostable model is first developed on a two-dimensional invariant manifold connecting the equilibrium and the limit cycle. Dynamics on this surface are represented by phase and isostable coordinates, while physical states and control inputs are related to these coordinates through nonlinear reconstruction and response functions. The required functions are computed from connecting trajectories and periodic-orbit data. A control strategy is then designed to provide extra damping while limiting phase distortion. Case studies on a two-area system and an IEEE 39-bus system demonstrate more effective oscillation damping than the compared equilibrium-linearized designs under the same conditions.

0.27

DC Voltage Control Dominated Oscillations in Electromechanical Frequency Range - Insights from Synchronous Coefficient Reduction Effect of IBR Plants and Network Interactions

eess.SY ·2026-11-09 ·Qiang Fu, Siqi Bu
top venue similarity 0.53
Abstract

Large-scale integration of inverter-based resources (IBRs) is widely known to cause subsynchronous oscillations. This paper investigates a distinct class of oscillations that occur in the electromechanical frequency range (EFR), referred to as EFOs, and are dominated by the DC voltage control (DVC) loops of grid-following IBRs rather than synchronous generator-like controls or phase-locked loops (PLLs). Although open-loop oscillation modes of DVC loops are subsynchronous, the corresponding closed-loop dominant oscillation mode related to DVC can shift downward into the EFR without retuning the control parameters. This frequency shift is caused by network-mediated interactions among the IBRs, which introduce a negative synchronous coefficient into the DVC oscillation loop. This synchronous coefficient reduction effect (SCRE) becomes stronger as the IBR plant scale increases and/or as the minimum eigenvalue of the network admittance matrix decreases. Furthermore, a complex vector-based stability analysis method is proposed, and a stability criterion for DVC-EFOs is derived. Finally, the analytical conclusions are validated using a practical power system configuration implemented in Simulink. The SCRE differs from traditional explanations, in which the open-loop oscillation modes are already located in the EFR, and provides new insight into DVC-dominated oscillations in the EFR for integration of IBR plants.

0.42

Guidelines for the implementation of power oscillation damping controllers in power converters

eess.SY ·2026-09-02 ·Javier Renedo, Macarena Martín Almenta, Sergio Martínez Villanueva, Agustín Díaz-García, Antonio Cordón +1 more
similarity 0.51
Abstract

One of the most effective ways to damp electromechanical oscillations in power systems is by means of supplementary controllers attached to the different devices in the power system is by means of power system stabilizers (PSS) in synchronous machines or by means of power oscillation damping (POD) controllers in facilities with power converters. In the recent years, the use of POD controllers in voltage source converters (VSCs) with grid-following (GFL) control has been investigated. Although the potential of POD controllers to help to damp inter-area oscillations in power systems is enormous, their correct implementation is not trivial, because their effectiveness is strongly linked to their settings. This paper provides guidelines for the implementation of POD controllers in power converters for application in real-world power systems. The paper proposes compliance criteria for POD controllers using a synthetic test system and a systematic methodology used in Spanish technical standard for monitoring compliance (NTS), considering practical considerations. The paper also includes numerical examples to illustrate compliance criteria for POD controllers in a synthetic test system. A generic power converter with grid-following (GFL) control is used for the analysis by simulation and POD controllers using modulation of active-power injection (POD-P), reactive-power injection (POD-Q) or both simultaneously (POD-PQ) will be analysed. Results were validated in a large-scale power system. The paper concludes that by using appropriate synthetic systems, methodologies and compliance criteria, POD controllers in power converters could be effective to damp electromechanical oscillation in large-scale power systems.

0.33

Impact of Reduced-Order Modelling on Sum-of-Squares Region-of-Attraction Certification for Grid-Forming and Grid-Following Converters

eess.SY math.OC ·2026-11-10 ·Chenxi Yuan, Jeremy D. Watson, Neville R. Watson
similarity 0.50
Abstract · 13 pages, 5 figures, 3 tables

With the increasing penetration of power-electronic equipment, the transient stability of grid-forming (GFM) and grid-following (GFL) converters is increasingly characterized through the region of attraction (ROA) of the post-fault equilibrium. Sum-of-squares (SOS) programming yields certified inner approximations of the ROA, yet its computational cost grows rapidly with system order. Reduced-order models are therefore widely used to reduce computational cost and, more importantly, to enable analytical investigation. However, ROA analyses based on these models often assume that reproducing the converter's transient response, or retaining more dynamics in the correct time-frame, is sufficient to preserve the ROA of the full-order system. Using time-domain ODE simulations as a reference, the SOS-based ROA of each reduced-order GFM and GFL model is assessed against both its own simulated ROA and that of the corresponding full-order model, thereby separating SOS-induced conservativeness from model-order-induced ROA distortion. The results indicate that increasing reduced-order model complexity does not necessarily improve SOS-based ROA fidelity. In the cases examined, more complex reduced-order models yield lower SOS coverage of the full-order reference ROA, despite closer ODE-boundary agreement in some regions. Model selection should therefore consider both full-order ROA fidelity and certified coverage of the practical operating range, rather than model complexity alone.

0.27

Performance Limits and Tradeoffs of Power Systems Synchronization Recovery in Complex-Frequency Representation

eess.SY ·2026-10-02 ·Xiaoyu Peng, Zelin Sun, Zhongze Li, Feng Liu
theory similarity 0.50
Abstract

Power-system synchronization studies mainly ask whether synchronization can be achieved, whereas a complementary question is how well post-disturbance synchronization recovery can be shaped. In inverter-dominated systems, this recovery involves coupled phase-angle and voltage-magnitude dynamics, for which complex frequency provides a unified representation. This paper establishes a conservation law for synchronization recovery in this representation. For a given system and its initial state, the logarithmic integral of the proposed recovery residual is fixed by the initial contraction rate and the right-half-plane (RHP) zero--pole structure. Hence, synchronization recovery performance cannot be improved uniformly over frequencies and variables unless the budget set by these terms changes; controller tuning that preserves them can only redistribute the residual response across frequencies. The conservation law applies to both linear and nonlinear recovery responses satisfying the mild analyticity conditions. It further yields finite-frequency peak--bandwidth limits and a lower bound on the time-domain integral of squared complex frequency recovery. A system-level extension recovers classical Bode-type sensitivity conservation as an LTI special case. Studies on a heterogeneous IEEE 39-bus system verify the theory.

0.25

Modular Model Order Reduction for Inverter-Based Power Systems with Stability and Accuracy Guarantees

eess.SY ·2026-10-01 ·Hanqing Zhang, Pudong Ge, Mohammad Fahim Shakib, Adrià Junyent-Ferré, Balarko Chaudhuri +3 more
similarity 0.49
Abstract · 10 pages, submitted to IEEE Transactions on Power Systems

This paper proposes a modular model order reduction framework for large-scale power grids integrated with renewable energy sources. The proposed framework has the advantage of reducing individual sub-areas independently while retaining the power grid interconnection structure. Moreover, given a user-defined accuracy specification on the overall reduced-order interconnected power grid, corresponding target specifications for the individual reduced sub-areas are determined: satisfaction of such individual specifications guarantees the overall user-defined accuracy specification, while also preserving the stability of the overall reduced-order interconnected power grid. The proposed framework is validated on a modified IEEE 118-bus system (where synchronous generators have been replaced by inverter-based resources) by assessing the accuracy specification satisfaction of the overall reduced-order interconnected power grid, in terms of frequency response, stability, active power, and sub-synchronous behaviour when injected with disturbances.

0.33